Plan Review Details - Permit 06030227
Plan Review Stops For Permit 06030227
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-04-13 Cont ID  
Sent By lmartine Date 2007-04-13 Time 18:16 Rev Time 0.00
Received By lmartine Date 2007-04-13 Time 18:16 Sent To  
Notes
2007-04-13 18:19:20 
 BUILDING COMMENTS
  
  
  
 PLANS SHALL BE STAMPED BY PALM BEACH COUNTY IMPACT FEE
 OFFICE BEFORE ISSUANCE OF PERMIT.
  
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2007-04-02 Cont ID  
Sent By lmartine Date 2007-04-02 Time 12:07 Rev Time 0.00
Received By lmartine Date 2007-04-02 Time 12:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-12 Cont ID  
Sent By lmartine Date 2007-02-12 Time 17:58 Rev Time 0.00
Received By lmartine Date 2007-02-12 Time 17:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-31 Cont ID  
Sent By amorse Date 2006-07-31 Time 07:58 Rev Time 0.00
Received By amorse Date 2006-07-31 Time 07:58 Sent To PC
Notes
2006-07-31 00:00:00 
  
 DENIED
  
 1) PRODUCT APPROVAL FOR MODIFIED ROOFING
 IS FOR TILE UNDERLAYMENT. PLEASE BE
 AWARE THAT CHOSEN PRODUCT WILL REQUIRE
 ENGINEER OR ARCHITECT TO CALCULATE
 ENHANCED FASTENING FOR THE ATTACHMENT
  
 2) PRODUCT APPROVAL FOR DOOR IS FOR
 FRECH DOOR WITH SIDELITES WHILE DRAWINGS
 SHOW SINGLE METAL DOOR PLEASE CLARIFY
  
 3) PRODUCT APPROVAL FOR TRACO WINDOW HAS
 BEEN REVISED THE NEW NOA# IS 05-0930.03
  
 4) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 *********PLEASE HAVE DESIGNER REVIEW AND
 APPROVE***********
  
 5) PRINTED NAME AND LICENCE # OF
 ARCHITECT THAT SEALS DRAWINGS SHALL
 APPEAR ON TITLE BLOCK PER 61G1-16.004
 FAC
  
 6) PROVIDE WIND DESIGN DATA ON DRAWINGS
 PER 1603.1.4 FBC
  
 7) PLEASE SUBMIT OLD DRAWINGS WITH
 COUNTY IMPACT FEE STAMP OR NEW DRAWING
 WILL REQUIRE RESTAMPING
  
 8) PLEASE SEE OTHER REVIEW COMMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-26 Cont ID  
Sent By amorse Date 2006-04-26 Time 14:04 Rev Time 1.00
Received By amorse Date 2006-04-26 Time 14:04 Sent To PC
Notes
2006-04-26 00:00:00 
  
 DENIED
  
 1) NOTES 1,2,4,6,&7 FROM THE FIRST
 REVIEW WERE NOT ADDRESSED
  
 2) PRODUCT APPROVALS REQUIRE 2 COPIES OF
 BOTH THE FLORIDA STATE APPROVAL SHEETS
 AND THE NOA OR EVALUATION REPORT THAT
 THE STATE USED FOR THE APPROVAL (SEE THE
 JELD-WEN APPROVAL THAT WAS PRINTED FOR
 YOU). THE OTHER 2 PRODUCT APPROVALS DO
 NOT HAVE STATE APPROVAL BUT ARE IN OUR
 SYSTEM AS LOCAL PRODUCT APPROVALS BUT 2
 COPIES ARE REQUIRED AND ALL COPIES ARE
 REQUIRED TO BE APPROVED BY THE DESIGNER
  
 3) THE SIDE ELEVATION SHOWS A NEW BUR
 ROOF AND AS SUCH REQUIRES THE PRODUCT
 APPROVALS
  
 4) NOTE 4 IS A REQUIRED DETAIL FOR
 RESIDENTIAL STRUCTURAL DRAWINGS PER 2004
 FBC 106.3.5.4(6)
  
 5) NOTE 6 SHOW HOW THE NEW FRAMED WALL
 WILL BE ATTACHED TO THE EXISTING WALL
 (DETAIL "A")
  
 6) NOTE 7 SHOW FRAMING DETAILS AT WINDOW
 OPENING THAT PROVIDES ALLOWANCE FOR
 SHUTTER ATTACHMENT
  
 7) TITLE BLOCK SHALL CONTAIN ARCHITECTS
 LICENCE NUMBER PER 61G1-16.004 F.A.C.
  
 8) SUBMIT NEW REVISED COPIES OF DRAWINGS
 WITH CORRECTIONS, NO HAND WRITTEN
 COMMENTS OR WHITEOUT ACCEPTED. REMOVE
 ALL NOTES AND CLOUDS THAT ARE NOT
 REQUIRED ON DRAWINGS. SUBMIT ORIGINAL
 DRAWING AS COUNTY IMPACT FEES STILL NEED
 TO BE ATTACHED TO THE NEW DRAWINGS
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-05 Cont ID  
Sent By amorse Date 2006-04-05 Time 12:19 Rev Time 1.00
Received By amorse Date 2006-04-05 Time 12:19 Sent To PC
Notes
2006-04-05 00:00:00 
  
 DENIED
  
 1) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 2) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 NOTE #1 PRODUCT APPROVALS ARE REQUIRED
 FOR WINDOWS,DOORS,ROOFING,ETC. NOTE #2
 APPROVED BY ARCHITECT.
  
 3) DRAWINGS SHALL REFERENCE 2004 FBC AND
 APPROPRIATE SECTIONS
  
 4) SHOW WALL SECTION TO DETAIL ROOF
 DIAPHRAM, OVERHANG SIZE, MAKE UP OF
 HEADER, MONOLITHIC SLAB DESIGN, ETC.
  
 5) SUBMIT FOUNDATION PLAN TO SHOW
 NECCESSARY DETAILS, CONNECTION TO
 EXISTING BUILDING, ETC.
  
 6) SUBMIT DETAIL 'A' WALL CONNECTION TO
 EXISTING BUILDING
  
 7) SUBMIT DETAILS FOR FRAMING AT
 OPENINGS THAT ALLOW ADEQUATE BACKING FOR
 ATTACHMENT OF SHUTTERS
  
 8) NOTE #5 REFERENCES HETAL 16 WHICH ARE
 IMBED ANCHORS PLEASE CLARIFY
  
 9) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC
  
 10) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-20 Cont ID  
Sent By btrobaug Date 2007-03-20 Time 10:30 Rev Time 0.50
Received By btrobaug Date 2007-03-20 Time 10:30 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-12-20 Cont ID  
Sent By btrobaug Date 2006-12-20 Time 13:26 Rev Time 0.50
Received By btrobaug Date 2006-12-20 Time 12:49 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-28 Cont ID  
Sent By dpalmer Date 2006-07-28 Time 16:06 Rev Time 0.00
Received By dpalmer Date 2006-07-28 Time 16:06 Sent To B
Notes
2006-07-28 00:00:00*** UNSAT ***
  
 THIS REVIEW IS BASE DON PLANS SUBMITTED
 DATED 7/3/06
  
 1) NOTE: PLEASE SEE FAC61G1-16.004 FOR
 MISSING PRINTED NAME AND LICENSE NUMBER
 FOR THE ARCHITECT OF RECORD ON TITLE
 BLOCKS.
  
 2) NOTE: PLEASE SEE PLANS SHALL
 REFERENCE THE CURRENT CODE UNDER
 ADOPTION BY THE STATE OF FLORIDA. PLEASE
 KNOW, PLANS STATE THE "LATEST EDITION",
 HOWEVER THE LATEST EDITION WHICH IS OUT
 IS NOT YET ADOPTED.
  
 ** PLEASE SEE PLANS ARE COMING BACK FOR
 ZONING COMMENTS PLEASE ADDRESS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2006-04-26 Cont ID  
Sent By btrobaug Date 2006-04-26 Time 06:50 Rev Time 0.33
Received By btrobaug Date 2006-04-26 Time 06:46 Sent To B
Notes
2006-04-26 00:00:00 
 GIVEN TO ME BY MICHELLE TO LOOK AT AGAIN
 HAVING FOUND THERE IAS A SECOND
 ELECTRICAL SERVICE AND WATER METER
 SERVING THE RESIDENCE. THE ADDITION
 PROPOSED IS NOT IN VIOLATION OF THE NEC
 AND THEREFORE A ZONING AND BUILDING
 ISSUE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-23 Cont ID  
Sent By btrobaug Date 2006-03-23 Time 14:55 Rev Time 0.50
Received By btrobaug Date 2006-03-23 Time 14:55 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 11:34 Sent To Z
Notes
2007-04-12 11:34:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-03-19 Cont ID  
Sent By adarroug Date 2007-03-19 Time 11:51 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 11:51 Sent To E
Notes
2007-03-19 11:51:20TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 13:52 Rev Time 0.00
Received By adarroug Date 2007-03-09 Time 13:52 Sent To Z
Notes
2007-03-09 13:52:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 11:48 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 11:48 Sent To E
Notes
2006-12-18 11:48:36TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-11 Cont ID  
Sent By adarroug Date 2006-12-11 Time 10:18 Rev Time 0.00
Received By adarroug Date 2006-12-11 Time 10:17 Sent To Z
Notes
2006-12-11 10:18:15TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 17:57 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 17:57 Sent To E
Notes
2006-07-27 00:00:00TO "E" BOX/RESUB-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 13:38 Rev Time 0.00
Received By adarroug Date 2006-07-21 Time 13:38 Sent To Z
Notes
2006-07-21 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 16:06 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 16:06 Sent To Z
Notes
2006-04-14 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 15:49 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 15:49 Sent To E
Notes
2006-03-21 00:00:00ELEC INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-05 Time   Rev Time 0.00
Received By adarroug Date 2006-03-08 Time 15:13 Sent To  
Notes
2006-03-08 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-23 Cont ID  
Sent By tgordon Date 2006-03-23 Time 15:30 Rev Time 0.15
Received By tgordon Date 2006-03-23 Time 15:30 Sent To B
Notes
2006-03-23 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop Z ZONING
Rev No 6 Status P Date 2007-04-12 Cont ID  
Sent By jroach Date 2007-04-12 Time 18:25 Rev Time 0.00
Received By jroach Date 2007-04-12 Time 18:25 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2007-03-16 Cont ID  
Sent By jroach Date 2007-03-16 Time 16:44 Rev Time 0.00
Received By jroach Date 2007-03-16 Time 16:44 Sent To I
Notes
2007-03-16 16:47:36***FAILED***
  
 1)THE DIMENSIONS (I.E. SETBACKS, ETC.) ON THE SURVEY
 PREPARED BY LITTON LAND SURVEYORS DOES NOT MATCH THE
 SITE PLAN ON A-1, NOR THE PREVIOUSLY-SUBMITTED SURVEY.
 ALL PLANS SHALL BE CONSISTENT, AND PLEASE WRITE VOID ON
 ANY PLANS THAT ARE NO LONGER BEING USED AS PART OF THE
 PERMIT PACKAGE.ONE SET OF VOIDED SHEETS SHALL BE
 RETAINED IN THE PACKAGE FOR REFERENCE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status F Date 2006-12-16 Cont ID  
Sent By mmclean Date 2006-12-16 Time 13:55 Rev Time 0.00
Received By mmclean Date 2006-12-16 Time 13:55 Sent To I
Notes
2006-12-16 14:00:11DENIED,
 1.FLOOR PLANS SUBMITTED A-3 DOES NOT MATCH PLANS FOR
 A-2.A-3 SHOWS ONLY ONE DOOR FOR INTERIOR ACCESS FROM
 THE EXISTING UTILITY ROOM TO THE NEW STRUCTURE WITH
 SOLID WALLS AND WINDOWS.A-2 SHOWS INTERIOR ACCESS
 FROM THE UTILITY ROOM (DOOR) AND FROM THE BATHROOM WITH
 A POCKET DOOR, BUT A-3 SHOWS A SOLID WALLS AND WINDOWS.
 PLEASE CLARIFY.
 2. SITEPLAN CANNOT BE USED FOR REVIEW, PLANS DOES NOT
 PROVIDE ALL INFORMATION NEEDED TO COMPLETE REVIEW,
 SURVEY WILL BE USED FOR REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 3 Status F Date 2006-07-23 Cont ID  
Sent By mmclean Date 2006-07-23 Time 15:53 Rev Time 0.00
Received By mmclean Date 2006-07-23 Time 15:53 Sent To I
Notes
2006-07-23 00:00:00DENIED,
 1. PLEASE PROVIDE A COPY OF THE CURRENT
 SURVEY.
 2. MUST PROVIDE A COMPLETE FLOOR PLAN OF
 THE EXISTING STRUCTURE AND PROPOSED
 ADDITION. THE FLOOR PLANS MUST IDENTIFY
 ALL ROOMS AND SHOW INTERIOR ACCESS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2006-04-25 Cont ID  
Sent By mmclean Date 2006-04-25 Time 15:42 Rev Time 0.00
Received By mmclean Date 2006-04-25 Time 15:42 Sent To E
Notes
2006-04-25 00:00:00DENIED.
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE PROPOSED WORK (ONLY 1
 COPY WAS SUBMITTED).
 2. NEED TO PROVIDE TWO COPY OF A
 COMPLETE FLOOR PLAN SHOWING THE INTERIOR
 ACCESS TO THE PROPOSED ADDITION TO
 EXISTING STRCTURE. FLOOR PLANS MUST SHOW
 ALL ROOMS & KITCHEN/S.
 3. ZONED SF7. ONLY ALLOWED TO HAVE ONE
 COOKING FACILITY/ONE ELECTRICAL
 METER/ONE WATER METER FOR 1 SINGLE
 FAMILY DWELLING.
 4. SHED MUST BE REMOVED AS INDICATED ON
 SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-17 Cont ID  
Sent By mmclean Date 2006-03-17 Time 07:41 Rev Time 0.00
Received By mmclean Date 2006-03-17 Time 07:41 Sent To I
Notes
2006-04-25 00:00:004/25/06 PER THE APPLICANT FOR A RENTAL
 LICENSE THERE ARE TWO KITCHEN AND METER.
  
  
2006-03-17 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE PROPOSED WORK
 2. NEED TO PROVIDE TWO COPY OF A
 COMPLETE FLOOR PLAN SHOWING THE INTERIOR
 ACCESS TO THE PROPOSED ADDITION TO
 EXISTING STRCTURE.
 3. THE SITEPLAN PROVIDED IS NOT CLEAR
 FOR A REVIEW (DOES NOT SHOW SETBACKS OF
 THE EXISTING & NEW) NEED TO SHOW THE
 STREET OF LOCATION.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720