| Plan Review Stops For Permit 06021083 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-03-29 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-03-29 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-03-29 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2006-03-29 00:00:00 | NEEDS FOR SUITE. | | | USE EXT # 0052 FOR THIS PERMIT BIG APPLE | | | PIZZA : 831 VILLAGE BLVD # 803 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2006-11-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-11-05 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-11-05 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2006-11-05 16:11:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | 1.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | | IN ADDITON TO THE NOA SUBMITTED, FAC9B72. | | | WWW.FLORIDABUILIDNG.ORG | | | | | | 2.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | | OF RECORD, FBC*106.3.3. | | | | | | 3.)SUBMIT LEGIBLE PRODUCT APPROVALS.THEY MAY BE | | | AVAILABLE AT WWW.MIAMIDADE.GOV (FIND A DEPARTMENT, | | | BUILDING CODE COMPLIANCE, PRODUCT CONTROL) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-10-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-10-18 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-10-18 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2006-10-18 11:49:35 | REVISED A1, A-A1,A3, A3A,FS2.1 DATED 9/15/06 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-08-11 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-08-11 |
Time |
11:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-06-22 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-06-22 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2006-06-22 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | FROM PREVIOUS REVIEW: | | | | | | 8.)PROVIDE FIRE SPRINKLER PLANS, | | | FBC*106.3.5.1.1(5). | | | | | | 2ND REVIEW - ARCHITECT'S RESPONSE THAT | | | THIS WILL BE DONE LATER IS ACKNOWLEDGED. | | | HOWEVER, IF SPRINKLERS ARE REQUIED IN | | | THIS BUILDING FOR CODE COMPLIANCE, A | | | FIRE SPRINKLER LAYOUT MUST BE PROVIDED | | | PRIOR TO PERMIT ISSUANCE. | | | | | | NEW COMMENT: | | | | | | PLEASE REMOVE OLD VOIDED SHEETS FROM THE | | | COLLATED SET AND SUBMIT SEPARATELY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-05-08 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-05-08 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2006-05-08 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)DECLARE OCCUPANCY, FBC CHAPTER 3. | | | | | | 3.)SIGN OWNER/AGENT LINE OF ENERGY | | | CALC, FBC13-103.1 | | | | | | 4.)THE ENERGY CALC STATES SQUARE FOOT | | | AREA AS 1685, PLAN IS 1774. | | | | | | 5.)THE ARCH ALUMINUM PRODUCT APPROVAL | | | IS NOT LEGIBLE AND IS EXPIRED, 2001 | | | CODE.IF A FLORIDA STATE PRODUCT | | | APPROVAL IS NOT AVAILABLE, A LOCAL | | | PRODUCT APPROVAL IS REQUIRED.A LOCAL | | | CAN BE ISSUED FROM THE NOA, BUT A | | | LEGIBLE COPY IS REQUIRED.THE | | | DOCUMENTATION PROVIDED APPEARS | | | INCOMPLETE AS THERE IS SOME INFORMATION | | | FROM MIAMI DADE BUT NO NOA NUMBER. | | | FAC9B72, WWW.FLORIDABUILDING.ORG | | | | | | 6.)PRODUCT APPROVALS ARE TO BE | | | APPROVED BY THE DESIGNER OF RECORD, | | | FBC*106.3.3. | | | | | | 7.)PROVIDE WIND DESIGN CRITERIA | | | FBC1603.1.4. | | | | | | 8.)PROVIDE FIRE SPRINKLER PLANS, | | | FBC*106.3.5.1.1(5). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2006-12-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-09 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-09 |
Time |
14:04 |
Sent To |
FIRE |
|
| Notes |
| 2006-12-09 14:28:28 | REV OK, SENT TO FIRE FOR REVIEW OF REMOVAL OF FIRE | | | DEVICES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-17 |
Time |
19:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-17 |
Time |
19:06 |
Sent To |
|
|
| Notes |
| 2006-10-17 19:54:01 | REV'S, GENERAL. | | | A/C LOAD ETC. | | | | | | OK, STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-24 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-24 |
Time |
17:29 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-08-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-20 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-20 |
Time |
11:07 |
Sent To |
PC |
|
| Notes |
| 2006-08-20 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE NOTE #1 FROM | | | PREVIOUS REVIEW. PLEASE SEE OVER-RIDES | | | REQUIRD AT INGRESS/EGRESS AREAS FOR THE | | | OCCUPANT TO VIEW LTS BEING CONTROLLED. | | | PLEASE SEE REAR DOOR ALSO. | | | PLEASE SEE SEPARATE SPACE (BATH ROOMS). | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND | | | .1.3. | | | PLEASE BE SURE ALL NEW DEVICES BEING | | | SHOWN FOR OVERRIDES, IN ALL LACATIONS | | | SHALL BE SPECIFIED WITH TYPE AND TIME | | | FOR OVER-RIDE. IF OCC SENSOR TYPE, (MAX | | | 30 MINS) IF TIMER TYPE (4HRS MAX). | | | | | | 2) NOTE: PLEASE SEE SHEET E-5 IN SET IS | | | THE SAME AS THE NEW REVISED SHEET E-3. | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS OR | | | SHEETS WHICH HAVE BEEN REPLACED WITH NEW | | | REVISED SHEETS. PLEASE BE AWARW THAT | | | SOME OF THE NUMBERING OF SHEETS HAS | | | CHANGED BY THE DEISGNERS. | | | | | | | | | ** CALLED CONTRACTOR. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-08-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-06 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-06 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2006-08-06 00:00:00 | **** UNSAT 3RD REVIEW ****** | | | | | | ** PLEASE SEE SOME COMMENTS FROM THE TWO | | | | | | PREVIOUS REVIEW STILL NEED TO BE | | | ADDRESSED. | | | NOTES BELOW ARE TAKEN FROM 2ND REVIEW. | | | | | | | | | 1) NOTE: NO, PLEASE SEE OVER RIDE | | | DEVICES ARE NOT SHOWN AND THE DETAILS OF | | | THE TYPE AND HRS OF OVERRIDE IS NOT ON | | | PLANS. RESPONSE LTR MENTIONS THIS IS | | | DONE, HOWEVER PLEASE SEE THESE | | | OVERIRIDES COULD NOT BE LOCATED AT THE | | | POINT OF ENTRANCE TO THE SPACE. PLEASE | | | SEE FRONT AND REAR INGRESS/EGRESS. | | | PLEASE SEE SEPARATE SPACES AS ALSO | | | PREVIOUSLY REQUESTED. PLEASE SEE ANY | | | AREAS W/ FLR TO CEILING HEIGHT | | | PARTITIONS. (BATH RMS ETC) | | | CALCS SEEM TO BE OK, AND OTHER ITEMS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE NOTE #2 FROM | | | PREVIOUS REVIEW WHICH WAS TYPED IN | | | ERROR. PLEASE SEE A 413 WAS TYPED | | | INSTEAD OF 415. IN EITHER CASE THE NOTES | | | REFERENCED WAS TO PROVIDE LIGHTING | | | CONTROLS , SCHEDULING OVER -RIDES ETC. | | | PLEASE SEE THAT RESPONSE WAS FOR VOLTAGE | | | DROP WHICH WAS ALSO CORRECT. | | | PLEASE SEE ALL OF FBC 2004 CHAPTER 13 AS | | | ALKL OF THE ABOVE APPLIES. | | | PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3 | | | PLEASE SEE THAT ENERGY CALCULATIONS MUST | | | BE DONE PER EITHER SPACE BY SPACE OR | | | ENTIRE AREA. | | | PLEASE ALSO SEE FORM WHICH IS TO BE | | | USED. | | | 13-415.1.AB.1, 13-415.1.ABC.1 | | | | | | 2) NOTE: NO, PLEASE SEE TWO PREVIOUS | | | REVIEW WHICH STATED THE ADDTIONAL | | | SERVICE IS NOT AND SHALL NOT BE GRANTED | | | UNLESS PROVIDING COMPELETED INFORMATION | | | FOR "SPECIAL PERMISSION" WHICH MUST BE | | | GRANTED BY THE AHJ. PLEASE SEE 230.2. | | | DUE TO INSUFFICIENT INFORMATION AND | | | BASED ON WHAT HAS BEEN SUBMITTED THE | | | ADDITIONAL SERVICE IS NOT GRANTED. | | | PLEASE SEE THIS IS ONE BUILDING AND THIS | | | IS A TENANT SPACE IN ONE BUILDING. IN | | | ORDER FOR THIS SPACE TO BE CONSIDERED A | | | SEPARATE "BUILDING" ON ITS OWN FOR A | | | SEPARATE SERVICE, IT MUST CONTAIN "FIRE | | | WALLS ON EACH SIDE. PLEASE SEE FBC 2004 | | | DEFINITIONS OF FIREWALL, WHICH IS 4HRS | | | AND IS CONSTRUCTED AS TO ALLOW COLLAPSE | | | ON EACH SIDE WITHOUT AFFECTING THE | | | STRUCTURAL INTEGRITY OF ADJACENT | | | BUILDING. PLEASE KNOW AS THIS LOCATION | | | DOES NOT CONTAIN SUCH STRUCTURAL | | | ELEMENTS, THEN ONLY THE EXCEPTIONS | | | ALLOWED IN THE NEC WILL BE CONSIDERED. | | | AT THIS TIME ANDBASED ON PLANS NO | | | CONSIDERATION CAN BE MADE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE PLANS STILL DO NOT | | | INDICATE LOCATION OF THE EXISTING | | | SERVICE, LOADS ETC. | | | PLEASE SEE A NOTE ON THE RISER DIAGRAM | | | MENTIONS SERVICE IS EXISTING, YET | | | SERVICE IS ALSO NOTED AS NEW?? | | | PLEASE PREVIOUS NOTES WITH RESPECT TO | | | THE SERVICE AND LOCATIONS. | | | THE NEW SERVICE AS SHOWN IS NOT APPROVED | | | BY THIS AHJ AT THIS TIME. | | | IF THIS IS BEING FED FROM AN EXISTING | | | LOCATION OR GUTTER OR OTHER MAIN, PLEASE | | | SHOW. | | | 230.2, 230.72, 230.70, 215.5 | | | | | | 3) NOTE:OK,PLEASE BE SURE TO DO THE | | | SAME WHEN RESUBMITTING PLANS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE PREVIOUS REVIEW | | | NOTES WHERE IT WAS REQUESTED THAT ALL | | | THE OLD/VOIDED SHEETS BE COMPLETELY | | | REMOVED FROM SETS AND ONLY TO INSERT NEW | | | REVISED SHEETS INTO SETS FOR REVIEW AND | | | STAMPING. PLEASE SEE THIS WAS NOT DONE. | | | PLEASE DO SO AND ONLY SUBMIT ONE COPY OF | | | THE OLD/VOIDED REMOVED SHEETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-06-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-20 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-20 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2006-06-20 00:00:00 | *********UNSAT ********* | | | | | | ** PLEASE SEE SOME COMMENTS FROM | | | PREVIOUS REVIEW. | | | | | | | | | 1) NOTE: PELASE SEE NOTE #2 FROM | | | PREVIOUS REVIEW WHICH WAS TYPED IN | | | ERROR. PLEASE SEE A 413 WAS TYPED | | | INSTEAD OF 415. IN EITHER CASE THE NOTES | | | REFERENCED WAS TO PROVIDE LIGHTING | | | CONTROLS , SCHEDULING OVER -RIDES ETC. | | | PLEASE SEE THAT RESPONSE WAS FOR VOLTAGE | | | DROP WHICH WAS ALSO CORRECT. | | | PLEASE SEE ALL OF FBC 2004 CHAPTER 13 AS | | | ALKL OF THE ABOVE APPLIES. | | | PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3 | | | PLEASE SEE THAT ENERGY CALCULATIONS MUST | | | BE DONE PER EITHER SPACE BY SPACE OR | | | ENTIRE AREA. | | | PLEASE ALSO SEE FORM WHICH IS TO BE | | | USED. | | | 13-415.1.AB.1, 13-415.1.ABC.1 | | | | | | 2) NOTE: PLEASE SEE PLANS STILL DO NOT | | | INDICATE LOCATION OF THE EXISTING | | | SERVICE, LOADS ETC. | | | PLEASE SEE A NOTE ON THE RISER DIAGRAM | | | MENTIONS SERVICE IS EXISTING, YET | | | SERVICE IS ALSO NOTED AS NEW?? | | | PLEASE PREVIOUS NOTES WITH RESPECT TO | | | THE SERVICE AND LOCATIONS. | | | THE NEW SERVICE AS SHOWN IS NOT APPROVED | | | BY THIS AHJ AT THIS TIME. | | | IF THIS IS BEING FED FROM AN EXISTING | | | LOCATION OR GUTTER OR OTHER MAIN, PLEASE | | | SHOW. | | | 230.2, 230.72, 230.70, 215.5 | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW | | | NOTES WHERE IT WAS REQUESTED THAT ALL | | | THE OLD/VOIDED SHEETS BE COMPLETELY | | | REMOVED FROM SETS AND ONLY TO INSERT NEW | | | REVISED SHEETS INTO SETS FOR REVIEW AND | | | STAMPING. PLEASE SEE THIS WAS NOT DONE. | | | PLEASE DO SO AND ONLY SUBMIT ONE COPY OF | | | THE OLD/VOIDED REMOVED SHEETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-29 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-28 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2006-03-29 00:00:00 | ***** UNSAT ******** | | | | | | | | | 1)NOTE: PLEASE REFERENCE THE FOLLOWING | | | CODES. NFPA-70 2002, NFPA-101 2003, | | | NFPA-72 2002. | | | | | | 2)NOTE: PLEASE SEE FBC CHAPTER 13, | | | 13-413.1.ABC.1.1, & .2. | | | PLEASE PROVIDE SCHEDULING, CIRCUITING | | | AND SPACE CONTROL DEVICES FOR OVERIDES | | | AND SPACE CONTROL OVERIDE FOR SPACE. | | | | | | 3)NOTE: PLEASE SEE SERVICE AS SHOWN DOES | | | NOT DEPICT EXISTING SERVICE AND | | | LOCATION. PLEASE KNOW, AN ADDITTIONAL | | | SERVICE MAY NOT BE GRANTED. PLEASE | | | PROVIDE COMPLETE LAYOUT AND LOCATIONS OF | | | EXISTING SERVICE, SIZE, LOAD | | | CALCULATIONS, ETC | | | THESE ITEMS WILL BE REVIEWED TO SEE "IF" | | | AN ADDITIONAL SERVICE MAY BE GRANTED. | | | PLEASE KNOW, SERVICE AS SHOWN IS NOT | | | PERMITTED AT THIS TIME. | | | 230.2,230.70.230.72, 215.5 | | | | | | 4)NOTE: PLEASE VERIFY SERVICE AS SHOWN, | | | AS THE FPL METERING DEVICE IS SHOWN ON | | | THE LOAD SIDE OF THE MAIN DISCONNECT. | | | PLEASE SEE FPL MININUM SERVICE | | | GUIDELINES. | | | THE DISCONNECT IS NOT PERMITTED AS | | | SHOWN. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | CONDUCTOR DOES NOT SHOW ANY GROUNDING | | | ELECTRODE SYSTEM, ONLY A BOND TO | | | EXISTINGMAIN NEUTRAL. THIS IS UNCLEAR | | | AT THIS TIME. | | | IF MORE THAN ONE SERVICE IS PERMITTED, | | | THE TWO OR MORE GROUNDING ELECTRODE | | | SYSTEMS SHALL BE BONDED TOGETHER, | | | HOWEVER THERE STILL MUST BE A GROUNDING | | | ELECTRODE SYSTEM. | | | 250.50,250.92 ETC | | | | | | 6) NOTE: PLEASE SEE COLOR CODING AS | | | SHOWN FOR 277/480V SYSTEMS SHALL BE BE | | | BROWN/PURPLE/YELLOW, AS "ORANGE" IS | | | STRICLY FOR A DELTA "HIGH-LEG SYSTEM | | | WHICH DOES NOT APPEAR TO BE SHOWN. | | | | | | 7) NOTE: PLEASE SUBMIT ALL AIC RATINGS | | | FOR ALL NEW MAINS/ SERVICE EQUIPMENT. | | | 110.9,215.5 | | | | | | 8)NOTE: PLEASE KNOW, ANY "LOCK-OUT" | | | DEVICS MUST BE APPROVED BY THE AHJ, | | | BEFORE INSTALLATION. PLEASE KNOW, THERE | | | ARE MANY DEVICES WHICH ARE NOT | | | ACCEPTABLE TO THIS AHJ AS THE | | | DISCONNECTING LOCK OUT DEVICE. | | | THE ONLY LOCK OUT DEVICE ACCEPTABLE, | | | MUST BE AN INTEGRAL PART OF THE BREAKER. | | | IT SHALL NOT HAVE THE ABILITY TO BE | | | REMOVED UNLESS BREAKER IS REMOVED FROM | | | PANEL. | | | 90.4,422.31 | | | | | | 9) NOTE: PLEASE SEE THAT PANEL SCHEDULE | | | SHALL REFLECT THE EQUIPMENT INSTEAD OF A | | | NUMERICAL SCHEDULE TO REFELCT AN | | | EQUIPMENT SCHEDULE WHICH MAY/MAY NOT BE | | | LOCATED IN PANEL. | | | PLEASE ADJUST PANEL SCHEDULE TO | | | CORRELATE WITH EQUIPMENT SCHEDULE A THIS | | | TIME.408.4, 215.5 | | | | | | 10) NOTE: PLEASE CLARIFY CIRCUTING FOR | | | RT GFI'S. PLANS INDICATE #24? | | | PLEASE CORRELATE WITH CIRCUIT INTENDED | | | FOR USE. | | | 215.5 | | | | | | 11)NOTE: PLEASE SEE CODE REFLECTED ON | | | PLANS FOR KTICHENGFI/GFI RECEPTS | | | PROTECTIONSEEMS TO BE MISPRINTED. | | | PLEASE SEE 2002 NEC , WHICH INDICATE | | | 210.8B3". "B2" IS FOR ROOF TOP RECEPTS. | | | | | | 12) NOTE: PLEASE SEE 220.12A FOR LOAD ON | | | "SHOW WINDOWS". PLEASE SPECIFY THE | | | LINEAR FT.IT APPEARS THE OPTION SHOWN IN | | | 220.3(B)(7) IS BEING USED IN LIEU OF | | | FT/VA. | | | PLEASE ONLY VERIFY. | | | | | | ** PLEASE BE SURE TO SEE COMMENTS FROM | | | OTHER REVIEWERS WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE BE SURE TO COMPLETELT REMOVE | | | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY | | | INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONLY ONE SET OF ANY OLD/VOIDED REMOVED | | | SHEETS NEED BE SUBMITTED BACK SEPARTELY | | | FOR REFERENCE. | | | | | | PLEASE SUBMITTHE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-21 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-21 |
Time |
10:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-11 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-11 |
Time |
14:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-06-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-23 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-23 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2006-06-23 00:00:00 | ***DENIED*** | | | | | | PLEASE SEE BUILDING REVIEW COMMENT | | | REGARDING SUBMITTAL OF FIRE PROTECTION | | | SHEETS FOR REVIEW. PLEASE NOTE THAT THIS | | | REQUIREMENT IS IN ADDITION TO SEPARATE | | | SHOP DRAWINGS AND PERMIT PRIOR TO SYSTEM | | | INSTALLATION. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-04-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-04-20 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-04-20 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2006-04-20 00:00:00 | ******DENIED****** | | | | | | 1) IT WOULD APPEAR THAT THE OCCUPANT | | | LOAD BASED ON 15 SQ' PER PERSON IS BASED | | | ON ASSEMBLY OCCUPANCY, HOWEVER THE | | | OCCUPANT LOAD < 50 DOES NOT MEET THE | | | DEFINITION CRITERIA OF NFPA 101, 2003 | | | EDITION SECTION 3.3.152.2. | | | | | | 2) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | 3) IN ADDITION TO HOOD/SUPPRESSION | | | EQUIPMENT, SEPARATE SHOP DRAWING AND | | | PERMITS ARE REQUIRED FOR FIRE SPRINKLER | | | AND FIRE ALARM REMODEL. | | | | | | 4) DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 5) 2A-10B,C RATED FIRE EXTINGUISHER(S) | | | ARE REQUIRED AT DISTANCES NOT TO EXCEED | | | 75' TRAVEL DISTANCE. "K" TYPE FIRE | | | EXTINGUISHER REQUIRED IN KITCHEN. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2006-07-26 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-26 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-26 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2006-07-26 00:00:00 | PAUL SCHMITZ | | | FBC 2004 FUEL GAS CODE, PLAN REVIEW | | | | | | PROVISS | | | | | | PREVIOUS NOTE. | | | | | | 10)EMERGENCY HOOD SHUT OFF VALVE | | | (E) AUTOMATIC SHUT OFF VALVE. | | | | | | GAS EMERGENCY SOV TO BEINSTALLED BELOW | | | THE CEILIMG. MANUAL SOV AND UNION | | | UPSTREAM OF EMERGENCY SHUT OFF VALVE. | | | | | | PLACED CALL TO ENG. OF RECORD | | | MR.GARY STENLUND 813-251-6848 | | | TO CHANGE TO BELOW CEILING. 7-3-06 | | | | | | END OF COMMENTS QUESTIOINS561-805-6692 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2006-07-03 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-03 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-03 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2006-07-03 00:00:00 | PAUL SCHMITZ | | | FBC 2004 FUEL GAS CODE, PLAN REVIEW | | | | | | UNSAT | | | | | | PREVIOUS NOTE. | | | | | | 10)EMERGENCY HOOD SHUT OFF VALVE | | | (E) AUTOMATIC SHUT OFF VALVE. | | | | | | GAS EMERGENCY SOV TO BEINSTALLED BELOW | | | THE CEILIMG. MANUAL SOV AND UNION | | | UPSTREAM OF EMERGENCY SHUT OFF VALVE. | | | | | | PLACED CALL TO ENG. OF RECORD | | | MR.GARY STENLUND 813-251-6848 | | | TO CHANGE TO BELOW CEILING. 7-3-06 | | | | | | END OF COMMENTS QUESTIOINS561-805-6692 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-05-06 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-05-06 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-05-06 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2006-05-06 00:00:00 | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | | | | UNSAT | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR THE GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304 | | | . | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 10)EMERGENCY HOOD SHUT OFF VALVE | | | (E) AUTOMATIC SHUT OFF VALVE. | | | NFPA-96 SEC 10.5.1, NFPA-1 SEC 50.4/7.1 | | | GAS EMERGENCY SOV TO BE 42" TO 48" AFF | | | | | | QUESTIONS 561-805-6692PAUL SCHMITZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-05 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-05 |
Time |
11:21 |
Sent To |
E |
|
| Notes |
| 2006-12-05 11:21:21 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-30 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-30 |
Time |
09:11 |
Sent To |
B |
|
| Notes |
| 2006-10-30 09:11:36 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-02 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-02 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2006-10-17 13:40:37 | TO "COMM" BD#27 | | 2006-10-02 00:00:00 | WAITING FOR "COMM" BD-REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-23 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-23 |
Time |
16:07 |
Sent To |
B |
|
| Notes |
| 2006-08-23 00:00:00 | WAITING FOR "COMM" BD-NEW SHEETS FOR | | | PLUMB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-17 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-17 |
Time |
16:05 |
Sent To |
E |
|
| Notes |
| 2006-08-17 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-05 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-05 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2006-08-05 00:00:00 | TO COMM BOARD #38 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-07-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-21 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-21 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-06-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-07 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-07 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2006-06-20 00:00:00 | TO "COMM" BD#30 | | 2006-06-07 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-05-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-05-08 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-02-23 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2006-03-22 00:00:00 | TO COMM BOARD #3. | | 2006-02-23 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-11-02 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-11-02 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-10-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-10-27 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-10-27 |
Time |
07:50 |
Sent To |
P |
|
| Notes |
| 2006-10-27 08:07:07 | PROVISO | | | 1) PLEASE REFER TO SECTION 606.2.1 SMOKE DETECTION AND | | | 606.4.1 SUPERVISON. | | | 2) PLEASE PROVIDE HANGING DETAIL ON HOOD WHEN HOOD | | | PLANS ARE SUBMITED FOR PERMIT. | | | 3) PLEASE PROVIDE TIE DOWN DETAIL FOR ALL CURBS TO ROOF | | | FOR ROUGH INSPECTION . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732. | | 2006-10-27 07:52:28 | PROVISO |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-08-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-08-16 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-08-16 |
Time |
17:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-08-14 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-07-14 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-07-14 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2006-07-14 00:00:00 | PRIVISO | | | 1) PLEASE PROVIDE HANGING DETAIL FOR | | | KITCHEN HOOD. | | | 2) PLEASE PROVIDE A DETAIL FOR TIEING | | | DOWN INTAKE AND EXHAUST FAN ON THE ROOF. | | | 3) CAN NOT FIND THE CHANGES ON PAGE M-3 | | | PLEASE MARK THE CHANGES AND RESUBMIT | | | PLANS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-04-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-04-10 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-04-10 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2006-04-10 00:00:00 | PASS PRIVISO | | | 1) PLEASE REFER TO NFPA 96 SECTION | | | 7.8.2.1 8B FAN TERMINATION ON ROOF. | | | 2) ADDITINAL MECHANICAL PERMITS REQUIRED | | | FOR WALK IN COOLERS,HOODS AND HOOD | | | SUPPRESSION. | | | 3) PLEASE SUBMIT TWO COPIES OF | | | MANUFACTURERS INSTALLATION | | | INSTRUCTIONS ON THE WALK IN COOLERS | | | WITH THE APPLICATION. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-11-01 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-11-01 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2006-11-01 15:02:58 | 11-01-06 REVISION SHT P-2, P-3 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-07-02 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-02 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-02 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-05-06 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-05-06 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-05-06 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2006-05-06 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | UNSAT | | | | | | 1) SHT P-2 GRASE TRAP TO BE SIZED BY | | | W P BEACHWATERPLANT LAB SUPERVISOR | | | INDUSTRIAL COORDINATOR, LYNN MASSON | | | OFFICE 561-822-2271 | | | E-MAIL [email protected] | | | | | | 2) SHT FS-2.1 PROVIDE TWO COPIES OF | | | COMMENTS SPECIFICATION SHEETS LOG NUMBER | | | P2-06-405, FROM DEPARTMENT OF HOTEL | | | BUSINESS REGULATION. | | | | | | 3) SHT A-2 REST ROOMS | | | 11-4.16.2 CLEAR FLOOR SPACE. | | | CLEAR FLOOR SPACE FOR WATER CLOSETS NOT | | | IN STALLS SHALL COMPLY WITH FIGURE | | | 11-28. CLEAR FLOOR SPACE MAY BE ARRANGED | | | TO ALLOW EITHER A LEFT-HANDED OR | | | RIGHT-HANDED APPROACH. | | | | | | 4)SHT P-3 GAS RISER DIAGRAM | | | SEE GAS PLAN REVIEW OMMENTS | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | | | | |
|
|