| Notes |
| 2006-05-03 00:00:00 | | | | PROVIDE A SITE PLAN, FLOOR PLAN OR BOTH | | | TO INDICATE THE LOCATION OF ALL SERVICE | | | AND GENERATOR EQUIPMENT. | | | | | | A PARTIAL RISER DIAGRAM WAS SUBMITTED | | | SHOWING A 200AMP PANEL AND A 100 AMP | | | TRANSFER SWITCH. A PICTURE WAS SUBMITTED | | | SHOWING 2 PANELS SIDE BY SIDE APPARANTLY | | | IN THE RESIDENCE. | | | | | | ANOTHER RISER(WITH NO NAME OR SIGNATURE | | | ON IT)SHOWS A MAINAN EXISTING PANEL, | | | AND A 100 AMP TRANSFER SWITCH, AND A | | | RACE WAY GOING TO A GENERATOR "POWER | | | INLET".PROVIDE A CALCULATION FOR THE | | | LOAD TO BE SERVED BY THE GENERATOR . SEE | | | 702.5. HEAT, IF IN THE CALCULATION, MUST | | | BE AT 100%. | | | | | | PLEASE SUBMIT TWO COPIES OF EVERYTHING, | | | AND INCLUDE THE APPLICATION NOT FOUND | | | WITH THIS RESUBMITTAL PACKAGE. TAKE OUT | | | ALL DOCUMENTS THAT HAVE BEEN CHANGED OR | | | ARE NOT NEEDED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-03-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-23 |
Time |
12:56 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2006-03-23 |
Time |
12:54 |
Sent To |
M |
|
| Notes |
| 2006-03-23 00:00:00 | | | | PLEASE PROVIDE A SITE PLAN AND A RISER | | | DIAGRAM OF ALL SERVICE AND OPTIONAL | | | EQQUIPMENT AND THEIR LOCATIONS SO THAT | | | COMPLIANCE WITH 225.31 THRIOGH 225.39 | | | CAN BE REVIEWED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2006-03-28 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-03-28 |
Time |
10:17 |
Rev Time |
0.15 |
| Received By |
mperson |
Date |
2006-03-28 |
Time |
10:17 |
Sent To |
B |
|
| Notes |
| 2006-03-28 00:00:00 | NOTE: GAS PERMIT REQUIRED. GAS | | | CONTRACTOR TO SUBMIT PLANS WITH PERMIT | | | APPLICATION. ALL GAS INSPECTIONS TO BE | | | COMPLETE BEFORE FINAL RES-GEN | | | INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-04-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-21 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-21 |
Time |
16:04 |
Sent To |
E |
|
| Notes |
| 2006-04-21 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-03-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-09 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-09 |
Time |
09:14 |
Sent To |
E |
|
| Notes |
| 2006-03-09 00:00:00 | TO "GEN-RES" BOX "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-03-31 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-03-31 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-03-02 |
Time |
19:13 |
Sent To |
|
|
| Notes |
| 2006-03-02 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-03-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-03-27 |
Time |
16:45 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-03-27 |
Time |
16:45 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-03-28 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-03-28 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-03-28 |
Time |
10:16 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-03-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-03-08 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-03-08 |
Time |
15:50 |
Sent To |
I |
|
| Notes |
| 2006-03-08 00:00:00 | GENERATOR CAN ONLY BE 4FT INTO A | | | SETBACK. |
|
|