Plan Review Details - Permit 06021083
Plan Review Stops For Permit 06021083
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-03-29 Cont ID  
Sent By lursu Date 2006-03-29 Time 09:21 Rev Time 0.00
Received By lursu Date 2006-03-29 Time 09:20 Sent To  
Notes
2006-03-29 00:00:00NEEDS FOR SUITE.
 USE EXT # 0052 FOR THIS PERMIT BIG APPLE
 PIZZA : 831 VILLAGE BLVD # 803

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-11-05 Cont ID  
Sent By shill Date 2006-11-05 Time 16:09 Rev Time 0.00
Received By shill Date 2006-11-05 Time 16:09 Sent To  
Notes
2006-11-05 16:11:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITON TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILIDNG.ORG
  
 2.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 3.)SUBMIT LEGIBLE PRODUCT APPROVALS.THEY MAY BE
 AVAILABLE AT WWW.MIAMIDADE.GOV (FIND A DEPARTMENT,
 BUILDING CODE COMPLIANCE, PRODUCT CONTROL)

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-18 Cont ID  
Sent By shill Date 2006-10-18 Time 11:48 Rev Time 0.00
Received By shill Date 2006-10-18 Time 11:48 Sent To  
Notes
2006-10-18 11:49:35REVISED A1, A-A1,A3, A3A,FS2.1 DATED 9/15/06

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 11:54 Rev Time 0.00
Received By shill Date 2006-08-11 Time 11:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-22 Cont ID  
Sent By shill Date 2006-06-22 Time 14:23 Rev Time 0.00
Received By shill Date 2006-06-22 Time 14:06 Sent To  
Notes
2006-06-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 8.)PROVIDE FIRE SPRINKLER PLANS,
 FBC*106.3.5.1.1(5).
  
 2ND REVIEW - ARCHITECT'S RESPONSE THAT
 THIS WILL BE DONE LATER IS ACKNOWLEDGED.
 HOWEVER, IF SPRINKLERS ARE REQUIED IN
 THIS BUILDING FOR CODE COMPLIANCE, A
 FIRE SPRINKLER LAYOUT MUST BE PROVIDED
 PRIOR TO PERMIT ISSUANCE.
  
 NEW COMMENT:
  
 PLEASE REMOVE OLD VOIDED SHEETS FROM THE
 COLLATED SET AND SUBMIT SEPARATELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By shill Date 2006-05-08 Time 10:08 Rev Time 0.00
Received By shill Date 2006-05-08 Time 07:53 Sent To  
Notes
2006-05-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)DECLARE OCCUPANCY, FBC CHAPTER 3.
  
 3.)SIGN OWNER/AGENT LINE OF ENERGY
 CALC, FBC13-103.1
  
 4.)THE ENERGY CALC STATES SQUARE FOOT
 AREA AS 1685, PLAN IS 1774.
  
 5.)THE ARCH ALUMINUM PRODUCT APPROVAL
 IS NOT LEGIBLE AND IS EXPIRED, 2001
 CODE.IF A FLORIDA STATE PRODUCT
 APPROVAL IS NOT AVAILABLE, A LOCAL
 PRODUCT APPROVAL IS REQUIRED.A LOCAL
 CAN BE ISSUED FROM THE NOA, BUT A
 LEGIBLE COPY IS REQUIRED.THE
 DOCUMENTATION PROVIDED APPEARS
 INCOMPLETE AS THERE IS SOME INFORMATION
 FROM MIAMI DADE BUT NO NOA NUMBER.
 FAC9B72, WWW.FLORIDABUILDING.ORG
  
 6.)PRODUCT APPROVALS ARE TO BE
 APPROVED BY THE DESIGNER OF RECORD,
 FBC*106.3.3.
  
 7.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
 8.)PROVIDE FIRE SPRINKLER PLANS,
 FBC*106.3.5.1.1(5).

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2006-12-09 Time 14:04 Sent To FIRE
Notes
2006-12-09 14:28:28REV OK, SENT TO FIRE FOR REVIEW OF REMOVAL OF FIRE
 DEVICES.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-10-17 Cont ID  
Sent By dpalmer Date 2006-10-17 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2006-10-17 Time 19:06 Sent To  
Notes
2006-10-17 19:54:01REV'S, GENERAL.
 A/C LOAD ETC.
  
 OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-24 Cont ID  
Sent By dpalmer Date 2006-08-24 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2006-08-24 Time 17:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 11:07 Sent To PC
Notes
2006-08-20 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NOTE #1 FROM
 PREVIOUS REVIEW. PLEASE SEE OVER-RIDES
 REQUIRD AT INGRESS/EGRESS AREAS FOR THE
 OCCUPANT TO VIEW LTS BEING CONTROLLED.
 PLEASE SEE REAR DOOR ALSO.
 PLEASE SEE SEPARATE SPACE (BATH ROOMS).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE BE SURE ALL NEW DEVICES BEING
 SHOWN FOR OVERRIDES, IN ALL LACATIONS
 SHALL BE SPECIFIED WITH TYPE AND TIME
 FOR OVER-RIDE. IF OCC SENSOR TYPE, (MAX
 30 MINS) IF TIMER TYPE (4HRS MAX).
  
 2) NOTE: PLEASE SEE SHEET E-5 IN SET IS
 THE SAME AS THE NEW REVISED SHEET E-3.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS OR
 SHEETS WHICH HAVE BEEN REPLACED WITH NEW
 REVISED SHEETS. PLEASE BE AWARW THAT
 SOME OF THE NUMBERING OF SHEETS HAS
 CHANGED BY THE DEISGNERS.
  
  
 ** CALLED CONTRACTOR.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 14:59 Sent To  
Notes
2006-08-06 00:00:00**** UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE SOME COMMENTS FROM THE TWO
  
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
 NOTES BELOW ARE TAKEN FROM 2ND REVIEW.
  
  
 1) NOTE: NO, PLEASE SEE OVER RIDE
 DEVICES ARE NOT SHOWN AND THE DETAILS OF
 THE TYPE AND HRS OF OVERRIDE IS NOT ON
 PLANS. RESPONSE LTR MENTIONS THIS IS
 DONE, HOWEVER PLEASE SEE THESE
 OVERIRIDES COULD NOT BE LOCATED AT THE
 POINT OF ENTRANCE TO THE SPACE. PLEASE
 SEE FRONT AND REAR INGRESS/EGRESS.
 PLEASE SEE SEPARATE SPACES AS ALSO
 PREVIOUSLY REQUESTED. PLEASE SEE ANY
 AREAS W/ FLR TO CEILING HEIGHT
 PARTITIONS. (BATH RMS ETC)
 CALCS SEEM TO BE OK, AND OTHER ITEMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NOTE #2 FROM
 PREVIOUS REVIEW WHICH WAS TYPED IN
 ERROR. PLEASE SEE A 413 WAS TYPED
 INSTEAD OF 415. IN EITHER CASE THE NOTES
 REFERENCED WAS TO PROVIDE LIGHTING
 CONTROLS , SCHEDULING OVER -RIDES ETC.
 PLEASE SEE THAT RESPONSE WAS FOR VOLTAGE
 DROP WHICH WAS ALSO CORRECT.
 PLEASE SEE ALL OF FBC 2004 CHAPTER 13 AS
 ALKL OF THE ABOVE APPLIES.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3
 PLEASE SEE THAT ENERGY CALCULATIONS MUST
 BE DONE PER EITHER SPACE BY SPACE OR
 ENTIRE AREA.
 PLEASE ALSO SEE FORM WHICH IS TO BE
 USED.
 13-415.1.AB.1, 13-415.1.ABC.1
  
 2) NOTE: NO, PLEASE SEE TWO PREVIOUS
 REVIEW WHICH STATED THE ADDTIONAL
 SERVICE IS NOT AND SHALL NOT BE GRANTED
 UNLESS PROVIDING COMPELETED INFORMATION
 FOR "SPECIAL PERMISSION" WHICH MUST BE
 GRANTED BY THE AHJ. PLEASE SEE 230.2.
 DUE TO INSUFFICIENT INFORMATION AND
 BASED ON WHAT HAS BEEN SUBMITTED THE
 ADDITIONAL SERVICE IS NOT GRANTED.
 PLEASE SEE THIS IS ONE BUILDING AND THIS
 IS A TENANT SPACE IN ONE BUILDING. IN
 ORDER FOR THIS SPACE TO BE CONSIDERED A
 SEPARATE "BUILDING" ON ITS OWN FOR A
 SEPARATE SERVICE, IT MUST CONTAIN "FIRE
 WALLS ON EACH SIDE. PLEASE SEE FBC 2004
 DEFINITIONS OF FIREWALL, WHICH IS 4HRS
 AND IS CONSTRUCTED AS TO ALLOW COLLAPSE
 ON EACH SIDE WITHOUT AFFECTING THE
 STRUCTURAL INTEGRITY OF ADJACENT
 BUILDING. PLEASE KNOW AS THIS LOCATION
 DOES NOT CONTAIN SUCH STRUCTURAL
 ELEMENTS, THEN ONLY THE EXCEPTIONS
 ALLOWED IN THE NEC WILL BE CONSIDERED.
 AT THIS TIME ANDBASED ON PLANS NO
 CONSIDERATION CAN BE MADE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS STILL DO NOT
 INDICATE LOCATION OF THE EXISTING
 SERVICE, LOADS ETC.
 PLEASE SEE A NOTE ON THE RISER DIAGRAM
 MENTIONS SERVICE IS EXISTING, YET
 SERVICE IS ALSO NOTED AS NEW??
 PLEASE PREVIOUS NOTES WITH RESPECT TO
 THE SERVICE AND LOCATIONS.
 THE NEW SERVICE AS SHOWN IS NOT APPROVED
 BY THIS AHJ AT THIS TIME.
 IF THIS IS BEING FED FROM AN EXISTING
 LOCATION OR GUTTER OR OTHER MAIN, PLEASE
 SHOW.
 230.2, 230.72, 230.70, 215.5
  
 3) NOTE:OK,PLEASE BE SURE TO DO THE
 SAME WHEN RESUBMITTING PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PREVIOUS REVIEW
 NOTES WHERE IT WAS REQUESTED THAT ALL
 THE OLD/VOIDED SHEETS BE COMPLETELY
 REMOVED FROM SETS AND ONLY TO INSERT NEW
 REVISED SHEETS INTO SETS FOR REVIEW AND
 STAMPING. PLEASE SEE THIS WAS NOT DONE.
 PLEASE DO SO AND ONLY SUBMIT ONE COPY OF
 THE OLD/VOIDED REMOVED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-20 Cont ID  
Sent By dpalmer Date 2006-06-20 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2006-06-20 Time 12:31 Sent To  
Notes
2006-06-20 00:00:00*********UNSAT *********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW.
  
  
 1) NOTE: PELASE SEE NOTE #2 FROM
 PREVIOUS REVIEW WHICH WAS TYPED IN
 ERROR. PLEASE SEE A 413 WAS TYPED
 INSTEAD OF 415. IN EITHER CASE THE NOTES
 REFERENCED WAS TO PROVIDE LIGHTING
 CONTROLS , SCHEDULING OVER -RIDES ETC.
 PLEASE SEE THAT RESPONSE WAS FOR VOLTAGE
 DROP WHICH WAS ALSO CORRECT.
 PLEASE SEE ALL OF FBC 2004 CHAPTER 13 AS
 ALKL OF THE ABOVE APPLIES.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3
 PLEASE SEE THAT ENERGY CALCULATIONS MUST
 BE DONE PER EITHER SPACE BY SPACE OR
 ENTIRE AREA.
 PLEASE ALSO SEE FORM WHICH IS TO BE
 USED.
 13-415.1.AB.1, 13-415.1.ABC.1
  
 2) NOTE: PLEASE SEE PLANS STILL DO NOT
 INDICATE LOCATION OF THE EXISTING
 SERVICE, LOADS ETC.
 PLEASE SEE A NOTE ON THE RISER DIAGRAM
 MENTIONS SERVICE IS EXISTING, YET
 SERVICE IS ALSO NOTED AS NEW??
 PLEASE PREVIOUS NOTES WITH RESPECT TO
 THE SERVICE AND LOCATIONS.
 THE NEW SERVICE AS SHOWN IS NOT APPROVED
 BY THIS AHJ AT THIS TIME.
 IF THIS IS BEING FED FROM AN EXISTING
 LOCATION OR GUTTER OR OTHER MAIN, PLEASE
 SHOW.
 230.2, 230.72, 230.70, 215.5
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW
 NOTES WHERE IT WAS REQUESTED THAT ALL
 THE OLD/VOIDED SHEETS BE COMPLETELY
 REMOVED FROM SETS AND ONLY TO INSERT NEW
 REVISED SHEETS INTO SETS FOR REVIEW AND
 STAMPING. PLEASE SEE THIS WAS NOT DONE.
 PLEASE DO SO AND ONLY SUBMIT ONE COPY OF
 THE OLD/VOIDED REMOVED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-29 Cont ID  
Sent By dpalmer Date 2006-03-29 Time 07:42 Rev Time 0.00
Received By dpalmer Date 2006-03-28 Time 10:58 Sent To  
Notes
2006-03-29 00:00:00***** UNSAT ********
  
  
 1)NOTE: PLEASE REFERENCE THE FOLLOWING
 CODES. NFPA-70 2002, NFPA-101 2003,
 NFPA-72 2002.
  
 2)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-413.1.ABC.1.1, & .2.
 PLEASE PROVIDE SCHEDULING, CIRCUITING
 AND SPACE CONTROL DEVICES FOR OVERIDES
 AND SPACE CONTROL OVERIDE FOR SPACE.
  
 3)NOTE: PLEASE SEE SERVICE AS SHOWN DOES
 NOT DEPICT EXISTING SERVICE AND
 LOCATION. PLEASE KNOW, AN ADDITTIONAL
 SERVICE MAY NOT BE GRANTED. PLEASE
 PROVIDE COMPLETE LAYOUT AND LOCATIONS OF
 EXISTING SERVICE, SIZE, LOAD
 CALCULATIONS, ETC
 THESE ITEMS WILL BE REVIEWED TO SEE "IF"
 AN ADDITIONAL SERVICE MAY BE GRANTED.
 PLEASE KNOW, SERVICE AS SHOWN IS NOT
 PERMITTED AT THIS TIME.
 230.2,230.70.230.72, 215.5
  
 4)NOTE: PLEASE VERIFY SERVICE AS SHOWN,
 AS THE FPL METERING DEVICE IS SHOWN ON
 THE LOAD SIDE OF THE MAIN DISCONNECT.
 PLEASE SEE FPL MININUM SERVICE
 GUIDELINES.
 THE DISCONNECT IS NOT PERMITTED AS
 SHOWN.
 215.5
  
 5)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR DOES NOT SHOW ANY GROUNDING
 ELECTRODE SYSTEM, ONLY A BOND TO
 EXISTINGMAIN NEUTRAL. THIS IS UNCLEAR
 AT THIS TIME.
 IF MORE THAN ONE SERVICE IS PERMITTED,
 THE TWO OR MORE GROUNDING ELECTRODE
 SYSTEMS SHALL BE BONDED TOGETHER,
 HOWEVER THERE STILL MUST BE A GROUNDING
 ELECTRODE SYSTEM.
 250.50,250.92 ETC
  
 6) NOTE: PLEASE SEE COLOR CODING AS
 SHOWN FOR 277/480V SYSTEMS SHALL BE BE
 BROWN/PURPLE/YELLOW, AS "ORANGE" IS
 STRICLY FOR A DELTA "HIGH-LEG SYSTEM
 WHICH DOES NOT APPEAR TO BE SHOWN.
  
 7) NOTE: PLEASE SUBMIT ALL AIC RATINGS
 FOR ALL NEW MAINS/ SERVICE EQUIPMENT.
 110.9,215.5
  
 8)NOTE: PLEASE KNOW, ANY "LOCK-OUT"
 DEVICS MUST BE APPROVED BY THE AHJ,
 BEFORE INSTALLATION. PLEASE KNOW, THERE
 ARE MANY DEVICES WHICH ARE NOT
 ACCEPTABLE TO THIS AHJ AS THE
 DISCONNECTING LOCK OUT DEVICE.
 THE ONLY LOCK OUT DEVICE ACCEPTABLE,
 MUST BE AN INTEGRAL PART OF THE BREAKER.
 IT SHALL NOT HAVE THE ABILITY TO BE
 REMOVED UNLESS BREAKER IS REMOVED FROM
 PANEL.
 90.4,422.31
  
 9) NOTE: PLEASE SEE THAT PANEL SCHEDULE
 SHALL REFLECT THE EQUIPMENT INSTEAD OF A
 NUMERICAL SCHEDULE TO REFELCT AN
 EQUIPMENT SCHEDULE WHICH MAY/MAY NOT BE
 LOCATED IN PANEL.
 PLEASE ADJUST PANEL SCHEDULE TO
 CORRELATE WITH EQUIPMENT SCHEDULE A THIS
 TIME.408.4, 215.5
  
 10) NOTE: PLEASE CLARIFY CIRCUTING FOR
 RT GFI'S. PLANS INDICATE #24?
 PLEASE CORRELATE WITH CIRCUIT INTENDED
 FOR USE.
 215.5
  
 11)NOTE: PLEASE SEE CODE REFLECTED ON
 PLANS FOR KTICHENGFI/GFI RECEPTS
 PROTECTIONSEEMS TO BE MISPRINTED.
 PLEASE SEE 2002 NEC , WHICH INDICATE
 210.8B3". "B2" IS FOR ROOF TOP RECEPTS.
  
 12) NOTE: PLEASE SEE 220.12A FOR LOAD ON
 "SHOW WINDOWS". PLEASE SPECIFY THE
 LINEAR FT.IT APPEARS THE OPTION SHOWN IN
 220.3(B)(7) IS BEING USED IN LIEU OF
 FT/VA.
 PLEASE ONLY VERIFY.
  
 ** PLEASE BE SURE TO SEE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO COMPLETELT REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE SET OF ANY OLD/VOIDED REMOVED
 SHEETS NEED BE SUBMITTED BACK SEPARTELY
 FOR REFERENCE.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-12-21 Cont ID  
Sent By mawillia Date 2006-12-21 Time 10:35 Rev Time 0.00
Received By mawillia Date 2006-12-21 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-08-11 Cont ID  
Sent By mwennerg Date 2006-08-11 Time 14:46 Rev Time 0.00
Received By mwennerg Date 2006-08-11 Time 14:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-06-23 Cont ID  
Sent By mwennerg Date 2006-06-23 Time 14:17 Rev Time 0.00
Received By mwennerg Date 2006-06-23 Time 14:17 Sent To  
Notes
2006-06-23 00:00:00***DENIED***
  
 PLEASE SEE BUILDING REVIEW COMMENT
 REGARDING SUBMITTAL OF FIRE PROTECTION
 SHEETS FOR REVIEW. PLEASE NOTE THAT THIS
 REQUIREMENT IS IN ADDITION TO SEPARATE
 SHOP DRAWINGS AND PERMIT PRIOR TO SYSTEM
 INSTALLATION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-20 Cont ID  
Sent By mwennerg Date 2006-04-20 Time 13:54 Rev Time 0.00
Received By mwennerg Date 2006-04-20 Time 13:54 Sent To  
Notes
2006-04-20 00:00:00******DENIED******
  
 1) IT WOULD APPEAR THAT THE OCCUPANT
 LOAD BASED ON 15 SQ' PER PERSON IS BASED
 ON ASSEMBLY OCCUPANCY, HOWEVER THE
 OCCUPANT LOAD < 50 DOES NOT MEET THE
 DEFINITION CRITERIA OF NFPA 101, 2003
 EDITION SECTION 3.3.152.2.
  
 2) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3) IN ADDITION TO HOOD/SUPPRESSION
 EQUIPMENT, SEPARATE SHOP DRAWING AND
 PERMITS ARE REQUIRED FOR FIRE SPRINKLER
 AND FIRE ALARM REMODEL.
  
 4) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHER(S)
 ARE REQUIRED AT DISTANCES NOT TO EXCEED
 75' TRAVEL DISTANCE. "K" TYPE FIRE
 EXTINGUISHER REQUIRED IN KITCHEN.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-07-26 Cont ID  
Sent By pschmitz Date 2006-07-26 Time 09:28 Rev Time 0.00
Received By pschmitz Date 2006-07-26 Time 09:28 Sent To  
Notes
2006-07-26 00:00:00PAUL SCHMITZ
 FBC 2004 FUEL GAS CODE, PLAN REVIEW
  
 PROVISS
  
 PREVIOUS NOTE.
  
 10)EMERGENCY HOOD SHUT OFF VALVE
 (E) AUTOMATIC SHUT OFF VALVE.
  
 GAS EMERGENCY SOV TO BEINSTALLED BELOW
 THE CEILIMG. MANUAL SOV AND UNION
 UPSTREAM OF EMERGENCY SHUT OFF VALVE.
  
 PLACED CALL TO ENG. OF RECORD
 MR.GARY STENLUND 813-251-6848
 TO CHANGE TO BELOW CEILING. 7-3-06
  
 END OF COMMENTS QUESTIOINS561-805-6692

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-07-03 Cont ID  
Sent By pschmitz Date 2006-07-03 Time 08:51 Rev Time 0.00
Received By pschmitz Date 2006-07-03 Time 08:51 Sent To  
Notes
2006-07-03 00:00:00PAUL SCHMITZ
 FBC 2004 FUEL GAS CODE, PLAN REVIEW
  
 UNSAT
  
 PREVIOUS NOTE.
  
 10)EMERGENCY HOOD SHUT OFF VALVE
 (E) AUTOMATIC SHUT OFF VALVE.
  
 GAS EMERGENCY SOV TO BEINSTALLED BELOW
 THE CEILIMG. MANUAL SOV AND UNION
 UPSTREAM OF EMERGENCY SHUT OFF VALVE.
  
 PLACED CALL TO ENG. OF RECORD
 MR.GARY STENLUND 813-251-6848
 TO CHANGE TO BELOW CEILING. 7-3-06
  
 END OF COMMENTS QUESTIOINS561-805-6692

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-06 Cont ID  
Sent By pschmitz Date 2006-05-06 Time 10:51 Rev Time 0.00
Received By pschmitz Date 2006-05-06 Time 10:51 Sent To  
Notes
2006-05-06 00:00:00[email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
  
 UNSAT
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10)EMERGENCY HOOD SHUT OFF VALVE
 (E) AUTOMATIC SHUT OFF VALVE.
 NFPA-96 SEC 10.5.1, NFPA-1 SEC 50.4/7.1
 GAS EMERGENCY SOV TO BE 42" TO 48" AFF
  
 QUESTIONS 561-805-6692PAUL SCHMITZ

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 11:21 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 11:21 Sent To E
Notes
2006-12-05 11:21:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-30 Cont ID  
Sent By adarroug Date 2006-10-30 Time 09:11 Rev Time 0.00
Received By adarroug Date 2006-10-30 Time 09:11 Sent To B
Notes
2006-10-30 09:11:36TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 10:43 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 10:43 Sent To  
Notes
2006-10-17 13:40:37TO "COMM" BD#27
2006-10-02 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 16:07 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 16:07 Sent To B
Notes
2006-08-23 00:00:00WAITING FOR "COMM" BD-NEW SHEETS FOR
 PLUMB.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 16:05 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 16:05 Sent To E
Notes
2006-08-17 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 14:38 Sent To  
Notes
2006-08-05 00:00:00TO COMM BOARD #38

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 16:12 Rev Time 0.00
Received By adarroug Date 2006-07-21 Time 16:12 Sent To  
Notes
2006-07-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 15:54 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 15:54 Sent To  
Notes
2006-06-20 00:00:00TO "COMM" BD#30
2006-06-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-08 Cont ID  
Sent By shill Date 2006-05-08 Time 10:09 Rev Time 0.00
Received By shill Date 2006-02-23 Time 16:17 Sent To  
Notes
2006-03-22 00:00:00TO COMM BOARD #3.
2006-02-23 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-11-02 Cont ID  
Sent By rregueir Date 2006-11-02 Time 16:34 Rev Time 0.00
Received By rregueir Date 2006-11-02 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-10-27 Cont ID  
Sent By hmoser Date 2006-10-27 Time 07:50 Rev Time 0.00
Received By hmoser Date 2006-10-27 Time 07:50 Sent To P
Notes
2006-10-27 08:07:07PROVISO
 1) PLEASE REFER TO SECTION 606.2.1 SMOKE DETECTION AND
 606.4.1 SUPERVISON.
 2) PLEASE PROVIDE HANGING DETAIL ON HOOD WHEN HOOD
 PLANS ARE SUBMITED FOR PERMIT.
 3) PLEASE PROVIDE TIE DOWN DETAIL FOR ALL CURBS TO ROOF
 FOR ROUGH INSPECTION .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732.
2006-10-27 07:52:28PROVISO

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-16 Cont ID  
Sent By hmoser Date 2006-08-16 Time 17:06 Rev Time 0.00
Received By hmoser Date 2006-08-16 Time 17:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-14 Cont ID  
Sent By hmoser Date 2006-07-14 Time 14:58 Rev Time 0.00
Received By hmoser Date 2006-07-14 Time 14:58 Sent To  
Notes
2006-07-14 00:00:00PRIVISO
 1) PLEASE PROVIDE HANGING DETAIL FOR
 KITCHEN HOOD.
 2) PLEASE PROVIDE A DETAIL FOR TIEING
 DOWN INTAKE AND EXHAUST FAN ON THE ROOF.
 3) CAN NOT FIND THE CHANGES ON PAGE M-3
 PLEASE MARK THE CHANGES AND RESUBMIT
 PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-10 Cont ID  
Sent By hmoser Date 2006-04-10 Time 10:33 Rev Time 0.00
Received By hmoser Date 2006-04-10 Time 10:33 Sent To  
Notes
2006-04-10 00:00:00PASS PRIVISO
 1) PLEASE REFER TO NFPA 96 SECTION
 7.8.2.1 8B FAN TERMINATION ON ROOF.
 2) ADDITINAL MECHANICAL PERMITS REQUIRED
 FOR WALK IN COOLERS,HOODS AND HOOD
 SUPPRESSION.
 3) PLEASE SUBMIT TWO COPIES OF
 MANUFACTURERS INSTALLATION
 INSTRUCTIONS ON THE WALK IN COOLERS
 WITH THE APPLICATION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-01 Cont ID  
Sent By pschmitz Date 2006-11-01 Time 14:47 Rev Time 0.00
Received By pschmitz Date 2006-11-01 Time 14:47 Sent To  
Notes
2006-11-01 15:02:5811-01-06 REVISION SHT P-2, P-3

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-02 Cont ID  
Sent By pschmitz Date 2006-07-02 Time 14:39 Rev Time 0.00
Received By pschmitz Date 2006-07-02 Time 14:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-06 Cont ID  
Sent By pschmitz Date 2006-05-06 Time 08:39 Rev Time 0.00
Received By pschmitz Date 2006-05-06 Time 08:39 Sent To  
Notes
2006-05-06 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 UNSAT
  
 1) SHT P-2 GRASE TRAP TO BE SIZED BY
 W P BEACHWATERPLANT LAB SUPERVISOR
 INDUSTRIAL COORDINATOR, LYNN MASSON
 OFFICE 561-822-2271
 E-MAIL [email protected]
  
 2) SHT FS-2.1 PROVIDE TWO COPIES OF
 COMMENTS SPECIFICATION SHEETS LOG NUMBER
 P2-06-405, FROM DEPARTMENT OF HOTEL
 BUSINESS REGULATION.
  
 3) SHT A-2 REST ROOMS
 11-4.16.2 CLEAR FLOOR SPACE.
 CLEAR FLOOR SPACE FOR WATER CLOSETS NOT
 IN STALLS SHALL COMPLY WITH FIGURE
 11-28. CLEAR FLOOR SPACE MAY BE ARRANGED
 TO ALLOW EITHER A LEFT-HANDED OR
 RIGHT-HANDED APPROACH.
  
 4)SHT P-3 GAS RISER DIAGRAM
 SEE GAS PLAN REVIEW OMMENTS
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  