Plan Review Details - Permit 06021249
Plan Review Stops For Permit 06021249
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-30 Time 15:24 Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 15:24 Sent To M
Notes
2006-03-30 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By tgordon Date 2006-03-06 Time 10:53 Rev Time 0.00
Received By tgordon Date 2006-03-02 Time 09:13 Sent To  
Notes
2006-03-02 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-31 Cont ID  
Sent By tgordon Date 2006-03-31 Time 14:23 Rev Time 0.30
Received By tgordon Date 2006-03-31 Time 14:23 Sent To  
Notes
2006-03-31 00:00:00*** PROVISO ***
 1)THE DWELLING WILL BE REQUIRED TO HAVE
 SMOKE ALARMS INSTALLED IF NOT ALREADY
 PRESENT, PER 2004 FBC/R 313.1.1, AND SEE
 2004 FEBC 303.1 LEVEL ONE ALTERATION
 INCLUDE REPLACEMENT OF EQUIPMENT.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By tgordon Date 2006-03-06 Time 10:44 Rev Time 0.25
Received By tgordon Date 2006-03-06 Time 10:44 Sent To  
Notes
2006-03-06 00:00:00*** DENIED ***
 1) NEED TO SHOW DUCT (FLEX) SIZES FOR
 BEDROOM #2, AND BATHROOM FOR EACH
 APARTMENT.
  
 2) ALL THE TRANSFER RETURN AIR GRILLS
 ARE TO SMALL, SEE NOTE #3.
  
 3)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  