Plan Review Details - Permit 06021054
Plan Review Stops For Permit 06021054
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-16 Cont ID  
Sent By alange Date 2006-06-16 Time 09:15 Rev Time 1.00
Received By alange Date 2006-06-16 Time 09:15 Sent To  
Notes
2006-06-16 00:00:00DENIED
 SECOND REVIEW:
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $80,324.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 3.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 LINTELS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
 SUBMIT PRODUCT APPROVAL WITH STATE
 APPROVAL.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 8.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9.ROOF SHEATHING NAILING SCHEDULE
 SHOULD COMPLY WITH FBC 2304.9.1
  
 10.SURVEYS SUBMITTED SHALL BE AN
 ORIGONAL SIGNED AND SEALED COPY.FS
 472.025
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-30 Cont ID  
Sent By alange Date 2006-03-30 Time 08:59 Rev Time 2.00
Received By alange Date 2006-03-30 Time 08:52 Sent To  
Notes
2006-03-30 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $80,324.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 3.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 LINTELS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 8.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9.ROOF SHEATHING NAILING SCHEDULE
 SHOULD COMPLY WITH FBC 2304.9.1
  
 10.SURVEYS SUBMITTED SHALL BE AN
 ORIGONAL SIGNED AND SEALED COPY.FS
 472.025
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-13 Cont ID  
Sent By btrobaug Date 2006-06-13 Time 10:40 Rev Time 1.00
Received By btrobaug Date 2006-06-13 Time 10:12 Sent To M
Notes
2006-06-13 00:00:00 
 PROVISO
  
 PLEASE SUBMIT THE FOLLOWING INFORMATION
 PRIOR TO THE ROUGH ELECTRICAL
 INSPECTION. ALLOW A WEEK FOR REVIEW.
  
 1} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND
 OVER CURRENT PROTECTION COMPLIANCE MAY
 BE REVIEWED PER 106.3.5.4 FBC AS
 AMENDED.
  
 2} PROVIDE A LOAD CALCULATION FORM THE
 ENTIRE SERVICE, INCLUDING THE ADDITION.
 SUBMIT WITH THE EXISTING SERVICE RATING.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-10 Cont ID  
Sent By btrobaug Date 2006-03-10 Time 14:47 Rev Time 0.50
Received By btrobaug Date 2006-03-10 Time 12:08 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 10:23 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 10:23 Sent To E
Notes
2006-06-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 14:49 Sent To Z
Notes
2006-05-30 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 08:59 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 08:59 Sent To E
Notes
2006-03-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-30 Cont ID  
Sent By alange Date 2006-03-30 Time 08:52 Rev Time 0.00
Received By alange Date 2006-02-27 Time 09:31 Sent To  
Notes
2006-02-27 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-14 Cont ID  
Sent By tgordon Date 2006-06-14 Time 11:44 Rev Time 0.30
Received By tgordon Date 2006-06-14 Time 12:16 Sent To B
Notes
2006-06-14 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) ENERGY CAL'S. NEED TO BE SIGNED BY
 OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2
  
 3) PLEASE SEE MANUAL J CAL'S. LAST PAGE
 TOTAL SENSIBLE GAIN 14847, THE EQUIPMENT
 BEING INSTALLED SENSIBLE BTU'S. CAN NOT
 BE MORE THAN 20% OVER THE MANUAL J
 CAL'S. PER 2004 FBC 13-607.1.ABC.1.1,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By tgordon Date 2006-03-13 Time 14:37 Rev Time 0.30
Received By tgordon Date 2006-03-13 Time 14:37 Sent To B
Notes
2006-03-13 00:00:00*** DENIED ***
 1) PLEASE PROVIDE ENERGY CALCULATIONS
 AND A MANUAL J (SHOWING CFM'S TO EACH
 ROOM) PER 2004 FBC 13-600.ABC .
  
 2) PLEASE SHOW ON MECHANICAL PLAN GRILL
 SIZES, COPPER LINE SIZES.
  
 3) PLEASE SHOW RETURN AIR DUCTS ON MECH.
 PLAN.
  
 4) PLEASE PROVIDE RETURN AIR TO ALL
 BEDROOMS, SEE NOTE #5.
  
 5)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-03-13 Cont ID  
Sent By tgordon Date 2006-06-14 Time 12:16 Rev Time 0.00
Received By jleech Date 2006-03-13 Time 14:17 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-10 Cont ID  
Sent By mmclean Date 2006-06-10 Time 10:42 Rev Time 0.00
Received By mmclean Date 2006-06-10 Time 10:42 Sent To I
Notes
2006-06-10 00:00:00NOTE: ONLY ONE COOKING FACILITY ALLOWED.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By mmclean Date 2006-03-06 Time 17:18 Rev Time 0.00
Received By mmclean Date 2006-03-06 Time 17:17 Sent To I
Notes
2006-03-06 00:00:00DENIED,
 1. THE SITEPLAN & SURVEY DOES NOT MATCH
 WITH SETBACKS.
 2. MUST PROVIDE TWO COPY OF FLOOR PLAN
 SHOWING THE EXISTING STRUCTURE WITH
 INTERIOR ACCESS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720