Plan Review Details - Permit 06021223
Plan Review Stops For Permit 06021223
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-04-20 Cont ID  
Sent By shill Date 2006-04-20 Time 16:17 Rev Time 0.00
Received By shill Date   Time 18:01 Sent To  
Notes
2006-04-20 00:00:00RAS 117 CALCULATIONS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2006-04-14 Cont ID  
Sent By shill Date 2006-04-14 Time 18:00 Rev Time 0.00
Received By shill Date 2006-04-14 Time 18:00 Sent To  
Notes
2006-04-14 00:00:00****CORRECTIONS****
 ****RAS 117 CALCULATIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE CALCULATIONS SUBMITTED REFER TO
 ASCE7-04.SEE FBC35 AND REVISE TO
 ASCE7-02.
  
 2.)PROVIDE ORIGINALS.A FAX WAS
 ACCEPTED FOR REVIEW BUT DOCUMENTS
 PREPARED BY AN ENGINEER SUBMITTED FOR
 PUBLIC RECORD ARE REQUIRED TO BE SIGNED,
 SEALED ORIGINALS, FAC61G15-23.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-04-13 Cont ID  
Sent By shill Date 2006-04-13 Time 18:20 Rev Time 0.00
Received By shill Date 2006-04-13 Time 18:20 Sent To  
Notes
2006-04-13 00:00:00****CORRECTIONS****
 ****RAS 117 CALCULATIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)IT IS NOT CLEAR AS TO HOW YOU HAVE
 DETERMINED THE SQUARE FEET PER FASTENER,
 .667 IN THE FORMULA FOR FY TO ARRIVE AT
 THE FASTENER VALUE OF 40 LBF.SUBMIT
 CALCULATIONS IN ACCORDANCE WITH RAS 117,
 10.4.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-04-12 Cont ID  
Sent By shill Date 2006-04-12 Time 14:43 Rev Time 0.00
Received By shill Date 2006-04-12 Time 14:43 Sent To  
Notes
2006-04-12 00:00:00****CORRECTIONS****
 CALCULATIONS
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)NO CALCULATIONS IN ACCORDANCE WITH
 RAS117 WERE SUBMITTED.WIND LOADS
 CALCULATIONS WERE PROVIDED BUT THIS IS
 NOT THE SAME AS ENHANCED FASTENING IN
 ACCORDANCE WITH RAS117 AS REQUIRED BY
 THE NOA.A COPY HAS BEEN RETAINED BY
 THIS OFFICE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-04-11 Cont ID  
Sent By shill Date 2006-04-11 Time 12:19 Rev Time 0.00
Received By shill Date 2006-04-11 Time 12:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-04-04 Cont ID  
Sent By shill Date 2006-04-04 Time 16:32 Rev Time 0.00
Received By shill Date 2006-04-04 Time 16:32 Sent To  
Notes
2006-04-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
  
 1.)SEE THE NOA, PRODUCT LIMITATION #7.
 IT STATES THAT CALCULATIONS IN
 ACCORDANCE WITH RAS117 ARE REQUIRED.NO
 CALCULATIONS WERE INCLUDED IN THE
 SPECIFICATION FROM THE ENGINEER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-27 Cont ID  
Sent By shill Date 2006-03-27 Time 17:22 Rev Time 0.00
Received By shill Date 2006-03-27 Time 17:22 Sent To  
Notes
2006-03-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)CALCULATIONS REQUIRED, SEE NOA
 PRODUCT LIMITATION #7.THE ENGINEERING
 DOCUMENT SUBMITTED IS A SPECIFICATION.
 CALCULATIONS IN ACCORDANCE WITH RAS117
 ARE REQUIRED.
  
 2.)TWO COPIES OF ALL PERMIT DOCUMENTS
 REQUIRED.ONLY ONE LETTER FROM THE
 ENGINEER WAS SUBMITTED.
  
 3.)PRIOR TO RESUBMITTING, PICK UP THE
 DENIED PACKAGE AND INCLUDE THIS
 DOCUMENTATION IN YOUR RESUBMITTAL.YOUR
 APPLICATION, NOC, AND OTHER REQUIRED
 DOCUMENTS WERE IN THE DENIED PACKAGE
 WHICH WAS STILL AT THE FRONT COUNTER
 WHEN YOU RESUBMITTED.THE TWO PACKAGES
 (DENIED PACKAGE, NEW PAPERWORK) MUST BE
 COMBINED PRIOR TO RESUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-08 Cont ID  
Sent By shill Date 2006-03-08 Time 14:13 Rev Time 0.00
Received By shill Date 2006-03-08 Time 14:13 Sent To  
Notes
2006-03-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)SEE PREVIOUS LIST.ENHANCED
 FASTENING TO BE CALCULATED BY A DESIGN
 PROFESSIONAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By shill Date 2006-02-27 Time 12:16 Rev Time 0.00
Received By shill Date 2006-02-27 Time 12:16 Sent To  
Notes
2006-02-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
  
 ____1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE
 MEAN ROOF HEIGHT ON THE APPLICATION.
  
 ____3.)CONTRACTOR IS TO PROVIDE THE
 ROOF PITCH ON THE APPLICATION.
  
 _XX_4.)CONTRACTOR IS TO PROVIDE THE
 ROOF DECK TYPE ON THE APPLICATION.
  
 ____5.)FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_6.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____7.)THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ____.
  
 ____8.)THE SYSTEM PROVIDED STATES
 LIMITATION #9, ENHANCED FASTENING NOT
 ALLOWED.
  
 ____9.)PROVIDE AN ENGINEER?S LETTER
 TO CONFIRM THAT THE ROOF WHICH CURRENTLY
 HAS SHINGLES INSTALLED CAN ACCOMMODATE
 THE ADDITIONAL WEIGHT OF THE PROPOSED
 TILE.
  
 _XX_ 10.)SEE NOTE D, ENHANCED
 FASTENING TO BE DESIGNED BY A QUALIFIED
 DESIGN PROFESSIONAL.
  
  
  