| 2007-02-18 14:45:56 | *** UNSAT *** |
| | |
| | ** ORIGINAL REVIEW DONE UNDER 05070398, THIS RE-STAMP |
| | WAS NOT REVIEWED UNDER THIS PERMIT NUMBER. |
| | |
| | 1) NOTE: PLEASE INDICATE ALL REVISIONS IN TITLE BLOCKS |
| | AND INDICATE BY CLOUDS/TRIANGLES ON PLANS. |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THE RISER NOW IS COMPLETELY REVISED |
| | WHICH NOW INDICATES THE SUB PANEL BEING REMOVED HOWEVER |
| | THE PLANS STILL INDICATE MANY ELECTRICAL ITEMS NOT |
| | LISTED ON ANY PANEL SCHEDULE. PLEASE ALSO SEE THE LOAD |
| | CALCULATIONS ALSO STILL LIST MANY ELECTRICAL ITEMS NOT |
| | ON ANY PANEL SCHEDULE?? |
| | PANEL *C* WAS REMOVED. |
| | PLEASE CORRELATE AND REVISE ACCORDINGLY. |
| | 215.5, 310.16, 240.4, 408.4 |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE REVISE PANEL SCHEDULES FOR ALL ROOMS |
| | AND AREAS WHICH ARE REQUIRED TO SPECIFIC. PLEASE SEE |
| | 408.4 WHICH THE COMMENTARY OF THIS SECTION STATES; |
| | *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION. |
| | |
| | 4) NOTE: PLEASE VERIFY THE MODEL NUMBER FOR PANEL *B* |
| | WHICH SHOWS THIS AS A 125AMP PANEL WHEN THIS IS A 200A |
| | PANEL. |
| | 215.5. |
| | FBC 106.1.2 PLEASE COORDINATE. |
| | |
| | 5) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE |
| | SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE |
| | DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE |
| | DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT |
| | ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER |
| | THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS |
| | SA/SMOKE ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE |
| | REFLECTED ON PLANS FOR DESIGN. |
| | 2002 NFPA-70, 2002 NFPA-72 |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |