| Plan Review Stops For Permit 06021223 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2006-04-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-20 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
|
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2006-04-20 00:00:00 | RAS 117 CALCULATIONS OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2006-04-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-14 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-14 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2006-04-14 00:00:00 | ****CORRECTIONS**** | | | ****RAS 117 CALCULATIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)THE CALCULATIONS SUBMITTED REFER TO | | | ASCE7-04.SEE FBC35 AND REVISE TO | | | ASCE7-02. | | | | | | 2.)PROVIDE ORIGINALS.A FAX WAS | | | ACCEPTED FOR REVIEW BUT DOCUMENTS | | | PREPARED BY AN ENGINEER SUBMITTED FOR | | | PUBLIC RECORD ARE REQUIRED TO BE SIGNED, | | | SEALED ORIGINALS, FAC61G15-23. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2006-04-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-13 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-13 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2006-04-13 00:00:00 | ****CORRECTIONS**** | | | ****RAS 117 CALCULATIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)IT IS NOT CLEAR AS TO HOW YOU HAVE | | | DETERMINED THE SQUARE FEET PER FASTENER, | | | .667 IN THE FORMULA FOR FY TO ARRIVE AT | | | THE FASTENER VALUE OF 40 LBF.SUBMIT | | | CALCULATIONS IN ACCORDANCE WITH RAS 117, | | | 10.4.2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2006-04-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-12 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-12 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2006-04-12 00:00:00 | ****CORRECTIONS**** | | | CALCULATIONS | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)NO CALCULATIONS IN ACCORDANCE WITH | | | RAS117 WERE SUBMITTED.WIND LOADS | | | CALCULATIONS WERE PROVIDED BUT THIS IS | | | NOT THE SAME AS ENHANCED FASTENING IN | | | ACCORDANCE WITH RAS117 AS REQUIRED BY | | | THE NOA.A COPY HAS BEEN RETAINED BY | | | THIS OFFICE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-04-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-11 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-11 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2006-04-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-04 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-04 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2006-04-04 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY | | | | | | | | | 1.)SEE THE NOA, PRODUCT LIMITATION #7. | | | IT STATES THAT CALCULATIONS IN | | | ACCORDANCE WITH RAS117 ARE REQUIRED.NO | | | CALCULATIONS WERE INCLUDED IN THE | | | SPECIFICATION FROM THE ENGINEER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-03-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-03-27 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-03-27 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2006-03-27 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)CALCULATIONS REQUIRED, SEE NOA | | | PRODUCT LIMITATION #7.THE ENGINEERING | | | DOCUMENT SUBMITTED IS A SPECIFICATION. | | | CALCULATIONS IN ACCORDANCE WITH RAS117 | | | ARE REQUIRED. | | | | | | 2.)TWO COPIES OF ALL PERMIT DOCUMENTS | | | REQUIRED.ONLY ONE LETTER FROM THE | | | ENGINEER WAS SUBMITTED. | | | | | | 3.)PRIOR TO RESUBMITTING, PICK UP THE | | | DENIED PACKAGE AND INCLUDE THIS | | | DOCUMENTATION IN YOUR RESUBMITTAL.YOUR | | | APPLICATION, NOC, AND OTHER REQUIRED | | | DOCUMENTS WERE IN THE DENIED PACKAGE | | | WHICH WAS STILL AT THE FRONT COUNTER | | | WHEN YOU RESUBMITTED.THE TWO PACKAGES | | | (DENIED PACKAGE, NEW PAPERWORK) MUST BE | | | COMBINED PRIOR TO RESUBMITTAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-03-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-03-08 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-03-08 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2006-03-08 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)SEE PREVIOUS LIST.ENHANCED | | | FASTENING TO BE CALCULATED BY A DESIGN | | | PROFESSIONAL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-02-27 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-02-27 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2006-02-27 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY | | | | | | | | | ____1.)A NOTICE OF COMMENCEMENT | | | MUST BE FILED WITH THE CLERK OF COURTS | | | BEFORE A PERMIT CAN BE ISSUED. | | | | | | ____2.)CONTRACTOR IS TO PROVIDE THE | | | MEAN ROOF HEIGHT ON THE APPLICATION. | | | | | | ____3.)CONTRACTOR IS TO PROVIDE THE | | | ROOF PITCH ON THE APPLICATION. | | | | | | _XX_4.)CONTRACTOR IS TO PROVIDE THE | | | ROOF DECK TYPE ON THE APPLICATION. | | | | | | ____5.)FLORIDA STATE OR LOCAL | | | PRODUCT APPROVAL REQUIRED IN ADDITION TO | | | THE EVALUATION REPORT SUBMITTED, | | | FAC9B72.WWW.FLORIDABUILDING.ORG | | | | | | _XX_6.)FOR THE FLAT DECK, SELECT THE | | | APPROVED ASSEMBLY YOU ARE USING. | | | | | | ____7.)THE SYSTEM PROVIDED HAS A LOW | | | PRESSURE FOR ZONE ____. | | | | | | ____8.)THE SYSTEM PROVIDED STATES | | | LIMITATION #9, ENHANCED FASTENING NOT | | | ALLOWED. | | | | | | ____9.)PROVIDE AN ENGINEER?S LETTER | | | TO CONFIRM THAT THE ROOF WHICH CURRENTLY | | | HAS SHINGLES INSTALLED CAN ACCOMMODATE | | | THE ADDITIONAL WEIGHT OF THE PROPOSED | | | TILE. | | | | | | _XX_ 10.)SEE NOTE D, ENHANCED | | | FASTENING TO BE DESIGNED BY A QUALIFIED | | | DESIGN PROFESSIONAL. | | | | | | | | | |
|
|