Plan Review Details - Permit 06021230
Plan Review Stops For Permit 06021230
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-25 Cont ID  
Sent By amorse Date 2006-05-25 Time 16:16 Rev Time 1.00
Received By amorse Date 2006-05-25 Time 16:16 Sent To Z
Notes
2006-05-25 00:00:00 
  
 **************PROVISO****************
  
 1) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 2) NEW DRIVEWAY APPROCH NOT SHOWN ON
 SURVEY, IF REQUIRED SUBMIT SEPARATE
 PERMIT FOR ENGINEERING DEPT. APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-04 Cont ID  
Sent By amorse Date 2006-04-04 Time 11:47 Rev Time 2.00
Received By amorse Date 2006-04-04 Time 11:47 Sent To PC
Notes
2006-04-04 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE
  
 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 4) NEW DRIVEWAY APPROCH WILL REQUIRE
 CITY ENGINEERING DEPT APPROVAL
  
 5) STORM PANEL PRODUCT APPROVALS ARE
 OLD, STATE COVER SHEETS AND DRAWINGS
 HAVE BEEN REVISED ON THE STATE WEB SITE
 ALSO PROVIDE ATTACHMENT TYPE, ANCHOR
 TYPE, EDGE DISTANCE, ETC. (MARK NOA)
  
 6) SINGLE HUNG WINDOW PRODUCT APPROVALS
 ARE REVISED BECAUSE NOA EXPIRED 02/25/06
 NEW FL# 239-R3 DOES NOT COVER SH-701
 (NON-IMPACT)
  
 7) BENCHMARK PRODUCT APPROVALS REQUIRE
 THE NAMI PAPERWORK TO ACCOMPANY THE
 STATE COVER SHEET. ALSO MARK FOR TYPE OF
 DOOR
  
 8) LINTEL PRODUCT APPROVALS, THE STATE
 COVER IS OK BUT THE ACCOMPANYING NOA IS
 FOR 4,6 & 12 INCH LINTEL NOT 8"
  
 9) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 10) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By btrobaug Date 2006-05-16 Time 17:06 Rev Time 0.33
Received By btrobaug Date 2006-05-16 Time 16:51 Sent To B
Notes
2006-05-16 00:00:00 
 PROVISO
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN MUST PRINT AND SIGN THEIR NAME TO
 SAME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-14 Cont ID  
Sent By btrobaug Date 2006-03-14 Time 12:21 Rev Time 0.50
Received By btrobaug Date 2006-03-14 Time 12:06 Sent To B
Notes
2006-03-14 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 225.31 DISCONNECTING MEANS.
 MEANS SHALL BE PROVIDED FOR
 DISCONNECTING ALL UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING
 OR STRUCTURE. SHOW LOCATION ON PLAN.
  
 2} 250.32 TWO OR MORE BUILDINGS OR
 STRUCTURES SUPPLIED FROM A COMMON
 SERVICE.
 (A) GROUNDING ELECTRODE. WHERE TWO OR
 MORE BUILDINGS OR STRUCTURES ARE
 SUPPLIED FROM A COMMON AC SERVICE BY A
 FEEDER(S) OR BRANCH CIRCUIT(S), THE
 GROUNDING ELECTRODE(S) REQUIRED IN PART
 III OF THIS ARTICLE AT EACH BUILDING OR
 STRUCTURE SHALL BE CONNECTED IN THE
 MANNER SPECIFIED IN 250.32(B) OR (C).
 WHERE THERE ARE NO EXISTING GROUNDING
 ELECTRODES, THE GROUNDING ELECTRODE(S)
 REQUIRED IN PART III OF THIS ARTICLE
 SHALL BE INSTALLED.
  
 3} 210.8(A) DWELLING UNITS. ALL
 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 (2) GARAGES, AND ALSO ACCESSORY
 BUILDINGS THAT HAVE A FLOOR LOCATED AT
 OR BELOW GRADE LEVEL NOT INTENDED AS
 HABITABLE ROOMS AND LIMITED TO STORAGE
 AREAS, WORK AREAS, AND AREAS OF SIMILAR
 USE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 10:06 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 10:06 Sent To B
Notes
2006-06-15 00:00:00TO "LMARTINEZ' DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 11:51 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 11:51 Sent To Z
Notes
2006-05-11 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-13 Cont ID  
Sent By adarroug Date 2006-03-13 Time 14:18 Rev Time 0.00
Received By adarroug Date 2006-03-13 Time 14:18 Sent To E
Notes
2006-03-13 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-04 Time   Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 08:58 Sent To  
Notes
2006-03-02 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 4 Status P Date 2006-06-15 Cont ID  
Sent By mmclean Date 2006-06-15 Time 10:44 Rev Time 0.00
Received By mmclean Date 2006-06-15 Time 10:44 Sent To  
Notes
2006-06-15 00:00:00MOVING OF POSITION OF PROPOSED GARAGE.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-05-17 Cont ID  
Sent By mmclean Date 2006-05-17 Time 15:44 Rev Time 0.00
Received By mmclean Date 2006-05-17 Time 15:44 Sent To B
Notes
2006-05-17 00:00:00A SEPERATE PERMIT WAS PULL FOR THE WALL
 THAT IS 6" FROM THE PROPOSED GARAGE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-17 Cont ID  
Sent By mmclean Date 2006-05-17 Time 14:19 Rev Time 0.00
Received By mmclean Date 2006-05-17 Time 14:19 Sent To  
Notes
2006-05-17 00:00:00DENIED,
 1. NEED TO REMOVE THE WALL OFF THE
 SURVEY TO REFLECT THE PLANS OF THE
 PROPOSED GARAGE ONLY.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-10 Cont ID  
Sent By mmclean Date 2006-03-10 Time 07:46 Rev Time 0.00
Received By mmclean Date 2006-03-10 Time 07:46 Sent To I
Notes
2006-03-10 00:00:00DENIED,
 1. CANNOT HAVE WALL ATTACHED TO
 STRUCTURE.
 2. STRUCTURE MUST MEET THE REQUIRED
 SETBACK IN REAR.
 3. MUST PULL A SEPERATE PERMIT FOR
 WALL/GATE (NOT ATTACHED TO STRUCTURE)
 WITH EASEMENT APPROVAL FROM THE CITY OF
 WEST PALM BEACH UTILITY DEPT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720