Plan Review Details - Permit 06021280
Plan Review Stops For Permit 06021280
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-02-22 Cont ID  
Sent By jgomez Date 2008-02-22 Time 14:57 Rev Time 0.00
Received By jgomez Date 2008-02-22 Time 14:57 Sent To PC
Notes
2008-02-22 14:57:59RETAINING WALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-02-05 Cont ID  
Sent By jgomez Date 2008-02-05 Time 14:59 Rev Time 0.00
Received By jgomez Date 2008-02-05 Time 14:59 Sent To PC
Notes
2008-02-05 16:19:31DRAINAGE RETAINING WALLS CHECKLIST:
  
 1- BOTH DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER SHOWN IN THE TITLE BLOCK AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE. ONLY ONE DRAWING WAS
 SIGNED AND SEALED.
  
 2- THERE ARE NO PLANS OR SURVEYS SHOWING EXACT LOCATION
 OF RETAINING WALLS AND DIMENSIONS. UNABLE TO VERIFY
 LOCATION.
  
 3- PROVIDE DRAINAGE PLAN SHOWINGCOMPLIANCE WITH
 SECTION R401.3 OF 2004 FLORIDA RESIDENTIAL CODE.WATER
 CAN'T BE DIVERTED TO THE NEIGHBOR'S PROPERTY.IT NEEDS
 TO BE RETAINED IN THE LOT OR CONVEYED TO APPROVED
 POINTS OF COLLECTION.
  
 4-WOOD POSTS:
 A) DRAWINGS DON'T PROVIDE SPACING OF 6X6 POSTS.
 B) THERE ARE NO SPECS FOR TYPE OF WOOD USED. EG:
 PRESSURE TREATED.
 C) IT'S NOT CLEAR IF USING(2) 5/8 THRU BOLTS OR
 (1). ONE DRAWING SHOWS TWO AND THE OTHER ONE SHOWS
 (1).
 D) HOW ARE THE REST OF 9X7 WOOD MEMBERS ATTACHED TO
 THE 6X6 POST.
 E) PROVIDE COMPLETE SPECIFICATIONS SHOWING HOW THE
 POSTWILL BE PLACED TO RESIST THE CALCULATED LOADS.
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- HOW ARE THE 9X7 WOOD MEMBERS ATTACHED TOGETHER?.
 SEC. R301.
  
 6- WHAT'SSEPTIC PAPER SPECIFIED ON RETAINING WALL
 SECTION. PROVIDESPECIFIC SPECIFICATIONS FOR TYPE OF
 PAPER TO BE USED.
  
 7 SURVEYSPROVIDEDNEED TO HAVE SURVEYOR'S ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
 COPY OF SIGNATURE IS NOT ALLOWED.
  
 8- GUARDS MAY BE REQUIRED IF THE DROP FROM ONE GRADE TO
 THE OTHER IS MORE THAN 30" AS REQUIRED BY SEC. R312 OF
 2004 FLORIDA RESIDENTIAL CODE.THIS WILL BE VERIFIED
 IN FIELD.
  
 9- DRAWINGS NEED TO SPECIFY SPECIFIC CODE FOR WHICH
 DESIGN WAS MADE.
  
 NOTE: ONE SET OF PLANS WILL BE RETAINED IN THIS OFFICE
 FOR BOARD OF ENGINEER'S REVIEW.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2007-11-07 Cont ID  
Sent By jgomez Date 2007-11-07 Time 11:30 Rev Time 0.00
Received By jgomez Date 2007-11-07 Time 11:30 Sent To  
Notes
2007-11-07 11:31:25ENERGY CALCULATIONS WERE NOT REVISED. SEE MECHANICAL
 NOTES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-24 Cont ID  
Sent By jgomez Date 2007-10-24 Time 16:14 Rev Time 0.00
Received By jgomez Date 2007-10-24 Time 16:14 Sent To M
Notes
2007-10-24 16:15:52REVISED ENERGY CALCULATIONS CHECKLIST.
  
 1- ENERGY CALCULATIONS WERE SUBMITTED FOR RE-STAMPING
 BECAUSE THE ONES FROM THE FIELD SET WERE LOST.
 PROVIDED ENERGY CALCULATIONS DON'T MATCH APPROVED ONES.
 THEREFORE, THIS IS A REVISION AND $70.00 REVISION FEES
 ARE DUE(NEW ENERGY CALCULATIONS AND MANUAL J
 CALCULATIONS PROVIDED).
  
 2- PROVIDE 2 COPIES OF REVISED ENERGY CALCULATIONS.
  
 3- NEW ENERGY CALCULATIONS CALL FOR R-30 FOR ADJACENT
 WOOD FRAMED WALL (ITEM 9(B).REVISE PLANS AS REQUIRED
 SHOWING HOWTHIS R-30 VALUEIS ACHIEVED ON A 2X4 STUD
 WALL?.SEE SHEET A-8.
 ***NOTE: IF USING BUTT INSULATION, THENONLY R-11 CAN
 BE ACHIEVEDON A 2X4 WALL.
  
 4- PROVIDE REVISED ENERGY CALCULATIONS FORM 600A-2004R.
  
  
 5- PROVIDE CORRECT CONTRACTOR'S NAMEAND COMPLETE ALL
 INFORMATION ON TOP OF ENERGY CALCULATIONS FORM.
  
 6- OWNER/AGENT TO DATE FORM OF FORM.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-21 Cont ID  
Sent By jgomez Date 2006-07-21 Time 19:16 Rev Time 2.00
Received By jgomez Date 2006-07-21 Time 17:17 Sent To M
Notes
2006-07-21 00:00:00BUILDING REVIEW PROVISO:
 1- PROVIDE 2 COMPLETE SETS OF TRUSS
 DRAWINGS. ONLY ONE SET OF TRUSSES
 SUBMITTED.
  
 2- TRUSS ENGINEER TO PROVIDE ALL HIS
 INFORMATION IN ALL DRAWINGS AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTES AND
 SECTION 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-06 Cont ID  
Sent By jgomez Date 2006-07-06 Time 14:39 Rev Time 3.00
Received By jgomez Date 2006-07-06 Time 14:38 Sent To  
Notes
2006-07-06 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2- HOUSE IS LOCATED IN FLOOD ZONE A5.
 DETERMINED FLOOD ELEVATION IS 7'-0".
 CITY OF W.P.B ORDINANCE SEC.94-546(B)(1)
 REQUIRES MIN. FLOOR ELEVATION TO BE AT
 LEAST 6" ABOVE THE DETERMINED FLOOD
 ELEVATION. GARAGE FIN. FLOOR ELEVATION
 SHOWN ON PLANS AND SURVEY IS 7'-0".
 REVISE PLANS AND SURVEY AS REQUIRED.
  
 3- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 FOR:
 A) SIDING. SEE PLANS. NO SUBMITTED WITH
 RE-SUBMITTAL PACKAGE.
 B) METAL ROOFING. NO SUBMITTED.
 C) SINGLE HUNG WINDOWS. PROVIDE DADE
 COUNTY NOA REPORT THAT MATCHES ONE
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL
 VISIT DCA SITE WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD SPECIFIC NOA SUBMITTED TO
 OBTAIN FLORIDA PRODUCT APPROVAL.
 ***NOTE: SEE APPROVED PACKAGE FOR FRENCH
 DOORS WITH SIDELITES PRODUCT APPROVAL.
 USE AS SAMPLE OF COMPLETE PRODUCT
 APPROVAL SUBMITTAL. PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND EXACT
 NOA REPORT THAT WAS APPROVED BY DCA.
 D) AWNING WINDOWS. NOT SUBMITTED.
 E) FIXED WINDOWS. PROVIDE EXACT DADE
 COUNTY NOA SUBMITTED FOR APPROVAL. SEE
 COMMENTS ABOVE.
 F) BAHAMA SHUTTERS. NOT SUBMITTED.
 G) PRECAST LINTELS. NOT SUBMITTED.
 H) ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS. SEE DETAIL SECTIONS
 AND TRUSS ANCHOR SCHEDULE. NOT SUBMITTED
 I) 4'X8' WITH SIDELITES ENTRY DOOR. NOT
 SUBMITTED WITH THIS PACKAGE.
 J) FRENCH DOORS. PROVIDE CURRENT NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
 K) WINDOW MULLIONS: PROVIDE CURRENT
 NOAS. ONES SUBMITTED EXPIRED ON 6-28-06.
 L) GARAGE DOORS AS SHOWN ON PLANS. NOT
 SUBMITTED WITH THIS PACKAGE.
  
 4- REMAINDER. DESIGNER OF RECORD TO RE-
 REVIEW AND APPROVE ALL REVISED PRODUCT
 APPROVALS. SEC. 106.3.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 5- PROVIDE COMPLETE INFORMATION FOR R-19
 ICYNENE INSULATION TO VERIFY COMPLIANCE
 WITH THE PROPOSED INSTALLATION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 AND
 R806.4 2004 RESIDENTIAL CODE.
 INFORMATION WAS NOT SUBMITTED.
  
 6- REVISE ENERGY CALCULATIONS:
 A) REVISE NAME OF BUILDER.
 B) CEILING INSULATION R VALUE DOESN'T
 MATCH PLANS.
  
 7- ARCHITECT TO SPECIFY R-30 INSULATION
 ON ADJACENT WALL BY GARAGE AREA TO MATCH
 ENERGY CALCULATIONS.
  
 8- REVISE SURVEY. A) NEED TO RAISE
 GARAGE FINISH FLOOR ELEVATION. SEE ITEM
 #2 ABOVE.
 B) INCLUDE FRONT AND REAR PORCHES TO
 MATCH ARCHITECT'S PLANS.
  
 9- TRUSSES PACKAGE SUBMITTED NEED:
 A) 2 COMPLETE SETS.
 B) DESIGNER OF RECORD TO REVIEW AND
 APPROVE PACKAGE IN WRITTING.
 C) TRUSS ENGINEER TO SIGN, SEAL, DATE
 AND PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES
 AND SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 10- SHEET A-7: STAIR RATIO SHOWN EXCEEDS
 THE RATIO REQUIRED SEC. R311.5.3.2. TWO
 RISERS AT 6.7" AND ONE TREAD AT 12"
 EQUALS 25.4. REVISE AS REQUIRED.
  
 11- SHEET A-8: DETAIL 5/A9 AND
 INFORMATION SHOWN ON FOUNDATION PLAN IS
 CONFUSING. CLARIFY HOW IS THE COLUMN C-1
 AND 8"X20" WITH 6-#5 VERT. INSTALLED.
 PROVIDE CLEAR DETAIL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By jgomez Date 2006-03-24 Time 18:59 Rev Time 4.00
Received By jgomez Date 2006-03-24 Time 18:59 Sent To  
Notes
2006-03-24 00:00:00BUILDING REVIEW CHECKLIST:
 1- ACCORDING TO THE DBPR PUBLIC WEBSITE
 GENERAL CONTRACTOR'S LICENSE IS
 SUSPENDED. CONTRACTOR TO RESOLVE ISSUES
 WITH DBPR PRIOR TO OBTAINING PERMIT.
  
 2- AFTER DRAWINGS ARE CORRECTED. PAY
 IMPACT FEES. BRING BACK STAMPED PLANS
 AND PAID RECEIPT.
  
 3- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS IF WORK IS NOT COMMENCED.
 NEED RE-RECORDED ONE.
  
 4- AREA TABULATION DOESN'T MATCH AREAS
 MEASURED FROM PLANS. PROVIDE BREAKDOWN
 OF AREAS. EG: 1ST FLOOR A/C AREA, 2ND
 FLOOR A/C AREA, GARAGE, FRONT PORCH,
 REAR PORCH AND SECOND FLOOR BALCONY.
  
 5- VALUATION DECLARED ON PERMIT
 APPLICATION WAS TOO LOW. VALUATION WAS
 UPDATED TO $359,923. OWES $900.84 FOR
 LOW VALUATION AND RADON FEES.
  
 6- HOUSE IS LOCATED IN FLOOD ZONE A5.
 DETERMINED FLOOD ELEVATION IS 7'-0".
 CITY OF WEST PALM BEACH REQUIRES MIN.
 FIN. FLOOR ELEVATION TO BE AT LEAST 6"
 ABOVE DETERMINED FLOOD ELEVATION.
 SPECIFY MIN. FIN. FLOOR ELEVATION ON
 PLANS AND SURVEY.
  
 7- PROVIDE DRAINAGE PLAN AS REQUIRED BY
 SEC. R401.3 2004 RESIDENTIAL CODE.
  
 8- SHEET A-1 SITE PLAN: CLARIFY WHAT ARE
 LINES SHOWN IN FRONT SIDEWALK. ARE THEY
 STEPS? IF SO PROVIDE COMPLETE
 INFORMATION TO VERIFY STEPS CODE
 COMPLIANCE AND HANDRAIL REQUIREMENTS.
  
 9- SHEET A1.1: A) NEED TO SPECIFY THE
 NON STORAGE ATTIC LIVE LOAD (BOTTOM
 CHORD) AS REQUIRED BY TABLE R301.5 2004
 RESIDENTIAL CODE.
 B) SHOW ON ROOF FRAMING PLANS AREAS TO
 HAVE STORAGE (80 PSF AS SHOWN ON PLANS).
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 C) UPDATE ACI REFERENCE EDITION CITED
 FOR REINFORCED MASONRY ON NOTE M-1. SEE
 CHAPTER 43 OF 2004 RESIDENTIAL CODE FOR
 EDITION ADOPTED BY THE CODE.
  
 10- NEED BATHROOM ON FIRST FLOOR WITH
 DOOR THAT ALLOWS 29" MIN. CLEAR OPENING.
 SEC. R322 2004 RESIDENTIAL CODE.
  
 11- WINDOWS IN DEN ROOM DON'T MEET THE
 EGRESS REQUIREMENTS OF SEC. R310 2004
 RESIDENTIAL CODE, IF ROOM IS USED FOR
 SLEEPING PURPOSES. PROVIDE COMPLYING
 EGRESS WINDOW OR CLEARLY WRITE ON PLANS
 ON DEN ROOM THAT SUCH ROOM IS NOT TO BE
 USED FOR SLEEPING PURPOSES.
  
 12- SPECIFY ATTIC ACCESS SIZE ON 1ST AND
 2ND FLOOR. SEC. R807 2004 RESID. CODE.
  
 13- PROVIDE FIREPLACE INFORMATION AS
 REQUIRED BY SEC. R1004.1 AND R1004.4
 2004 RESIDENTIAL CODE.
  
 14- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 (GO
 TO WWW.FLORIDABUILDING.ORG) FOR:
 A) SIDING. SEE PLANS.
 B) METAL ROOFING. SEE PLANS
 C) SINGLE HUNG WINDOWS. SEE PLANS.
 D) FIXED WINDOWS. SEE PLANS.
 E) BAHAMA SHUTTERS. SEE PLANS.
 F) PRECAST LINTELS.
 G) ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS.
 H) 4'X8' ENTRY DOOR WITH SIDELITES
 ASSEMBLY AS SHOWN ON PLANS.
 I) FRENCH DOORS WITH SIDELITES AND
 WITHOUT SIDELITES AS SHOWN ON PLANS.
 J) WINDOW MULLIONS.
 K) GARAGE DOORS AS SHOWN ON PLANS.
  
 15- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 OF
 CITY AMENDMENTS TO FBC 2004.
  
 16- PROVIDE COMPLETE INFORMATION TO SHOW
 HOW IS THE ATTIC AREA COMPLYING WITH
 SEC. R806 REGARDING ROOF VENTILATION.
 SEE SEC. R806.4 FOR UNVENTED CONDITIONS
 THAT ARE ALLOWED.
  
 17- PROVIDE COMPLETE INFORMATION FOR
 R-19 ICYNENE INSULATION AND ARCHITECT TO
 PROVIDE COMPLETE DETAILS/SPECS FOR
 BUILDING ENVELOPE TO MEET REQUIREMENTS
 OF ICYNENE INSULATION.
 ***NOTE: ABOVE ITEM #16 MUST BE CLEARED
 FIRST TO PROCEED WITH THIS INSULATION.
  
 18- ENERGY CALCULATIONS: A) A/C AREA
 DOESN'T MATCH PLANS. SEE PLANS.
 B) HOW IS R6.4 ACHIEVED FOR CONCRETE
 SLAB ON GRADE. SEE PLANS.
 C) HOW IS R7.7 ACHIEVED FOR CONCRETE
 BLOCK WALLS. SEE PLANS.
 D) CEILING INSULATION R VALUE DOESN'T
 MATCH PLANS.
 E) REVISE UNDER ATTIC AREA. SEE SEC.
 13-604.1.A.1 FBC 2004 FOR AREAS TO BE
 CONSIDERED AS CEILING AREA.
 F) CEILING FAN CREDIT WAS TAKEN. SHOW
 IN PLANS MIN. SIZE AND NUMBER OF CEILING
 FANS AS REQUIRED BY TABLE 13-607.1.A.1
 OF FBC 2004.
 G) COMPLETEINFORMATION ON TOP OF
 FORM.
 H) ARCHITECT TO PROVIDE ALL HIS
 INFORMATION AT BOTTOM OF FORM AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTE
 AND FLORIDA ADMINISTRATIVE CODE.
 I) OWNER/AGENT TO SIGN AND DATE FORM.
  
 19- REAR PORCH FOUNDATION PLAN AND FIRST
 FLOOR PLAN DON'T SHOW CONCRETE SLAB.
 PROVIDE COMPLETE INFORMATION AND SHOW IF
 STEPS ARE REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 20- PROVIDE SURVEY FOR PROPOSED HOUSE.
 SURVEY SUBMITTED IS FOR DEMOLISHED HOUSE
  
 21- A) SPECIFY FASTENERS FOR DOOR &
 WINDOWS STRUCTURAL BUCKS. SEE SEC.
 R613.6.2 RESIDENTIAL CODE AND PRODUCT
 APPROVAL SUBMITTED FOR SIZE OF BUCK
 REQUIRED.
 B) DETAIL 1 OF A-6: USING 1X OR 2X
 BUCK. SEE DETAIL AND CLARIFY AS REQ'D.
  
 22- SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION ON LARGE BUILDING SECTIONS IN
 CONCEALED SPACES AND AT STAIR DETAILS.
 SEC. R602.8 2004 RESIDENTIAL CODE
  
 23- PROVIDE COLUMN AND LINTEL SCHEDULE.
 SEC. 106.1.2 CITY AMENDMENTS TO FB 2004.
  
 24- MAKE SURE THAT ALL DETAILS AND
 SECTIONS THAT ARE KEYED MATCH DETAILS
 AND SECTIONS SHOWN ON PLANS. SOME OF
 THEM DON'T COORDINATE. REVISE AS REQ'D.
  
 25- PROVIDE COMPLETE SECTION/DETAIL AND
 SPECS FOR CANTILEVERED BEAMS ON 2ND
 FLOOR ABOVE STAIRS. SHOW LENGTH,
 REINFORCEMENT AND ATTACHMENT TO
 SUPPORTING COLUMNS, ETC. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 26- NEED TO SHOW SMOKE DETECTOR ON EACH
 FLOOR. SEC. R313.1 2004 RESIDENTIAL CODE
  
 27- TRUSSES PACKAGE: A) DESIGNER OF
 RECORD TO REVIEW AND APPROVE ALL TRUSS
 DRAWINGS AND TRUSS LAYOUT PRIOR TO
 SUBMITTAL TO THIS OFFICE(TYPICALLY
 DONE USING THE STANDARD REVIEW STAMP).
 B) LOADS SHOWN ON TRUSS DRAWINGS AND
 LAYOUT DON'T MATCH LOADS SHOWN ON
 ARCHITECT'S PLAN. REVISE AS REQUIRED.
 C) CLARIFY FLOOR FRAMING NEXT TO THE
 STAIRS. ARCHITECTURAL PLANS AND TRUSS
 LAYOUT DON'T MATCH. IS IT FLOOR TRUSSES
 OR CONVENTIONAL FRAMING. PROVIDE
 COMPLETE MATCHING INFORMATION FOR EITHER
 D) TRUSS ENGINEER TO SIGN AND SEAL ALL
 DRAWINGS AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE AND FLORIDA
 ADMININSTRATIVE CODE WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
  
 28- SHEET A-4: FOOTING SHOWN ON BUILDING
 SECTION 2 AT FRONT OF HOUSE DOESN'T
 MATCH FOUNDATION PLAN. FOUNDATION PLAN
 SHOWS STEMWALL. REVISE AS REQUIRED.
  
 29- SHEET A-4.1 AND BUILDING SECTION 1:
 A) DETAIL 8 OF A-9 DOESN'T APPLY TO
 THE BOTTOM OF THE COLUMN. SEE DETAIL
 B) FOOTING SHOWN BY COVERED PORCH
 DOESN'T MATCH FOUNDATION PLAN.REVISE.
  
 30- SHEET A-5: A) SPECIFY FIREBLOCKING
 AND LOCATION IN CONCEALED SPACES.
 SECTION R602.8 2004 RESIDENTIAL CODE.
 B) FOOTINGS SHOWN ON SECTIONS TO MATCH
 FOUNDATION PLAN. REVISE AS REQUIRED.
  
 31- SHEET A-5.1: A) CONCRETE STAIR
 DETAIL. SPECIFY WHERE IS IT TAKEN AT TO
 VERIFY COMPLIANCE WITH NUMBER OF STEPS,
 HEIGHT AND HANDRAIL REQUIREMENTS.
 B) RATIO SHOWN ON STEPS DON'T COMPLY
 WITH SEC. R311.5.3.2 2004 RESIDENTIAL
 CODE. REVISE AS REQUIRED.
 C) PORCH DETAIL: 4" SPACING SHOWN
 BETWEEN PICKETS ALLOWS A 4" SPHERE TO GO
 THRU. SPACING NEEDS TO BE LESS THAN 4".
 REVISE AS REQUIRED.
  
 32- SHEET A-7: A) STAIR RATIO SHOWN
 EXCEEDS THE RATIO REQUIRED BY SEC.
 R311.5.3.2 2004 RESIDENTIAL CODE. REVISE
 AS REQ'D.
 B) SHOW FIREBLOCKING LOCATION AND
 MATERIAL AS REQUIRED BY SEC. R602.8 OF
 2004 RESIDENTIAL CODE.
  
 33- SHEET A-8: A) PROVIDE INFORMATION
 FOR CONCRETE SLAB AT REAR COVERED PORCH.
 B) WHAT'S TE-1 SHOWN BY DOOR OPENINGS.
 C) DETAIL 6/A9 KEYED BY GARAGE AREA
 DOESN'T CORRESPOND. REVISE AS REQUIRED.
 D) WHAT IS TS-2 & DETAIL 3/A9.1 SHOWN
 BY LIVING ROOM FRONT WALL. SEE PLAN.
 E) COLUMN BETWEEN 2 GARAGE DOORS WAS
 REVISED BY PENCIL. REVISE ORIGINAL
 DRAWING TO DESCRIBE SPECIFIC COLUMN.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 F) CLARIFY CONSTRUCTION BY GARAGE ENTRY.
 FOUNDATION PLAN, DETAIL 1/A9 AND FOOTING
 F-1 TO MATCH.
  
 34- SHEET A-8.1: A) SPECIFY BEAM AT 2ND
 FLOOR ROOF BY THE BALCONY AREA. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 B) ROOF FRAMING ABOVE BALCONY DOESN'T
 MATCH SIZES SHOWN ON WALL SECTIONS.
 REVISE AS REQUIRED.
 C) SPECIFY CONNECTORS FOR FLOOR
 TRUSSES ABOVE GARAGE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 D) FRAMING INFORMATION IN AREA NEXT TO
 STAIRS DON'T MATCH TRUSS LAYOUT. REVISE
 AS REQUIRED.
 E) CLARIFY WHY THE WORD CONCRETE IS
 WRITTEN ON TOP OF FLOOR TRUSSES.
 CLARIFY IF SECOND FLOOR IS GOING TO BE
 CONCRETE OR WOOD. REVISE AS REQUIRED.
 F) FRAMING LAYOUT SHOWN AT ENTRY PORCH
 DOESN'T MATCH TRUSS LAYOUT. REVISE AS
 REQUIRED.
 G) IF USING 2X10 BEAMS, THEN SPECIFY
 CONNECTORS AT THE ENDS (STEEL COLUMN AND
 CONCRETE WALL) AND SPECIFY CONNECTORS
 FOR RAFTERS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 H) REVISE CONECTOR SPECIFIED FOR
 TRUSSES RESTING ON WOOD BEAM AT REAR
 COVERED PORCH. NEED WOOD TO WOOD
 CONNECTORS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 35: SHEET A-9: A) DETAIL 7 NEED TO
 SPECIFY RISER AND TREAD TO VERIFY
 COMPLIANCE WITH STAIR RATIO AND TO
 VERIFY IF RAILING IS REQUIRED. SECTIONS
 R11.5.3 AND 312 2004 RESIDENTIAL CODE.
 B) DETAIL 12: SPECIFY IF USING
 PRESSURE TREATED 2X LEDGER OR HOW IS
 WOOD LEDGER PROTECTED FROM CONTACT WITH
 CONCRETE. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 36- SHEET A-9.1 BALCONY CONCRETE DETAIL:
 REVISE SPECIFIED REINFORCEMENT TO MATCH
 SPECS SHOWN ON SECOND FLOOR PLAN.
  
 37- NEED 2 REPORTS OF SOIL TEST REPORTS
 WITH ENGINEER'S ORIGINAL SIGNATURE AND
 SEAL AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE AND FLORIDA ADMINISTRATIVE CODE.
  
 ***NOTE:
 PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS TO EXPEDITE THE REVIEW PROCESS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-01-31 Cont ID  
Sent By btrobaug Date 2008-01-31 Time 07:52 Rev Time 0.00
Received By btrobaug Date 2008-01-31 Time 07:36 Sent To P
Notes
2008-01-31 07:52:00 
  
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE AS
 THEY CANNOT BE VERIFIED AS BEING MADE BY THE DESIGNER
 OF RECORD AS REQUIRED BY FS 471 OR 481, AS APPLICABLE.
 PLANS MUST BE REDRAWN BY THE DESIGNER OF RECORD, THEY
 MUST BE DATED TO REFLOECT THE REVISION DATE.
  
 2} REVISE THE LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 3} ADD THE NEW EQUIPMENT TO THE PANEL SCHEDULE PER
 106.3.5.4(8) FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-15 Cont ID  
Sent By btrobaug Date 2006-06-15 Time 12:50 Rev Time 0.50
Received By btrobaug Date 2006-06-15 Time 12:05 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-08 Cont ID  
Sent By btrobaug Date 2006-03-08 Time 16:21 Rev Time 0.50
Received By btrobaug Date 2006-03-08 Time 07:41 Sent To Z
Notes
2006-03-08 00:00:00 
  
 PROVISO
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION. ALLOW
 2 WEEKS TO COMPLETE THE REVIEW PROCESS
 FROM TIME OF SUBMITTAL.
  
 1} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH 250.52(A)(1) THROUGH (A)(6),
 INDICATE ELECTRODES AVAILABLE BEING
 USED.(IG: FOOTER STEEL)
  
 2} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE SIZED PER 250.66.(#2 MINIMUM.)
  
 3) THE KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH 210.8(A)(7).
  
 4} THE LAUNDRY RECEPTACLE MUST BE GFI
 PROTECTED PER 210.8(A)(7).
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-02-22 Cont ID  
Sent By adarroug Date 2008-02-22 Time 10:29 Rev Time 0.00
Received By adarroug Date 2008-02-22 Time 10:29 Sent To Z
Notes
2008-02-22 10:29:42TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 14:37 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 14:37 Sent To Z
Notes
2008-02-01 14:38:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 16:14 Sent To E
Notes
2008-01-29 16:14:41TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 13:53 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 13:53 Sent To Z
Notes
2008-01-29 13:54:17TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2008-01-25 Time 16:45 Sent To  
Notes
2008-01-25 16:45:56TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 17:01 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 17:01 Sent To M
Notes
2008-01-10 17:01:28SENT TO TOM GORDON'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 10:48 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 10:48 Sent To M
Notes
2007-11-02 10:48:25TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 12:30 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 12:30 Sent To B
Notes
2007-10-24 12:30:32TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 13:48 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 13:48 Sent To  
Notes
2007-05-15 13:49:09TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-18 Cont ID  
Sent By adarroug Date 2007-04-18 Time 11:13 Rev Time 0.00
Received By adarroug Date 2007-04-18 Time 11:13 Sent To M
Notes
2007-04-18 11:14:12TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 09:45 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 09:45 Sent To E
Notes
2006-06-14 00:00:00TO "BTROBAUG" DESK/RESUB-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 11:29 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 11:29 Sent To Z
Notes
2006-06-09 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By jgomez Date 2006-03-24 Time 19:03 Rev Time 0.00
Received By jgomez Date 2006-03-02 Time 14:58 Sent To  
Notes
2006-03-02 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 10 Status F Date 2008-02-07 Cont ID  
Sent By tgordon Date 2008-02-07 Time 13:42 Rev Time 0.20
Received By tgordon Date 2008-02-07 Time 13:42 Sent To  
Notes
2008-02-07 13:47:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO PLANS E-1 AND M-2 **
 *** DENIED ***
 1) PLANS ARE SIGNED AND SEALED BY AN ARCHITECT (KERMIT
 C. WHITE) AND ONLY HE CAN MAKE REVISIONS TO THEM.
  
 2) TWO DIFFERENT PAGES WERE SUBMITTED E-1 AND M-2,
 PLEASE SUBMIT TWO IDENTICAL PLANS FOR REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-01-28 Cont ID  
Sent By tgordon Date 2008-01-28 Time 08:36 Rev Time 0.25
Received By tgordon Date 2008-01-28 Time 08:36 Sent To  
Notes
2008-01-28 08:38:10REVISION TO MECHANICAL EQUIPMENT LIST (ARCHIT. LETTER).

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-01-11 Cont ID  
Sent By tgordon Date 2008-01-11 Time 10:00 Rev Time 0.30
Received By tgordon Date 2008-01-11 Time 10:00 Sent To  
Notes
2008-01-11 10:01:29REVISION TO SECOND FLOOR MECHANICAL PLAN 1/4 PAGE.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-11-07 Cont ID  
Sent By tgordon Date 2007-11-07 Time 11:39 Rev Time 0.25
Received By tgordon Date 2007-11-07 Time 11:39 Sent To  
Notes
2007-11-07 11:40:06RE-STAMP ENERGY CAL'S. AND COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 08:51 Rev Time 0.20
Received By tgordon Date 2007-10-25 Time 08:51 Sent To P
Notes
2007-10-25 08:54:22REVISION TO ENERGY CALCULATIONS
 *** DENIED ***
  
 1) SEE BUILDING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-05-16 Cont ID  
Sent By tgordon Date 2007-05-16 Time 15:49 Rev Time 0.30
Received By tgordon Date 2007-05-16 Time 15:49 Sent To  
Notes
2007-05-16 15:50:12REVISION TO MECHANICAL PLANS PAGE M-2.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-04-19 Cont ID  
Sent By tgordon Date 2007-04-19 Time 09:32 Rev Time 0.30
Received By tgordon Date 2007-04-19 Time 09:32 Sent To  
Notes
2007-04-19 09:43:41REVISION TO MECHANICAL PLANS PAGE M-1
 *** DENIED ***
 1) ORIGINAL MECHANICAL PLANS ON FILE WERE SEALED BY AN
 ARCHITECT (KERMIT C. WHITE) SO ONLY HE CAN MAKE
 REVISIONS TO THEM.
  
 2) ONE RETURN AIR DUCT FROM AHU 1 TO 18X12 RHF SW NEED
 TO BE SIZED, AND ONE SUPPLY AID DUCT FROM AHU 1 TO THE
 BOX GOING TO THE FIRST FLOOR NEEDS TO BE SIZED, SEE
 YELLOW HIGH LIGHT ON PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-26 Cont ID  
Sent By tgordon Date 2006-07-26 Time 09:50 Rev Time 1.30
Received By tgordon Date 2006-07-26 Time 09:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 08:11 Rev Time 1.00
Received By tgordon Date 2006-06-19 Time 08:11 Sent To P
Notes
2006-06-19 00:00:00*** DENIED ***
 1) DUCT SIZES ON MECHANICAL PLANS ARE
 INCORRECT, PLEASE REVIEW MANUAL J
 CALCULATIONS (UNDER CFM'S) AND CORRECT
 DUCT SIZES.
  
 2) HEATER KW ON MECHANICAL PLANS IS
 INCORRECT, PLEASE SEE ENERGY
 CALCULATIONS (HEATER SYSTEMS) AND
 CORRECT HEATER KW ON PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By tgordon Date 2006-03-09 Time 13:42 Rev Time 0.45
Received By tgordon Date 2006-03-09 Time 13:42 Sent To Z
Notes
2006-03-09 00:00:00*** DENIED ***
 1) MECHANICAL PLANS PAGE M-1 EQUIPMENT
 SCHEDULE IS SHOWING INCORRECT TOTAL AND
 SENSIBLE BTU'S, PLEASE CORRECT.
  
 2) PLEASE SUBMITT A MANUAL J (LONG FORM)
 SHOWING CFM'S TO EACH ROOM. PLEASE NOTE
 THE TRAIN TRACE 700 IS NOT RECOGNIZED AS
 A REPLACEMENT.
  
 3) ENERGY CALCULATIONS ARE SHOWING
 CONDITIONEDFLOOR AREA AS 2,949 SQ.
 FT., PLANS ARE SHOWING 3,286 A/C SQ.
 FT., PLEASE CORRECT.
  
 4) OWNER/AGENT ALSO NEEDS TO SIGN
 CORRECTED ENERGY CAL'S.
  
 5) TRANSFER RETURN AIR GRILL TO MASTER
 SUITE IS TO SMALL, SEE NOTE #6.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 7) MAIN RETURN AIR GRILL TO AHU #2
 (18X18) IS TO SMALL FOR A 5 TON SYSTEM.
  
 8) PLEASE PROVIDE DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR THE GAS FIRE PLACE.
  
 9) OPEN GRILL IN COVERED PORCH WILL NEED
 AN APPROVED EXHAUST HOOD, PER 2004 FBC/M
 505.3 .
  
 10) MASTER BATHROOM (OUTSIDE OF WATER
 CLOSET) WILL NEED AN EXHAUST FAN,PER
 2004 FBC/M 402.3.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-02-07 Cont ID  
Sent By jleech Date 2008-02-07 Time 08:36 Rev Time 0.00
Received By jleech Date 2008-02-07 Time 08:30 Sent To M
Notes
2008-02-07 08:42:44DENIED;
 1.ALL CHANGES TO THE PLANS MUST BE APPROVED BY
 ARCHITECT OF RECORD HAND DRAWN CHANGES NOT PERMITED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status N Date 2007-10-25 Cont ID  
Sent By mperson Date 2007-10-25 Time 10:38 Rev Time 0.00
Received By mperson Date 2007-10-25 Time 10:38 Sent To PC
Notes
2007-10-25 10:39:31NOTE: REVISED ENERGY CALCS. NOT REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-20 Cont ID  
Sent By jleech Date 2006-06-20 Time 10:39 Rev Time 0.00
Received By jleech Date 2006-06-20 Time 10:38 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By jleech Date 2006-03-09 Time 10:02 Rev Time 0.50
Received By jleech Date 2006-03-09 Time 10:02 Sent To Z
Notes
2006-03-09 00:00:00DENIED;
 1.AUTOMATIC CLOTHES WASHER DRAIN
 REQUIRED TO BE 3" SEE FBC-2004 PLUMBING
 SEC. 406.3. CLEANOUT AT 48" AFF.
 2.SECOND FLOOR BATH CANNOT DISCHARGE
 INTO THE VENT FOR THE AUTOMATIC CLOTHES
 WASHER, MUST HAVE ON STACK.
 3.FLOOR PLAN SHOWS TWO TOILETS IN MASTER
 BATHROOM SANITARY RISER DIAGRAMONLY
 SHOWS ONE.
 4.FIRST FLOOR SHOWER BATH VENT REQUIRED
 ON LAV TO VENT BATHROOM GROUP.
 5.PLEASE SUBMIT THE MANUFACTURE'S SPECS.
 FOR THE ICE MACHINE. (FLOOR DRAIN MAY BE
 REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 7 Status P Date 2008-02-22 Cont ID  
Sent By choops Date 2008-02-22 Time 14:16 Rev Time 0.00
Received By choops Date 2008-02-22 Time 14:15 Sent To B
Notes
2008-02-22 14:16:50***APPROVED - REVISION - AS BUILT SITE WALL***
  
  
  
  
 SENT TO "B" - JG

Review Stop Z ZONING
Rev No 6 Status F Date 2008-02-04 Cont ID  
Sent By choops Date 2008-02-04 Time 11:17 Rev Time 0.00
Received By choops Date 2008-02-04 Time 11:17 Sent To B
Notes
2008-02-04 11:19:20***FAILED - REVISION - AS BUILT SITE WALL***
  
  
 1)PROVIDE EASEMENT CONSENT FORMS FROM: THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES, FP&L,
 COMCAST, BELLSOUTH, AND FLORIDA PUBLIC UTILITIES. (SEE
 ATTACHED LIST FOR CONTACTS).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "B" - JG

Review Stop Z ZONING
Rev No 5 Status P Date 2008-01-30 Cont ID  
Sent By choops Date 2008-01-30 Time 14:55 Rev Time 0.00
Received By choops Date 2008-01-30 Time 14:55 Sent To PC
Notes
2008-01-30 14:56:18***APPROVED - LANDSCAPE PLAN SUBMITTAL***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-07-26 Cont ID  
Sent By mmclean Date 2006-07-26 Time 10:55 Rev Time 0.00
Received By mmclean Date 2006-07-26 Time 10:55 Sent To M
Notes
2006-07-26 00:00:00RESTAMP OF PLANS (NEW PLANS).

Review Stop Z ZONING
Rev No 3 Status P Date 2006-07-07 Cont ID  
Sent By mmclean Date 2006-07-07 Time 07:19 Rev Time 0.00
Received By mmclean Date 2006-07-07 Time 07:19 Sent To  
Notes
2006-07-07 00:00:00NOTE: APPROVED WITH FPU UTILITY EASEMENT
 APPROVAL (ONLY UTILITY IN THE 5FT U.E)

Review Stop Z ZONING
Rev No 2 Status F Date 2006-06-12 Cont ID  
Sent By mmclean Date 2006-06-12 Time 15:45 Rev Time 0.00
Received By mmclean Date 2006-06-12 Time 15:45 Sent To I
Notes
2006-06-12 00:00:00DENIED, 2ND REQUEST
 1. THE A/C EQUIPMENT CANNOT BE IN THE
 5FT UTILITY EASEMENT ON THE SIDE OF THE
 HOUSE.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-17 Cont ID  
Sent By mmclean Date 2006-03-17 Time 14:31 Rev Time 0.00
Received By mmclean Date 2006-03-17 Time 14:30 Sent To B
Notes
2006-03-17 00:00:00DENIED,
 1. THE A/C EQUIPMENT CANNOT BE IN THE
 5FT UTILITY EASEMENT ON THE SIDE OF THE
 HOUSE.
 2. MUST PROVIDE THE DIMENSION OF
 PROPOSED DRIVEWAY & WALKWAY. CAN ONLY
 HAVE 875SQ FT OF CONCRETE WITHIN THE
 FIRST 25FT FRONT SETBACK
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK).
 3. THE STRUCTURAL INTRUSION (BALCONY)
 CAN ONLY PROJECT 3FT INTO A SETBACK.
 4. THE STEPS WITHIN THE FRONT SETBACK
 CAN ONLY ENROACH 3FT INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720