Plan Review Details - Permit 06030075
Plan Review Stops For Permit 06030075
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-19 Cont ID  
Sent By lmartine Date 2006-03-19 Time 10:09 Rev Time 0.00
Received By lmartine Date 2006-03-19 Time 10:09 Sent To  
Notes
2006-03-19 00:00:00 
 ACTIVATE NEW PERMIT
 WITH RESTAMP PLANS
  
  
 ORIGINAL CONSTRUCTION VALUE IS HONORED,
 NO ADDITIONAL AJUSTED VALUE NECESSARY.
  
 SPEC'S FOR FUTURE BBQ. TO BE SUBMITTED
 UNDER SEPARATE PERMIT.
  
 UPDATED ENERGY CAL'S ARE REQUIRED TO BE
 SUBMITTED, PER FBC 2004.
  
 TRUSS DESIGN DRAWINGS SHALL BE
 SUBMITTED BEFORE INSTALLATION.
  
  
  
  
  
  
  
  
 L.MARTRINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-14 Cont ID  
Sent By alange Date 2006-03-14 Time 10:25 Rev Time 0.00
Received By lmartine Date 2006-03-14 Time 10:08 Sent To  
Notes
2006-03-19 00:00:00WENT IN BY ACCIDENT
 SEE NEW COMMENTS UNDER 3/19/06 REVIEW
2006-03-14 00:00:00DENIED
  
 1.BASED ON ICC BUILDING VALUATION DATE
 THE PERMIT VALUATION HAS BEN REVISED AS
 FOLLOWS;
 3466 SQ.FT. AC X $86.37 = $299,358
 1127 SQ.FT. OTHER X $33.81 = $38,103
 TOTAL REVISED VALUE = $337,461.00
 SEE ATTACHED INVOICE.
  
 2.SUBMIT TWO COPIES OF SPECS FOR OUT
 DOOR BBQ AND REQUIRED HOOD.
  
 3.SUBMIT ENERGY CALCS TO THE 2004 FBC.
  
 4.SUBMIT TRUSS DESIGN DRAWINGS PRIOR
 TO INSTALLATION OF TRUSSES PER
 R-802.10.1 FBC 2004
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-11 Cont ID  
Sent By dpalmer Date 2007-03-11 Time 11:40 Rev Time 0.00
Received By dpalmer Date 2007-03-11 Time 11:03 Sent To M
Notes
2007-03-11 11:40:24*** REDLINED PLANS/PROVISO/ REVISON NEEDED BEFORE
 ROUGH***
  
  
 1) NOTE: PLEASE SEE NFPA-72 11.8.3 AS THE SA IN MASTER
 BEDROOOM MUST BE INSTALLED WITHIN 3FT OF THE HIGHEST
 POINT ON A SLOPED CEILING AND MUST BE INSTALLTED WITHIN
 12INCHES ON THE HIGHEST POINT ON A FLAT/TRAY CEILING.
 THIS DEVICE DOES NOT SEEMS LIKE IT WILL MEET THIS
 SECTION AND SHALL BE FEILD VERIFIED AS ELEVATION OF
 CEILING IS NOT ON ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE THE PANEL SCHEDULES BOTH INDICATE
 4/0 CONDUCTORS FOR THE FEEDERS TO EACH OF THE PANELS,
 YET THE RISER DIAGRAM SHOWS 2/0'S FOR EACH OF THESE.?
 PLEASE CORRELATE. THIS WAS SHOWN THIS WAY ON THE
 PREVIOUS SUBMITTED REVISIONS, HOWEVER WAS MISSED.
  
 ** PLEASE REVISE THE ABOVE WITH ANY OTHER REVSIONS
 BEFORE ROUGH ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-18 Cont ID  
Sent By dpalmer Date 2007-02-18 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2007-02-18 Time 14:12 Sent To M
Notes
2007-02-18 14:45:56*** UNSAT ***
  
 ** ORIGINAL REVIEW DONE UNDER 05070398, THIS RE-STAMP
 WAS NOT REVIEWED UNDER THIS PERMIT NUMBER.
  
 1) NOTE: PLEASE INDICATE ALL REVISIONS IN TITLE BLOCKS
 AND INDICATE BY CLOUDS/TRIANGLES ON PLANS.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE THE RISER NOW IS COMPLETELY REVISED
 WHICH NOW INDICATES THE SUB PANEL BEING REMOVED HOWEVER
 THE PLANS STILL INDICATE MANY ELECTRICAL ITEMS NOT
 LISTED ON ANY PANEL SCHEDULE. PLEASE ALSO SEE THE LOAD
 CALCULATIONS ALSO STILL LIST MANY ELECTRICAL ITEMS NOT
 ON ANY PANEL SCHEDULE??
 PANEL *C* WAS REMOVED.
 PLEASE CORRELATE AND REVISE ACCORDINGLY.
 215.5, 310.16, 240.4, 408.4
 FBC 106.1.2
  
 3) NOTE: PLEASE REVISE PANEL SCHEDULES FOR ALL ROOMS
 AND AREAS WHICH ARE REQUIRED TO SPECIFIC. PLEASE SEE
 408.4 WHICH THE COMMENTARY OF THIS SECTION STATES;
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 4) NOTE: PLEASE VERIFY THE MODEL NUMBER FOR PANEL *B*
 WHICH SHOWS THIS AS A 125AMP PANEL WHEN THIS IS A 200A
 PANEL.
 215.5.
 FBC 106.1.2 PLEASE COORDINATE.
  
 5) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 6) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON PLANS FOR DESIGN.
 2002 NFPA-70, 2002 NFPA-72
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 12:55 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 12:55 Sent To E
Notes
2007-03-10 12:55:54TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 16:33 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 16:33 Sent To E
Notes
2007-02-14 16:35:06TO "DPALMER" DESK/REV--ELEC AND MECH REV, PLEASE
 REFERENCE VOIDED PERMIT#05070398

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-19 Cont ID  
Sent By lmartine Date 2006-03-19 Time 10:02 Rev Time 0.00
Received By lmartine Date 2006-03-02 Time 10:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-12 Cont ID  
Sent By tgordon Date 2007-03-12 Time 11:43 Rev Time 0.30
Received By tgordon Date 2007-03-12 Time 11:43 Sent To  
Notes
2007-03-12 11:44:15REVISION TO MECHANICAL PLANS PAGE M1.1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-20 Cont ID  
Sent By tgordon Date 2007-02-20 Time 13:53 Rev Time 0.30
Received By tgordon Date 2007-02-20 Time 13:53 Sent To  
Notes
2007-02-20 14:10:43** MECHANICAL REVISION **
 FOR VOIDED BUILDING PERMIT #05070398
 *** DENIED ***
 1) SEE YELLOW HIGH-LIGHT ON MECHANICAL PLANS SHOWING
 DUCTS THAT NEED TO BE SIZED.
  
 2) AFTER SIZING THE SUPPLY AIR DUCT TO THE MASTER SUITE
 CHECK TO MAKE SURE THE RETURN AIR DUCT TO THE MASTER
 SUITE IS LARGE ENOUGH,SEE 2004 FBC/R M1602.4 (C)
 EXCEPT.
  
 ** 2004 FBC/R M1602.4BALANCED RETURN AIR.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.