Plan Review Details - Permit 06030218
Plan Review Stops For Permit 06030218
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-05-17 Cont ID  
Sent By amorse Date 2006-05-17 Time 11:08 Rev Time 0.50
Received By amorse Date 2006-05-17 Time 11:08 Sent To PC
Notes
2006-05-17 00:00:00 
  
 **************REVISION****************
  
 DENIED
  
 1) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 2) PLYWOOD ATTACHMENT DOES NOT MEET THE
 MINIMUM REQUIREMENTS AS SET FORTH IN
 TABLE 2304.9.1 FBC
  
 3) FASTENER SPACING FOR ZONE 1 SHALL NOT
 BE LESS THAN SPECIFIED IN THE NOA. THE
 ENHANCEMENT OF FASTENERS IS ONLY
 REQUIRED FOR ZONE 2 PERIMETER AND ZONE 3
 CORNER
  
 4) RAS117 10.4.5, ALL FRACTIONS ARE TO
 ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
  
 5) THE FASTENING PATTERN SHOWN
 GRAPHICALLY ON THE RAS 117 CALCULATIONS
 ARE NOT CORRECT.IF YOU DO NOT UNDERSTAND
 THIS, SEE RAS117 AND THE EXAMPLE
 CALCULATION IN REGARDS TO DETERMINING
 HOW MANY FASTENERS PER SQUARE.
  
 6) THE SIGNATURES APPEAR TO BE A
 PHOTOCOPY. ORIGINAL WET SIGNATURE
 REQUIRED PER FBPE.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-08 Cont ID  
Sent By amorse Date 2006-03-08 Time 14:02 Rev Time 0.50
Received By amorse Date 2006-03-08 Time 14:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-07 Cont ID  
Sent By amorse Date 2006-03-07 Time 13:16 Rev Time 0.50
Received By amorse Date 2006-03-07 Time 13:16 Sent To PC
Notes
2006-03-07 00:00:00 
  
 DENIED
  
 1) PERMIT APPLICATION SHALL CONTAIN THE
 FOLLOWING INFORMATION: MEAN ROOF HEIGHT,
 SQ.FT. OF EACH TYPE OF ROOF, PITCH OF
 ANY SLOPED ROOF, DECK TYPE AND IF
 INSULATED OR NON-INSULATED
  
 2) PRODUCT APPROVALS REQUIRE THE FLORIDA
 COVER SHEET AND THE NOA THAT WAS USED IN
 THE APPROVAL OF THE PRODUCT
  
 3) THE MODIFIED PRODUCT THAT WAS CHOSEN
 ALL ARE FOR INSULATED WOOD DECK,
 INSULATION WAS NOT INDICATED ON THE
 APPLICATION PLEASE CLARIFY
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 14:12 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 14:12 Sent To B
Notes
2006-06-05 00:00:00TO "AMORSE" DESK/RESUB
 6/5/06-PLANS TAKEN OUT OF
 REVIEW-CONTRACTOR SUBMITTED WRONG INFO