Plan Review Details - Permit 06030097
Plan Review Stops For Permit 06030097
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-03-29 Cont ID  
Sent By lursu Date 2006-03-29 Time 09:32 Rev Time 0.00
Received By lursu Date 2006-03-29 Time 09:28 Sent To  
Notes
2006-03-29 00:00:00OWNER'S INFO HAS BEEN CHANGED AT THE
 PROPERTY FILE LEVEL,HOWEVER THE OWNER'S
 ADDRESS HAS BEEN CHANGED AT THE PERMIT
 LEVEL.THE REASON OF CHANGING INFO IS
 BECAUSE THE PROPERTY HAS CHANGED OWNERS
 IN FEB 06 AND THE CONTRACTOR REQUESTED
 THIS BASED ON THE PROOF OF OWNERSHIP.LU

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-10-25 Cont ID  
Sent By mjacobs Date 2006-10-25 Time 10:09 Rev Time 0.00
Received By mjacobs Date 2006-10-25 Time 07:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-10-19 Cont ID  
Sent By mjacobs Date 2006-10-19 Time 18:02 Rev Time 0.00
Received By mjacobs Date 2006-10-19 Time 17:30 Sent To PC
Notes
2006-10-19 18:01:00 
  
 BUILDING PLAN REVIEW
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEWREV. 1ST
 ACTION: DENIED
  
 1) ALL CHANGES WHICH WERE MADE TO THE DRAWINGS SHALL BE
 CLOUDED WITH THE REVISION NUMBER. THIS INFORMATION WILL
 SPEED UP THE REVIEW PROCESS. SHOW CLEARLY WHERE THE
 CHANGES WERE MADE.
  
 2) 61G15-23.002. (2) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZE ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER,AS WELL AS, THE NAME ADDRESS, AND
 CERTIFICATE OF AUTHORIZATIONNUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-12 Cont ID  
Sent By mjacobs Date 2006-06-12 Time 14:05 Rev Time 0.00
Received By mjacobs Date 2006-06-10 Time 10:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-31 Cont ID  
Sent By mjacobs Date 2006-05-31 Time 16:41 Rev Time 0.00
Received By mjacobs Date 2006-05-30 Time 10:36 Sent To  
Notes
2006-05-30 00:00:00 
 1) SUBMIT DRAWINGS SHOWING THE PREVIOUS
 LAYOUT OF THE BUILDING. SHEET'ET.1' HAS
 NO LAYOUT OF THE PREVIOUS DESIGN.
  
 2) WPB AMMENDMENTSS TO FBC 106.3.3 THOSE
 PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FOR FURTHER
 INFORMATION SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTW WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. ALL STATE WIDE PRODUCT APPROVAL
 NEEDS THE STATE COVER SHEETS. NOTE: SOME
 THE PRODUCT APPROVAL SUBMITTED HAVE NO
 STATE COVEER SHEETS AND NEED THE
 APPROVAL BY THE DESIGNER IN WRITING.
 EACH PRODUCT APPROVAL NEEDS IT'S OWN
 COVER SHEET. ONE SET WILL BE FILED FOR
 RECORD AND THE OTHER SET WILL BE GIVEN
 TO THE CONTRACTOR.
  
 3) THE DEMO NOTE "B" ON SHEET A.O STILL
 SHOWS THE DOORS BEING REMOVED AND THE
 OPENING FRAME IN COMPLETELY. THE
 INFORMATION NEEDS TO INDICATE THE NEW
 IMPACT DOORS.
  
 4) IF THE WINDOWS AND DOORS WERE CHANGED
 THE PRODUCT APPROVALS SHALL BE SUBMITTED
 FOR REEVIEW FOR THE ONES WHICH WERE
 CHANGED.
  
 5) THE LEVEL OF ALTERATION INDICATED ON
 THE DRAWINGS STATES LEVEL ONE. THIS IN
 INCORRECT. SEE FLORIDA EXISTING BUILDING
 CODE SEC.303 AND SEC.304 FOR THE
 DIFFERENT TYPES OF ALTERATIONS.
  
 6) 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34 INCHES (865 MM) IN
 HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTER
 WHICH IS 60 INCHES (1525 MM) IN LENGTH
 MINIMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN
 THE SAME AREA.
  
 7) THE DOOR NUMBERS ON THE DOOR SCHEDULE
 AND THE FLOOR SHALL CORRESPOND WITH EACH
 OTHER. SOME OF THE DOORS ON THE FLOOR
 PLAN DON'T HAVE ANY NUMBER. ON THE
 SECOND FLOOR BETWEEN THE CONFERENCE
 ROOOM AND THE TWO OFFICES, THERE ARE TWO
 POCKET DOORS WHICH ARE NOT NUMBERED OR
 INDICATED ON THE DOOR SHCEDULE.THESE
 DOORS SHALL BE NOTED ON THE PLANS AND
 DOOR SCHEDULE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-21 Cont ID  
Sent By mjacobs Date 2006-04-21 Time 13:28 Rev Time 0.00
Received By mjacobs Date 2006-04-19 Time 17:39 Sent To  
Notes
2006-04-19 00:00:001) SUBMIT DRAWINGS SHOWING THE PREVIOUS
 LAYOUT OF THE BUILDING. SEE FBC.106.3.5
  
 2) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 3)THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
 FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE
 REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE.
 ALL STATE WIDE PRODUCT APPROVAL NEEDS
 THE STATE COVER SHEETS. PRODUCT
 APPROVALS ARE REQUIRED FOR DOORS/GLASS
 BLOCK/WINDOWS ETC.
  
 4)EXISTING BUILDING CODE. 501.2
 CONFORMANCE.
 AN EXISTING BUILDING OR PORTION THEREOF
 SHALL NOT BE ALTERED SUCH THAT THE
 BUILDING BECOMES LESS SAFE OR ENERGY
 EFFICIENT THAN ITS EXISTING CONDITION.
 IF IN THE ALTERATION THE CURRENT LEVEL
 OF SAFETY OR SANITATION IS TO BE
 REDUCED, THE PORTION ALTERED SHALL
 CONFORM TO THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. SEE
 DEMO NOTES 'B' DOOR #114.
  
 5)11-4.11 PLATFORM LIFTS (WHEELCHAIR
 LIFTS). 11-4.11.1 LOCATION.
 PLATFORM LIFTS (WHEELCHAIR LIFTS)
 PERMITTED BY SECTION 11-4.1 SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION
 11-4.11.
 11-4.11.2 OTHER REQUIREMENTS.
 IF PLATFORM LIFTS (WHEELCHAIR LIFTS) ARE
 USED, THEY SHALL COMPLY WITH SECTIONS
 11-4.2.4 , 11-4.5 , 11-4.27 , AND ASME
 A17.1, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS , SECTION XX, 1990. 11-4.11.3
 ENTRANCE. IF PLATFORM LIFTS ARE USED
 THEN THEY SHALL FACILITATE UNASSISTED
 ENTRY,
 OPERATION, AND EXIT FROM THE LIFT IN
 COMPLIANCE WITH SECTION 11-4.11.2 .
  
 6) 1607.7.1 HANDRAILS AND GUARDS .
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE
 DESIGNED TO RESIST A LOAD OF 50 PLF
 (0.73 KN/M) APPLIED IN ANY DIRECTION AT
 THE TOP AND TO TRANSFER THIS LOAD
 THROUGH THE SUPPORTS TO THE STRUCTURE.
 SUBMIT THE INFORMATION FOR THE GLASS AT
 THE RAILING.
  
 7) INDICATE THE CLEAR FLOOR SPACE FOR
 THE WATER CLOSET. SEE 11-4.16.2.
 CLEAR FLOOR SPACE FOR THE LAVATORY IS
 REQUIRED AND ALL OTHER DETAILS. SEE
 11-4.19.3 FOR MORE INFORMATION.
  
 8) SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24 .
  
 9)704.8 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED OR
 PROTECTED OPENINGS PERMITTED IN AN
 EXTERIOR WALL IN ANY STORY SHALL NOT
 EXCEED THE VALUES SET FORTH IN TABLE
 704.8 . WHERE BOTH UNPROTECTED AND
 PROTECTED OPENINGS ARE LOCATED IN THE
 EXTERIOR WALL IN ANY STORY, THE TOTAL
 AREA OF THE OPENINGS SHALL COMPLY WITH
 THE FOLLOWING FORMULA:
  
 10) THE DIMENTION FOR THE WIDTH OF
 STAIRS ON THE FIRST FLOOR AND THE SECOND
 FLOOR DONOT MATCH. PLEASE CLARIFY.
  
 11) FIRE SUPRESSION SYSTEM DRAWINGS IS
 REQUIRED FOR REVIEW BEFORE PERMIT CAN BE
 ISSUED.
  
 12) INDICATE THE CORRECT FLOOD ZONE ON
 THE DRAWINGS. THE IS NO "X" ZONES IN THE
 CITY OF WEST PALM.
  
 13) INFO. ONLY: THE AREA REFERED TO AS A
 MEZZANIE EXCEEDS THE ONE-THIRD
 REQUIREMENT OF THE TOTAL FLOOR AREA.
 THEREFORE, THE AREA WILL BE CONSIDER AS
 A SECOND FLOOR. THE TYPE OF CONSTRUCTION
 INDICATED ON THE DRAWINGS IS TYPE IIA
 SPRINKLED. THE FLOOR OF A TYPE IIA
 BUILDING REQUIRES A ONE-HOUR RATING.SEE
 FBC.TABLE 601. HOWEVER, BUSINESS LESS
 THAN TWO STORY WITH 9000SF CAN BE TYPE
 VB CONSTRUCTION WHICH IS THE MINIMUM
 CONSTRUCTION TYPE. TYPE VB CONSTRUCTION
 HAS A 'O' FLOOR RATING. WITH A TYPE IIA
 CONSTRUCTION THE STAIRWAYS SHALL BE
 ENCLOSE WITH A ONE-HOUR RATED WALL.
  
 14) WHAT TYPE OF BAR WILL BE WILL BE
 INSTALL AT THIS BUSINESS. ALSO INDICATE
 THE TYPE OF SERVICES THE OFFICES WILL
 PROVIDE. WILL THERE BE SEATING AT THE
 BAR AREA? PLEASE SHOW ALL THIS
 INFORMATION ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
 FAX:(561)805-67312
 [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-10-21 Cont ID  
Sent By dpalmer Date 2006-10-21 Time 14:42 Rev Time 0.00
Received By dpalmer Date 2006-10-21 Time 14:26 Sent To PC
Notes
2006-10-21 14:43:46REDLINED 110.26 FOR GUTTER SHOWN BELOW SERVICE MAIN,
 MIN 6" . ETC

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 15:39 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 20:51 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 20:26 Sent To M
Notes
2006-08-07 00:00:00** UNSAT **
  
 1) NOTE: PLEASE COMPLETE PANEL LOADS ON
 SUB PANEL SPLP.
 PLEASE SEE 220.12B FOR LOADS FOR TRACK
 LIGHTING. PELAS ADJUST CIRCUITING AS
 NEEDED.
 220, 215.3, 215.5
  
 2) NOTE: PLEASE SEE SPLP, NOW MENTIONS A
 "SERVER" AND SHOWS THIS IS MAY APPEAR TO
 BE AN "IT" ROOM. PLEASE SEE NEC 645 IF
 THIS ROOM IS AN IT ROOM. PLEASE SEE
 NFPA-75. PLEASE SPECIFY ON PLANS IF NOT
 AN IT ROOM AND DOES NT MEET NFPA-75
 REQUIREMENTS.
  
 3) NOTE: PLEASE SE SPLP SHOWS A LOADOF
 6.5 A'S FOR CIRCUITS #2, UNCLEAR WHERE
 THIS LOAD COMES FROM AT THIS TIME AS
 THIS IS A DEDICATED CIRCUIT UNLESS THIS
 ALSO FEEDS SOMETHING ELSE.
  
 4) NOTE: PLEASE SEE VALUE FOR INCREASED
 SCOPE OF WORK SHALL BE ADJUSTED. PLEASE
 ALSO SEE THE ORIGINAL APPLIED VALUE WAS
 137K .
 FBC 108.3
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-08 Cont ID  
Sent By dpalmer Date 2006-06-08 Time 07:35 Rev Time 0.00
Received By dpalmer Date 2006-06-08 Time 06:58 Sent To B
Notes
2006-06-08 00:00:00STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-01 Cont ID  
Sent By dpalmer Date 2006-06-01 Time 07:25 Rev Time 0.00
Received By dpalmer Date 2006-06-01 Time 06:11 Sent To  
Notes
2006-06-01 00:00:00IN ELEC FOR REVIEW.
 ********* UNSAT ************
  
  
 ** PLEASE SEE SOME ITEMS FROM FIRST
 REVIEW AND NEW ITEMS DUE TO CHANGEES IN
 PLANS.
  
  
 1) NOTE: PLEASE SEE PLANS REFERENCE
 "PALM BEACH COUNTY LOCAL AMENDMENTS" ON
 E.0. PLEASE KNOW, THIS WORK IS LOCATED
 IN THE CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE A VD CALCULATION WAS
 PROVIDED FOR THE MAIN SEC'S, HOWEVER
 COULD NOT LOCATE ANY WORST CASE FOR
 BRANCH CIRCUITS PER FBC CHAPTER 13,
 13-413.1ABC.1.2
  
 3) NOTE: PLEASE SEE A COMPLETELY NEW
 SERVICE IS NOT SHOWN, PLEASE CLARIFY
 "GUTTER" NOW SHOWN ON THE LOAD SIDE OF
 THE METER AND NEW MAIN?
 PLEASE SEE RISER NEEDS TO INDICATE THE
 EXISTING SERVICE BEING REMOVED AND NEW
 SERVICE ONLY.
 PLEASE ALSO CORRELATE WITH PLANS, AS
 PLANS DONOT INDICATE MAINS OR
 LOCATIONS.
 UNABLE TO VERIFY SERVICE MEETING 230.2,
 230.70,230.72 ETC.
  
 4) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL SERVICE EQUIPMENT. PLEASE SEE A NEW
 MAIN IS NOW SHOWN, HOWEVER NO RATING(S)
 ARE INDICATED. 110.9.215.5
  
 5) NOTE: PLEASE SEE CONNECTION LOCATIONS
 FOR THE GROUNDING ELECTRODE CONDUCTOR
 NEEDS TO BE VERIFIED AS IT IS SHOWN IN
 TWO LOCATIONS?
 PLEASE SEE 250.24B,250.6.
  
 6) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO THE
 PANELS.
 250.110,250.122,250.24, ETC
  
 7) NOTE: PLEASE SEE PREVIOUS PLANS
 INDICATED ALL CONTINUOUS LOADS AT 125%,
 HOWEVER NOW THIS HAS BEEN REMOVED??
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%.
 215.3,230.42 ETC.
  
 *** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 SUBMIT THE OLD/VOIDED SHEETS SEPARATELY
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-29 Cont ID  
Sent By dpalmer Date 2006-03-29 Time 20:17 Rev Time 0.00
Received By dpalmer Date 2006-03-29 Time 18:18 Sent To  
Notes
2006-03-29 00:00:00IN ELEC FOR REVIEW
 ******* UNSAT ********
  
 1) NOTE: PLEASE SEE ADDRESSING ON TITLE
 BLOCK FOR ENGINEERING FIRM SHALL
 CORRELATE WITH THE STATE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION. (
 DBPR).
 PLEASE SEE ADDRESS ON SITE LIST BUSINESS
 IN WELLINGTON.
 PLEASE ADJUST.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENTS IS
 MADE BY OTHER TRADES.
 FAC 61G15-23.002
  
 2) NOTE: PLEASE SPECIFY THE FOLLOWING
 CURRENT CODES IN EFFECT.
 NFPA-70 2002
 NFPA-101 2003
 NFPA-72, 2002.
 PLEASE ADJUST ANY CODES REFERENCED ON
 PLANS AS NEEDED.
  
 3) NOTE: PLEASE KNOW, WE ARE CURRENTLY
 UNDER THE 2004 FBC.
 PLEASE SEE CHAPTER 13, FOR ALL NEW
 REQUIREMENTS FOR COMMERICAL BUILDINGS
 AND THE ENERGY CODE.
 PLEASE PROVIDE A WORST CASE SCENERIO FOR
 VOLTAGE DROP. 13-413.1ABC.1.2
 PLEASE PROVIDE AUTOMATED LIGHTING
 CONTROL SYSTEM AS REQUIRED PER
 13-415.1.ABC.1.1
 PLEASE PROVIDE COMPLETE SCHEDULING WITH
 THAT SYSTEM AND TIME OF USE AND MAX TIME
 ALLOWED.
 PLEASE PROVIDE THE ACCESSIBLE LOCATIONS
 FOR OVERIDES.
 PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE
 CONTROL FOR AREAS WITH PARTITION WALLS.
 PLEASE KNOW, THESE DEVICES SHALL BE
 CAPABLE OF OVER-RIDING THE LIGHTING
 CONTROL SYSTEM, WITH EXCEPTIONS ALLOWED
 FOR TIMES, OCCUPANCY ETC.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM
 WIRING.
 PLEASE SUBMIT SPECS/MANUFACTURES SUT
 SHEETS FOR PROPOSED SYSTEM.
  
 4) NOTE: PLEASE SEE SERVICE AS SHOWN ON
 RISER WILL NOT BE PERMITTED.
 PLEASE PROVIDE INFORMATION ON ANY
 EXISTING SERVICE, MAINS ETC.
 IF OLD SERVICE IS BEING REMOVED, PLEASE
 INDICATE. 215.5
 PLEASE SEE MAINS ARE NOT GROUPED AS
 REQUIRED PER 230.72
 PLEASE SEE THE NEW "FUTURE" TENANT MAIN
 AND METER WILL NOT BE PERMITTED AS SPACE
 DOES NOT ALLOW FOR ANY FUTURE TENANT
 SEPARATION AT THIS TIME. ANY FUTURE
 SERVICE, MAINS ETC WILL BE REVIEWED AT
 THAT TIME BASED ON PLANS, FIRE
 SEPARATIONS, OCCUPANCY ETC.
 215.5, 230.2
  
 5) NOTE: PLEASE SEE MIN GUTTER
 CALCULATIONS SHALL BE PROVIDED AS GUTTER
 SIZE SHOWN FOR SEC'S AND TAPS DO NOT
 APPEAR TO MEET MININUM SIZE PER
 366.6,314.40 FOR MIN TURNING RADIUS )IF
 APPLICABLE).
  
 6) NOTE: PLEASE SEE 250.66 FOR MINUNUM
 SIZING OF THE GROUNDING ELECTRODE
 CONDUCTOR.
 (2/0)
  
 7) NOTE: PLEASE SEE 2002 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS.
  
 8) NOTE: PLEASE SEE COMMENTS WITH
 RESPECT TO SEPARATION FROM A
 MERCHANTILE/(BAR) AND BUS OCCUPANCY.
 THIS IS NOT AN ELECTRICAL COMMENT,
 HOWEVER MAY AFFECT ELECTRICAL PLANS.
  
 9) NOTE: PLEASE SEE MISSING SIGN CIRCUIT
 PER 600.5
  
 10) NOTE: PLEASE SEE MISSING RECEPTS
 ABOVE WINDOWS WHICH WILL BE REQUIRED PER
 210.62. THIS IS TO ALLEAVIATE ANY
 EXTENSION CORDS LIKELY TO CAUSE PHYSICAL
 INJURY, RECEPTACLES MUST BE INSTALLED
 DIRECTLY ABOVEWINDOW, AND ONE
 RECEPTACLE IS REQUIRED FOR EVERY 12
 LINEAR FT OR "MAJOR FRACTION THEREOF" (6
 FT OR MORE)
  
 11) NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EMERGENCY AND EXIT LTS.
 PLEASE SEE THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING AS NEEDED.
  
 12) NOTE: PLEASE PROVIDE MIN
 PHOTO-METRICS FOR EGRESS STAIRWAYS.
 PLEASE ALSO SEE MAIN AREA WHICH MAY ALSO
 REQUIRE ADDITIONAL FIXTURES AT FRONT
 AREA TO PROVIDE MIN LIGHTING LEVELS
 UNDER EMERGENCY CONDITIONS.
 THIS SHOULD BE DETAILED IN
 PHOTO-METRICS.
 PLEASE SEE 2003 LS 101 WHICH REQUIRES
 A MININUM OF 10FT CANDLES(108 LUX) UNDER
 NORMAL CONDITIONS AND 1FT CANDLE UNDER
 EMERGENCY CONDITIONS. PLEASE SEE STAIRS
 DO NOT APPEAR TO SHOW ANY EM BATTERY
 BACK UP FIXTURES AT THIS TIME?
 PLEASE ALSO SEE FIRE REVIEW COMMENTS FOR
 ANY MISSING LOCATIONS WHICH MAY BE
 REQUIRED AND WILL AFFECT ELECTRICAL
 PLANS.
  
 13) NOTE: PLEASE SEE PHASE "B" OF WATER
 HEATER ON PANEL SCHEDULE. THIS SEEMS TO
 BE A MISPRINT. (2, 9)
 PLEASE ADJUST.
 215.5
  
 14) NOTE: PLEASE ADJUST ANY LOADS FOR
 ADDED DEDICATED CIRCUITS FOR WINDOW
 RECEPTS, 220.12B, SIGN CIRCUIT 600.5 ARE
 TO BE FIGURED INTO LOAD CALCS.
 ETC.
  
 15) NOTE: PLEASE SEE DISCONNECTING MEANS
 FOR AHU'S IN CLOSETS ON LOWER LEVEL DO
 NOT SEEM TO MEET 110.26
 PLEASE ALSO SEE ACCESS TO DISC'S ON SOME
 UNITS ON UPPER LEVEL ALSO.
  
 16) NOTE: PLEASE SEE GROUDING ELECTRODE
 SYSTEM INDICATES GEC TO THE "FOOTER
 STEEL" ?? PLEASE KNOW, THIS SEEMS TO BE
 AN EXISTING BLDG AND THE GEC IS NOT
 REQUIRED TO BE ATTACHED TO THE FOOTER
 STEEL AS THIS PROCESS MAY AFFECT THE
 STRUCTURAL INTEGRITY OF THE EXISTING
 FOOTER.
 THIS MAY BE DONE, HOWEVER THIS IS NOT
 REQUIRED. IF SHOWN ON RISER, THEN THIS
 WILL BE REQUIRED.
 ** THIS IS ONLY A NOTE AND NO CORRECTION
 IS NEED. INFORMATIONAL ONLY.
  
 17) NOTE: PLEASE SHOW DISCONNECTING
 MEANS REQUIRED FOR WATER HEATER.
 422.31
  
 18) NOTE: PLEASE REVISE ENERGY
 CALCULATIONS AND FORMS PER COMMENTS
 ABOVE. 13-415.1.ABC.1
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS .
  
 ** WHEN RE-SUBMITTING PLANS AFTER ALL
 REVIEWS ARE COMPLETED. PLEASE BES URE TO
 COMPLETELY REVMOVED ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. ONE SET OF THE REMOVED
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED IN
 A SEPARATE SET FOR REFERENCE..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-01 Cont ID  
Sent By mwennerg Date 2006-06-01 Time 11:12 Rev Time 0.00
Received By mwennerg Date 2006-06-01 Time 11:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-25 Cont ID  
Sent By mwennerg Date 2006-04-25 Time 10:47 Rev Time 0.00
Received By mwennerg Date 2006-04-25 Time 10:47 Sent To  
Notes
2006-04-25 00:00:00******DENIED******
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION. SHT A.4.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 3) DOES THE UPPER LEVEL MEET THE
 REQUIREMENTS OF NFPA 101, SECTION
 8.6.9.2 IN REGARDS TO MEZZANINE AREA
 LIMITATIONS?
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 5) A SMOKE DETECTOR IS REQUIRED IN THE
 AREA OF THE FIRE ALARM CONTROL PANEL.
  
 6) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 14:22 Sent To B
Notes
2006-10-24 14:23:13TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 13:28 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 13:27 Sent To P
Notes
2006-10-23 13:28:17TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 13:09 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 13:09 Sent To M
Notes
2006-10-23 13:09:46TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 16:36 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 16:36 Sent To  
Notes
2006-10-18 16:36:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 14:09 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 14:09 Sent To B
Notes
2006-10-18 14:11:16TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-11 Cont ID  
Sent By mmiller Date 2006-08-11 Time 14:42 Rev Time 0.00
Received By mmiller Date 2006-08-11 Time 14:42 Sent To E
Notes
2006-08-11 00:00:00SENT TO "DP" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 14:42 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 14:42 Sent To  
Notes
2006-08-03 00:00:00WAITING FOR "COMM" BD/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-06-06 Time 16:19 Sent To E
Notes
2006-06-06 00:00:00TO "DPALMER" DESK/RESUB--EXPEDITED PLAN

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-05 Cont ID  
Sent By adarroug Date 2006-05-05 Time 15:42 Rev Time 0.00
Received By adarroug Date 2006-05-05 Time 15:42 Sent To  
Notes
2006-06-02 00:00:006/2/06--TAKEN FROM "COMM" BD#36 AND
 ROUTED TO "HMOSER" DESK
2006-05-24 00:00:00TO "COMM" BD#36
2006-05-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-29 Cont ID  
Sent By dpalmer Date 2006-03-29 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2006-03-29 Time 07:48 Sent To  
Notes
2006-04-19 00:00:00MOVED TO "BOB"#2
2006-03-29 00:00:00TO COMM BOARD #22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-25 Cont ID  
Sent By jleech Date 2006-04-25 Time 15:06 Rev Time 0.00
Received By jleech Date 2006-03-04 Time 14:44 Sent To  
Notes
2006-03-04 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-10-26 Cont ID  
Sent By tgordon Date 2006-10-26 Time 14:33 Rev Time 0.45
Received By tgordon Date 2006-10-26 Time 14:33 Sent To  
Notes
2006-10-26 14:39:22** MECHANICAL REVISION **
 *** DENIED ***
 1) SEE PAGE M-0.2 AIR DIST. SCH. (FLEX DUCT SCH. HAS
 BEEN REMOVED), THERE IS NO WAY TO DETERMINE WHICH SIZE
 FLEX OR GRILL NECK SIZE TO INSTALL, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-08 Cont ID  
Sent By hmoser Date 2006-08-08 Time 14:06 Rev Time 0.00
Received By hmoser Date 2006-08-08 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-05 Cont ID  
Sent By hmoser Date 2006-06-05 Time 09:53 Rev Time 0.00
Received By hmoser Date 2006-06-05 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By hmoser Date 2006-04-11 Time 14:23 Rev Time 0.00
Received By hmoser Date 2006-04-11 Time 14:23 Sent To  
Notes
2006-04-11 00:00:00PLAN DENIED
 1) PLEASE REFER TO SECTION 13-101.1.3
 RENOVATIONS OF COMMERCIAL BUILDINGS
 FLORIDA ENERGY CODE 2004.
 2) PLEASE REFER TO SECTION 602.2.1 2004
 FBC(M) MECHANICAL COLSIT DOORS MUST
 MEET FIRE AND SMOKE INDEX OF 25-50.
 3) PLESAE SHOW FANSHUT DOWN ON
 AIRHANDLER # 3 ON THE PLANS.
 4) PLEASE REFER TO SECTION 307.2.3 2004
 FBC(M) AUXILIARY AND SECONDARY DRAIN
 SYSTEM FOR AIRHANHLERS 1,2,3,4
 5) PLEASE PROVIDE DUCT SIZE ON THE PLANS
 FOR AIRHANDLER #6.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-13 Cont ID  
Sent By jleech Date 2006-11-13 Time 14:50 Rev Time 0.00
Received By jleech Date 2006-11-13 Time 14:50 Sent To  
Notes
2006-11-13 14:50:57REVISED PLANS ADDED A URINAL AND DELETED A SHOWER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-30 Cont ID  
Sent By pschmitz Date 2006-05-30 Time 09:53 Rev Time 0.00
Received By pschmitz Date 2006-05-30 Time 14:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-25 Cont ID  
Sent By jleech Date 2006-04-25 Time 14:33 Rev Time 0.00
Received By jleech Date 2006-04-25 Time 14:33 Sent To  
Notes
2006-04-25 00:00:00DENIED;
 1.PAGE P-0 WATER HEATER DETAIL. THERMAL
 EXPANSION TANK TO BE INSTALLED ON COLD
 WATER SIDE PER MANUFACTURE'S
 SPECIFICATIONS.
 2.PLUMBING NOTES NUMBER 16 FIRE STOP
 MATERIAL, LIST MANUFACTURE AND LIST THE
 UL NUMBERS.
 3.BAR AREA FLOOR SINKS REQUIRED FOR
 INDIRECT WASTE FROM ICE BINS,SODA AND
 BEER DISPENSOR DRAINS.
 4.WATER HAMMER ARRESTORS TO BE INSTALLED
 AS CLOSE TO SOURCE OF HAMMER AS POSSIBLE
 PER MANUFACTURE'S INSTALLATION
 INSTRUCTIONS.
 5.PAGE A.0 (PROJECT INFORMATION) 1526
 SQ. FT. GROUP DOES NOT MEET ALL OF THE
 EXCEPTIONS IN SECTION 403.2 (2) 15
 PEOPLE OR LESS.
 6.THE BAR AREA ON FIRST FLOOR SHOULD BE
 A-2 IN TABLE 403.1 NOT GROUP B. SHOW
 SEATING IN BAR AREA.
 7.ADA BATHROOM ON SECOND FLOOR, SHOWER
 IS REQUIRED TO MEET HANDICAP CODE
 SECTIONS 11-4.21.1 THRU 11-4.21.6 (SHOW
 DETAIL ON PLANS)
 8.LOUNGE SINK TO BE HANDICAP ACCESSIBLE.
 MUST COMPLY WITH CHAPTER 11 SECTIONS
 11-4.24.1 THRU 11-4.24.7. SHOW FRONTAL
 APPROACH ON PLANS AND A DETAIL OF
 CABINETS ON PLANS
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695