Plan Review Details - Permit 06030036
Plan Review Stops For Permit 06030036
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-31 Cont ID  
Sent By alange Date 2006-03-31 Time 09:51 Rev Time 0.50
Received By alange Date 2006-03-31 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-03 Cont ID  
Sent By btrobaug Date 2006-05-03 Time 15:28 Rev Time 0.50
Received By btrobaug Date 2006-05-03 Time 14:45 Sent To PC
Notes
2006-05-03 00:00:00 
 PROVIDE A SITE PLAN, FLOOR PLAN OR BOTH
 TO INDICATE THE LOCATION OF ALL SERVICE
 AND GENERATOR EQUIPMENT.
  
 A PARTIAL RISER DIAGRAM WAS SUBMITTED
 SHOWING A 200AMP PANEL AND A 100 AMP
 TRANSFER SWITCH. A PICTURE WAS SUBMITTED
 SHOWING 2 PANELS SIDE BY SIDE APPARANTLY
 IN THE RESIDENCE.
  
 ANOTHER RISER(WITH NO NAME OR SIGNATURE
 ON IT)SHOWS A MAINAN EXISTING PANEL,
 AND A 100 AMP TRANSFER SWITCH, AND A
 RACE WAY GOING TO A GENERATOR "POWER
 INLET".PROVIDE A CALCULATION FOR THE
 LOAD TO BE SERVED BY THE GENERATOR . SEE
 702.5. HEAT, IF IN THE CALCULATION, MUST
 BE AT 100%.
  
 PLEASE SUBMIT TWO COPIES OF EVERYTHING,
 AND INCLUDE THE APPLICATION NOT FOUND
 WITH THIS RESUBMITTAL PACKAGE. TAKE OUT
 ALL DOCUMENTS THAT HAVE BEEN CHANGED OR
 ARE NOT NEEDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-23 Cont ID  
Sent By btrobaug Date 2006-03-23 Time 12:56 Rev Time 0.33
Received By btrobaug Date 2006-03-23 Time 12:54 Sent To M
Notes
2006-03-23 00:00:00 
 PLEASE PROVIDE A SITE PLAN AND A RISER
 DIAGRAM OF ALL SERVICE AND OPTIONAL
 EQQUIPMENT AND THEIR LOCATIONS SO THAT
 COMPLIANCE WITH 225.31 THRIOGH 225.39
 CAN BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-28 Cont ID  
Sent By mperson Date 2006-03-28 Time 10:17 Rev Time 0.15
Received By mperson Date 2006-03-28 Time 10:17 Sent To B
Notes
2006-03-28 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL RES-GEN
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 16:04 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 16:04 Sent To E
Notes
2006-04-21 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 09:14 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 09:14 Sent To E
Notes
2006-03-09 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-31 Cont ID  
Sent By alange Date 2006-03-31 Time 09:51 Rev Time 0.00
Received By alange Date 2006-03-02 Time 19:13 Sent To  
Notes
2006-03-02 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-03-27 Cont ID  
Sent By tgordon Date 2006-03-27 Time 16:45 Rev Time 0.15
Received By tgordon Date 2006-03-27 Time 16:45 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-03-28 Cont ID  
Sent By mperson Date 2006-03-28 Time 10:17 Rev Time 0.00
Received By mperson Date 2006-03-28 Time 10:16 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-03-08 Cont ID  
Sent By mmclean Date 2006-03-08 Time 15:50 Rev Time 0.00
Received By mmclean Date 2006-03-08 Time 15:50 Sent To I
Notes
2006-03-08 00:00:00GENERATOR CAN ONLY BE 4FT INTO A
 SETBACK.