Plan Review Details - Permit 06021049
Plan Review Stops For Permit 06021049
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2006-12-27 Cont ID  
Sent By lursu Date 2006-12-27 Time 09:25 Rev Time 0.00
Received By lursu Date 2006-12-27 Time 09:25 Sent To  
Notes
2006-12-27 09:32:49BASED ON THE E-MAIL SENT BY THE CONTRACTOR
 [email protected], THE PROPERTY OWNER IS
 WEST PALM BEACH CONCOURSE PLAZA AND THE TENANT IS
 DYNAMIC GROWTH PARTNERS,INC.THE PROOF OF OWNERSHIP IS
 NOT REQUIRED ANYMORE SINCE IS THE PERMIT APPLICATION
 AND PROPERTY APPRAISER HAVE THE SAME OWNERSHIP
 INFORMATION .PERMIT WAS ATTACHED TO THE CORRECT
 RECORD.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 OFFICE:822-1239
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-12-20 Cont ID  
Sent By lursu Date 2006-12-20 Time 11:42 Rev Time 0.00
Received By lursu Date 2006-12-20 Time 11:42 Sent To  
Notes
2006-12-20 11:44:08ON THE ORIGINAL PERMIT APPLICATION THE OWNER OF RECORD
 IS LISTED AS DYNAMIC GROWTH PARTNERS INC.
 HOWEVER IN THE PROPERTY APPRASIER'S DATA UNDER THE
 ABOVE PARCEL CONTROL NUMBER THE OWNER OF RECORD IS
 LISTED AS WEST PALM BCH CONCOURSE PLAZA.
 IF THE OWNER ON THE APPLICATION IS CORRECT THEN THE
 PROOF OF OWNERSHIP IS NEEDED BEFORE ISSUING THE
 PERMIT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-12-15 Cont ID  
Sent By lursu Date 2006-12-15 Time 08:43 Rev Time 0.00
Received By lursu Date 2006-12-15 Time 08:43 Sent To  
Notes
2006-12-15 08:44:07PERMIT ATTACHED TO THE CORRECT ADDRESS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]
2006-02-23 00:00:00TOLD MARC GEFTMAN WE WILL NEED LEGAL
 DOCUMENT TO CHANGE OWNER INFO BEFORE WE
 CAN ISSUE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-01-11 Cont ID  
Sent By shill Date 2007-01-11 Time 16:16 Rev Time 0.00
Received By shill Date 2007-01-11 Time 16:16 Sent To  
Notes
2007-01-11 16:17:15CONTRACTOR APPLIED FOR PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-01-02 Cont ID  
Sent By shill Date 2007-01-02 Time 11:20 Rev Time 0.00
Received By shill Date 2007-01-02 Time 11:00 Sent To  
Notes
2007-01-02 11:21:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)THIS HAS BEEN SUBMITTED FOR PLAN CHECK ONLY.
 PLEASE APPLY FOR PERMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-05 Cont ID  
Sent By shill Date 2006-10-05 Time 16:48 Rev Time 0.00
Received By shill Date 2006-10-05 Time 15:27 Sent To  
Notes
2006-10-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LISTS:
  
 1.)A NOTICE OF COMMENCEMENT REQUIRED,
 FS713.13.
  
 2.)DECLARE OCCUPANCY, FBC 3.
  
 6.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ARCHITECT FIRM IS TO BE
 ON EACH SHEET, FAC61G1-16.003, 004.SEE
 ALSO ELECTRIC REVIEWER?S COMMENTS
 REGARDING TURNKEY CONCEPTS, INC.
  
 11.)PLANS STATE THAT THIS IS TYPE IV
 UPROTECTED.THIS IS HEAVY TIMBER.TO
 MY KNOWLEDGE, THERE IS ONLY ONE HEAVY
 TIMBER BUILDING IN THE CITY OF WEST PALM
 BEACH AND IT IS NOT THIS BUILDING.
 PLEASE CONFIRM THAT THIS IS A HEAVY
 TIMBER BUILDING.
  
 PLANS STATE THAT THIS BUILDING IS NOT
 REQUIRED TO BE SPRINKLED.YOU HAVE ALSO
 STATED THAT THE BUILDING IS 21450 SF.
 IT APPEARS THAT DUE TO THE SIZE OF THE
 BUILDING, IT IS LIKELY THAT IT IS
 REQUIRED BY CODE TO BE FULLY SPRINKLED.
 OUR RECORDS SHOW A FIRE ALARM/FIRE
 SPRINKLER PERMIT ISSUED IN THE PAST.
 ADDRESS.
  
 IF THE BUILDING IS REQUIRED TO BE
 SPRINKLED, FIRE SPRINKLER PLANS
 REQUIRED.
  
 13.)SHOW ACCESS AISLES, FBC11-5.3.
  
 15.)SHOW MANEUVERING CLEARANCE, DOOR
 5, FBC 11 FIGURE 25, FBC11-4.13.6.THE
 DIMENSIONS SHOWN ARE FOR THE PUSH SIDE,
 THIS IS THE PULL SIDE OF THE DOOR.
  
 16.)DOORS 5 AND 6, SHOW COMPLIANCE
 WITH FBC1008.1.8.8, LEAVE UNOBSTRUCTED
 HALF THE REQUIRED WIDTH.ALSO DOOR 4.
 THE RESPONSE LETTER STATES THAT THE REAR
 DOOR IS NOT AN EXIT.SEE ITEM 19.
 ALSO, EVEN IF ONE EXIT REQUIRED, SOMEONE
 WHO IS IN THE RESTROOM WILL EXIT THROUGH
 THE HALLWAY, WITH DOORS 4 AND 6 BLOCKING
 THE REQUIRED WIDTH.SOMEONE IN THE
 COOLER AREA ATTEMPTING TO EXIT THE
 KITCHEN AREA THROUGH DOOR 6 WOULD PASS
 DOOR 5, WHICH BLOCKS OVER HALF THE
 REQUIRED WIDTH.
  
 19.)PLANS STATE THAT ONE EXIT IS
 REQUIRED.OCCUPANT LOAD DOES NOT MEET
 THE EXCEPTION FOR ONE EXIT FBC TABLE
 1018.2.BASED ON INFORMATION PROVIDED,
 TWO EXITS ARE REQUIRED.
  
 NEW COMMENT:
  
 20.)ENERGY CALCS STATE 1800 SF, PLANS
 STATE 1747.REVISE.
  
 21.)WHAT IS THE CURRENT OCCUPANCY
 CLASSIFICATION OF THIS SPACE?I WAS
 UNABLE TO LOCATE AN OCCUPATIONAL LICENSE
 FOR THIS ADDRESS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By shill Date 2006-07-18 Time 10:44 Rev Time 0.00
Received By shill Date 2006-07-18 Time 10:44 Sent To  
Notes
2006-07-18 00:00:00****CORRECTIONS****
 ****MAJOR WORKING DRAWING REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)DECLARE OCCUPANCY, FBC CHAPTER 3.
  
 3.)SIGN OWNER/AGENT LINE OF ENERGY
 CALC, FBC13-103.1.
  
 4.)THE SEAL FOR THE ARCHITECT IS TO BE
 DATED, FAC61G1-16.
  
 5.)THE SEAL FOR THE ENGINEER IS
 EXPIRED, FAC61G15-23. (ENERGY CALCS)
  
 6.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ARCHITECT FIRM IS TO BE
 ON EACH SHEET, FAC61G1-16.003, 004.
  
 7.)THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS TO BE ON EACH
 SHEET, FAC61G1-16.003, 004.
  
 8.)GOVERNING CODES ARE FBC2004,
 FBC2004 EXISTING BUILDING CODE.
  
 9.)THE PLAN STATES THAT THE BUILDING
 DEPARTMENT IS PALM BEACH COUNTY, SHOULD
 STATE CITY OF WEST PALM BEACH.
  
 10.)ADDRESSED.
  
 11.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; HEIGHT, AREA,
 MINIMUM BUILDING TYPE FBC6, SPRINKLED OR
 UNSPRINKLED.IF THE BUILDING IS
 REQUIRED TO BE SPRINKLED, FIRE SPRINKLER
 PLANS REQUIRED.
  
 12.)SHOW THE REQUIRED CLEAR FLOOR
 SPACE AT THE SINKS, MEN?S TOILET AND
 WOMEN?S TOILET, FBC11-4.24.5.
  
 13.)SHOW ACCESS AISLES, FBC11-5.3.
  
 14.)PROVIDE THE HEIGHT OF THE POS
 AREA, A1.2, FBC11-7.2.
  
 15.)SHOW MANEUVERING CLEARANCE, DOOR
 5, FBC11 FIGURE 25, FBC11-4.13.6.
  
 16.)DOORS 5 AND 6, SHOW COMPLIANCE
 WITH FBC1008.1.8.8, LEAVE UNOBSTRUCTED
 HALF THE REQUIRED WIDTH.
  
 NEW COMMENTS:
  
 17.)ENERGY CALCS ARE TO BE FBC2004.
  
 18.)DECLARE OCCUPANT LOAD.COVER
 SHEET SHOWS SEATING OF 44, WHAT ABOUT
 EMPLOYEES?
  
 19.)SHOW TRAVEL DISTANCE.PLANS STATE
 THAT ONE EXIT IS REQUIRED.TWO ARE
 SHOWN, BUT PLANS HAVE NOW BEEN REVISED
 SO THAT DOORS 3 AND 4 DO NOT COMPLY WITH
 FBC1008.1.1.8.ADDRESS.
  
 20.)DECLARE LEVEL OF ALTERATION, FBC
 EB CHAPTER 3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By shill Date 2006-05-08 Time 16:25 Rev Time 0.00
Received By shill Date 2006-05-08 Time 16:25 Sent To  
Notes
2006-05-08 00:00:00****CORRECTIONS****
 ****MAJOR WORKING DRAWING REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)DECLARE OCCUPANCY, FBC CHAPTER 3.
  
 3.)SIGN OWNER/AGENT LINE OF ENERGY
 CALC, FBC13-103.1
  
 4.)THE SEAL FOR THE ARCHITECT IS TO BE
 DATED, FAC61G1-16.
  
 5.)THE SEAL FOR THE ENGINEER IS
 EXPIRED, FAC61G15-23.
  
 6.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ARCHITECT FIRM IS TO BE
 ON EACH SHEET, FAC61G1-16.003, 004.
  
 7.)THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS TO BE ON EACH
 SHEET, FAC61G1-16.003, 004.
  
 8.)GOVERNING CODES ARE FBC2004,
 FBC2004 EXISTING BUILDING CODE.
  
 9.)THE PLAN STATES THAT THE BUILDING
 DEPARTMENT IS PALM BEACH COUNTY, SHOULD
 STATE CITY OF WEST PALM BEACH.
  
 10.)HANDICAP CODE REFERS TO DADE
 COUNTY, GOVERNING ACCESSIBILITY CODE IS
 FBC2004 CHAPTER 11.
  
 11.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; HEIGHT, AREA,
 MINIMUM BUILDING TYPE FBC6, SPRINKLED OR
 UNSPRINKLED.IF THE BUILDING IS
 REQUIRED TO BE SPRINKLED, FIRE SPRINKLER
 PLANS REQUIRED.
  
 12.)SHOW THE REQUIRED CLEAR FLOOR
 SPACE AT THE SINKS, MEN?S TOILET AND
 WOMEN?S TOILET, FBC11-4.24.5.
  
 13.)SHOW ACCESS AISLES, FBC11-5.3.
  
 14.)PROVIDE THE HEIGHT OF THE POS
 AREA, A1.2, FBC11-7.2.
  
 15.)SHOW MANEUVERING CLEARANCE, DOOR
 5, FBC11 FIGURE 25, FBC11-4.13.6.
  
 16.)DOORS 5 AND 6, SHOW COMPLIANCE
 WITH FBC1008.1.8.8, LEAVE UNOBSTRUCTED
 HALF THE REQUIRED WIDTH.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-01-14 Cont ID  
Sent By dpalmer Date 2007-01-14 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2007-01-14 Time 10:58 Sent To PC
Notes
2007-01-14 11:37:46*** THIS IS UNDER THE 2006 REVSIONS TO THE 2004 FBC AND
 THE 2005 NEC.
 DID NOT APPLY FOR PERMIT UNTIL JAN 8TH, 2007

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-11-28 Cont ID  
Sent By dpalmer Date 2006-11-28 Time 20:19 Rev Time 0.00
Received By dpalmer Date 2006-11-28 Time 20:06 Sent To  
Notes
2006-11-28 20:20:46**** UNSAT ***
  
 1) NOTE: PLEASE KNOW AS THE PLANS HAVE STILL ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW", STAMPING AND PASSING OF
 ELECTRICAL PLANS ARE NOT POSSIBLE AT THIS TIME. PLEASE
 KNOW AS THIS PROJECT HAS NOT APPLIED FOR PERMIT, PLEASE
 KNOW AS OF DEC 8TH, 2006 THE STATE OF FLORIDA WILL
 ADOPT THE 2005 NEC (NATIONAL ELECTRICAL CODE) AND ANY
 PERMIT APPLICATIONS MAY AFTER THAT DATE WILL HAVE TO
 COMPLY WITH NEW CODE. AS THIS PROJECT HAS NOT BEEN
 SUBMITTED FOR PERMIT, THIS WILL NOT FALL UNDER THE
 PRESENT 2002 NEC. CHANGES IN DESIGN AND CODES WILL BE
 REQUIRED.
 PLANS CAN NOT BE STAMPED AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, COMMENTS OR IF ANY PART OF
 NOTES ABOVE ARE NOT UNDERSTOOD OR TYPED IN A MANNER
 WHICH IS NOT CLEAR, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE OR REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 16:29 Sent To  
Notes
2006-10-01 00:00:00*** UNSAT 3RD REVIEW ***
  
 ** PLEASE KNOW, PLANS ARE STILL ONLY
 BEING SUBMITTED FOR "'PLAN REVIEW** AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT TO
 DATE.
  
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL APPLY. MOST WERE
 ADDRESSED.
 PLEASE KNOW, FS 553.80(2)(B) DOES NOT
 APPLY AS PLANS HAVE NOT BEEN SUBMITTED
 FOR PERMIT.
  
  
 *** NOTES FOR ELECTRICAL ENGINEERING
 FIRM WERE ADDRESSED AND ARE OK.
  
 1) PLEASE SEE NEW NOTE #12 BELOW FROM
 PREVIOUS REVIEW AS THE TITLE BLOCKS DO
 NOT CONTAIN THE LICENSING INFORMATION
 FOR THE ARCHITECT/ DESIGNER "TURNKEY
 CONCEPTS"
 PLEASE SEE FS 481.203, 481.223(1)(A),
 AND 481.229 (1)(C).
 PLEASE IF THIS IS INDEED A "DESIGN"
 FIRM/OR "DRAFTING" FIRM, PLEASE KNOW IT
 HAS BEEN CONFIRMED WITH THE STATE'S
 LEGAL COUNSEL TO THE BOARD THAT THIS IS
 PROHIBITED.
 PLEASE KNOW, IF "TURNKEY" IS A LICENSED
 ARCHITECTURAL FIRM OFFERING
 ARCHITECTURAL SERVICES PLEASE INCLUDE
 ALL INFORMATION ON TITLE BLOCKS AS
 PREVIOUSLY REQUESTED. PLEASE KNOW A
 SERCH ON THE STATE'S WEBSITE HAS NOT
 COME UP WITH ANY INFORMATION ON SUCH
 COMPANY FROM THE DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGUALTION.
 ONE COPY OF ALL SAID PLANS WILL BE
 RETAINED AT THE REQUEST OF STATE'S
 PROSECUTING ATTORNEY.
  
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW **
 ************* NEW NOTE ************
  
  
 12) NOTE: PLEASE SEE MISSING REQUIRED ON
 TITLE BLOCKS FOR ARCHITECT AND FIRM AS
 SHOWN.
 PLEASE SEE FAC 61G1-16.004, AND FS
 481.219.
 MISSING PRINTED NAME AND LICENSE #.
 MISSING THE FIRM LICENSE #, ALSO KNOWN
 AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN THIS TITLE BLOCK
 AND WHICH ARE SIGNED, DATED AND SEALED
 BY THE ARCHITECT.
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
 ** PLEASE SEE ARCHITECT HAS NOT DATED
 PLANS AS REQUIRED PER FS 481.221
  
 ** PLEASE BE AWARE OF ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE SET OF ANY OLD/VOIDED REMOVED
 SHEETS NEED BE SUBMITTED BACK SEPARTELY
 FOR REFERENCE.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-30 Cont ID  
Sent By dpalmer Date 2006-06-30 Time 21:57 Rev Time 0.00
Received By dpalmer Date 2006-06-30 Time 21:24 Sent To  
Notes
2006-06-30 00:00:00*** UNSAT ***
  
 ** PLEASE KNOW, PLANS ARE STILL ONLY
 BEING SUBMITTED FOR "'PLAN REVIEW** AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT TO
 DATE.
  
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL APPLY. MOST WERE
 ADDRESSED.
 PLEASE KNOW, FS 553.80(2)(B) DOES NOT
 APPLY AS PLANS HAVE NOT BEEN SUBMITTED
 FOR PERMIT.
  
  
  
 1)NOTE:NO, PLEASE SEE PLANS/COVER
 SHEETS REFLECTS THE 2004 FBC FOR THE
 ELECTRICAL CODE. PLEASE REFERENCE THE
 2002 NFPA-70.
 PLEASE ALSO SEE ENERGY CALCULATIONS ARE
 STILL DESIGNED AND STATED PER 2001 FBC.
  
 ** PREVIOUS NOTE **
 PLEASE SEE PLANS REFERENCE THE
 2001 FBC AND OTHER CODES NO LONGER IN
 AFFECT. PLEASE KNOW, THE NEW 2004 FBC
 WAS ADOPTED ON OCT, 1ST, 2005.
 PLEASE ALSO SEE OTHER CODES NOTES WHICH
 ARE NO LONGER IN AFFECT. PLEASE
 REFERENCE THE FOLLOWING
 CODES. NFPA-70 2002, NFPA-101 2003,
 NFPA-72 2002.
  
  
 2)NOTE:NO, PLEASE SEE THIS NOTE WAS
 TYPED WITH THE "413" INSTEAD OF THE
 "415". THIS WAS IN ERROROF THIS
 OFFICE. THE NOTE WAS SHOWN ON PLANS FOR
 THE RESPONSE FROM THE DESIGNER INSTEAD
 OF OF PLACING ANY COMMENTS OR QUESTIONS
 IN A RESPONSE LETTER?
 PLEASE SEE THIS REQUIREMENT OF HAVING
 THE LIGHTING CONTROLS DOES APPLY AS
 STATED, IT IS IN A BUILDING LARGER THAN
 5K SQ FT. PLEASE SEE THAT THIS SPACE IS
 A SEPARATELY METERED SPACE ON THIS SAME
 ELECTRICAL SERVICE.
 PLEASE SEE THAT THE TC PROVIDED IS OK,
 HOWEVER AN OVER RIDE DEVICE IS REQUIRED
 AT THE ENTRANCE(S) TO SPACE WHERE THE
 OCCUPANT CAN READLITY SEE THE LIGHTING
 BEING CONTROLLED. THIS OVERRIDE(S)
 DEVICE IF TIMER CANE ONLY HAVE A SETTING
 OF 4HRS. PLEASE SEE ANY SEPARATE SPACES
 WITH FLR TO CEILING HEIGHT PARTITIONS
 SHALL ALSO CONTAIN AN DEVICE OF SOME
 SORT EITHER MOTION SENSOR, INFARED,
 OCCUPANCY SENSOR ETC
 PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1
 WHICH REQUIRES THESE EVEN WHEN A
 SEPARATELY METERED TENANT.
 ** PLEASE KNOW, IF THIS TENANTS SPACE IS
 LESS THAN 5% OF THE TOTAL "BUILDING" SQ
 FOOTAGE THEN IT IS POSSIBLE THAT THIS
 SPACE MAY MEET AN EXCEPTION.
 ** PLEASE KNOW, THIS DOES NOT INCLUDE
 ANY LIGHTING FOR EM/NIGHT LTS WHICH ARE
 REQUIRED OR ON FOR "SAFETY".
  
 ** PREVIOUS NOTE **
 PLEASE SEE FBC CHAPTER 13,
 13-413.1.ABC.1.1, & .2.
 PLEASE PROVIDE SCHEDULING, CIRCUITING
 AND SPACE CONTROL DEVICES FOR OVERIDES
 AND SPACE CONTROL OVERIDE FOR SPACE.
  
 3)NOTE: PLEASE SEE SEE ADDRESSING NEEDS
 TO BE CORRECTED. PLEASE SEE PERMIT
 APPLICATION MENTIONS 2060 ALONG WITH
 PLANS, HOWEVER THE PCN USED FOR
 APPLICATION CORRELATES TO OUR SYSTEM AND
 PAPA AS 2000 PALM BEACH LAKES. PLEASE
 SEE COMMENTS FROM ADDRESSING STOP AND
 ADJUST PLANS WHEN NEEDED OR APPLICATION.
 FAC 61G1-16.004
  
 4)NOTE:NO, PLEASE SEE ENERGY
 CALCULATIONS STILL ARE SEALED WITH
 "CERTIFICATE"?? PLEASE KNOW, THIS
 PROJECT HAS NOT BEEN SUBMITTED FOR
 PERMIT AND WAS NOT SUBMITTED FOR PERMIT
 BEFORE THE DEC 31ST, 2005 DATE.
 THEREFORE ALL SEALS MUST MEET THE
 REQUIREMENTS AS STATED IN THE FAC AND FS
 BELOW.
  
 ** PREVIOUS NOTE **
 PLEASE SEE ENERGY CALCUALTIONS
 CONTAINS THE SEAL WHICH INDICATES
 "CERTIFICATE" IN THE SAID SEAL OF THE
 ENGINEER OF RECORD. PLEASE SEE FAC
 61G15-23.001 WHICH REQUIRED THE SEAL TO
 CHANGE FROM "CERTIFICATE" TO "LICENSE"
 AS OF FEB 5, 2004. PLEASE KNOW AND
 EXTENSION WAS GRANTED TO THE FINAL DATE
 OF 12/31/05. PLEASE KNOW, THE NEW SEAL
 MUST BE USED.
 ** PLANS ARE USING CORRECT SEAL.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE:OK.
  
 ************* NEW NOTE ************
  
  
 12) NOTE: PLEASE SEE MISSING REQUIRED ON
 TITLE BLOCKS FOR ARCHITECT AND FIRM AS
 SHOWN.
 PLEASE SEE FAC 61G1-16.004, AND FS
 481.219.
 MISSING PRINTED NAME AND LICENSE #.
 MISSING THE FIRM LICENSE #, ALSO KNOWN
 AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN THIS TITLE BLOCK
 AND WHICH ARE SIGNED, DATED AND SEALED
 BY THE ARCHITECT.
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
 ** PLEASE SEE ARCHITECT HAS NOT DATED
 PLANS AS REQUIRED PER FS 481.221
  
 ** PLEASE BE AWARE OF ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE SET OF ANY OLD/VOIDED REMOVED
 SHEETS NEED BE SUBMITTED BACK SEPARTELY
 FOR REFERENCE.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-29 Cont ID  
Sent By dpalmer Date 2006-03-29 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2006-03-29 Time 07:55 Sent To  
Notes
2006-03-29 00:00:00***** UNSAT ********
  
 ** PLEASE KNOW, PLANS WERE SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE SEE PLANS REFERENCE THE
 2001 FBC AND OTHER CODES NO LONGER IN
 AFFECT. PLEASE KNOW, THE NEW 2004 FBC
 WAS ADOPTED ON OCT, 1ST, 2005.
 PLEASE ALSO SEE OTHER CODES NOTES WHICH
 ARE NO LONGER IN AFFECT. PLEASE
 REFERENCE THE FOLLOWING
 CODES. NFPA-70 2002, NFPA-101 2003,
 NFPA-72 2002.
  
  
 2)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-413.1.ABC.1.1, & .2.
 PLEASE PROVIDE SCHEDULING, CIRCUITING
 AND SPACE CONTROL DEVICES FOR OVERIDES
 AND SPACE CONTROL OVERIDE FOR SPACE.
  
 3)NOTE: PLEASE SEE SEE ADDRESSING NEEDS
 TO BE CORRECTED. PLEASE SEE PERMIT
 APPLICATION MENTIONS 2060 ALONG WITH
 PLANS, HOWEVER THE PCN USED FOR
 APPLICATION CORRELATES TO OUR SYSTEM AND
 PAPA AS 2000 PALM BEACH LAKES. PLEASE
 SEE COMMENTS FROM ADDRESSING STOP AND
 ADJUST PLANS WHEN NEEDED OR APPLICATION.
 FAC 61G1-16.004
  
 4)NOTE:PLEASE SEE ENERGY CALCUALTIONS
 CONTAINS THE SEAL WHICH INDICATES
 "CERTIFICATE" IN THE SAID SEAL OF THE
 ENGINEER OF RECORD. PLEASE SEE FAC
 61G15-23.001 WHICH REQUIRED THE SEAL TO
 CHANGE FROM "CERTIFICATE" TO "LICENSE"
 AS OF FEB 5, 2004. PLEASE KNOW AND
 EXTENSION WAS GRANTED TO THE FINAL DATE
 OF 12/31/05. PLEASE KNOW, THE NEW SEAL
 MUST BE USED.
 ** PLANS ARE USING CORRECT SEAL.
  
 5)NOTE: PLEASE LOAD CALCUALTIONS FOR
 EXISTING SERVICE AND NEW LOADS ADDED TO
 EXISTING.
 215.5, 220,
  
 6) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%.
 215.3,230.42
  
 7) NOTE: PLEASE PROVIDE GFI PROTECTION
 PER 2002 NEC, 210.8B3
  
 8) NOTE: PLEASE SUBMIT ALL AIC RATINGS
 FOR ALL NEW MAINS/ SERVICE EQUIPMENT.
 110.9,215.5
  
 8)NOTE: PLEASE PROVIDE
 NOTE/IDENTIFICATION OF "FEED-THRU" LUGS
 IF INDEED THIS IS THE METHOD OF FEDDING
 PANEL "B".
 215.5
  
 9) NOTE: PLEASE INDICATE THE
 "FLOATING/ISOLATED" NEUTRAL IN METER AS
 THIS LOCAITON IS NOT THE FIRST MEANS OF
 DISCONNECT FOR SERVICE.
 250.6,250.24B
  
 10) NOTE: PLEASE CLARIFY CIRCUTING,
 PLEASE SEE SOME CIRCUITS DO NOT SEEM TO
 CORRELATE WITH PLANS?
 "SHOW WINDOWS?"
 215.5
  
 11) NOTE: PLEASE SEE 210.62, 220.12A FOR
 MIN RECEPTS REQUIRED FOR WINDOW SPACING.
 PLEASE SEE PLANS INDICATE A "SIGN"
 ALREADY FOR THE WINDOW RECEPT AS
 DEDICATED. ADDITIONAL RECEPTS WOULD BE
 REQUIRED ALONG WITH ADDITIONAL RECEPTS
 FOR THE LINEAR FT SHOWN MORE THAN 12'.
  
 ** PLEASE BE AWARE OF ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE SET OF ANY OLD/VOIDED REMOVED
 SHEETS NEED BE SUBMITTED BACK SEPARTELY
 FOR REFERENCE.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-01-03 Cont ID  
Sent By mawillia Date 2007-01-03 Time 10:38 Rev Time 0.00
Received By mawillia Date 2007-01-03 Time 10:38 Sent To  
Notes
2007-01-03 10:42:52*****PROVISO*****
  
  
  
 PLEASE REFER TO BUILDING AND ELECTRICAL COMMENTS IN
 REFERENCE TO THIS BEING A REVIEW FOR "PLAN CHECK" ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-10-24 Cont ID  
Sent By mawillia Date 2006-10-24 Time 14:00 Rev Time 0.00
Received By mawillia Date 2006-10-24 Time 14:00 Sent To  
Notes
2006-10-24 14:04:55*****DENIED****
  
 RESPONSES TO THE FIRE PLAN REVIEW COMMENTS OF 07/10/06
 RECEIVIED AS FOLLOWS:
  
  
 1.)OK
  
 2.) OK
  
 3.)PLEASE SHOW WHERE THIS COMMENT HAS BEEN
 ACKNOWLEDGED.
  
 4.)REVISE SO THAT DOORS DO NOT OPEN INTO THE EXIT
 CORRIDOR.ALTHOUGH THE REAR DOOR IS READILY ACCESSABLE
 TO EMPLOYEES, IT SHALL BE REQUIRED EXIT.
  
 5.)PLEASE SHOW WHERE THIS COMMENT HAS BEEN
 ACKNOWLEDGED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 13:12 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 13:01 Sent To  
Notes
2006-07-10 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. EXITS SHALL REMAIN CLEAR AND
 ACCESSIBLE.
  
 4. ONLY 14" REMAIN FOR EXIT ACCESS IN
 THE REAR HALLWAY WHEN THE RESTROOM DOORS
 ARE IN THE OPEN POSITION. THE RESTROOM
 DOORS ARE 36" WIDE THAT OPEN ONTO A
 CORRIDOR THAT IS 50" WIDE. PLEASE
 REVISE.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY REQUIRED HOOD, DUCT, AND
 SUPPRESSION SYSTEMS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-20 Cont ID  
Sent By mwennerg Date 2006-04-20 Time 14:58 Rev Time 0.00
Received By mwennerg Date 2006-04-20 Time 14:58 Sent To  
Notes
2006-04-20 00:00:00******DENIED******
 PLAN REVIEW ONLY
  
 1) BUILDING DATA INDICATES THAT BUILDING
 IS NOT SPRINKLERED, BUT RESPONSIBILITY
 SCHEDULE INDICATES SPRINKLER SYSTEM.
 PLEASE CLARIFY.
  
 2) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING IN TERMS OF CLASS A,B ORC.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHER(S)
 REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' TRAVEL
 DISTANCE REQUIREMENT. "K" TYPE
 EXTINGUISHER REQUIRED IN KITCHEN.
  
 4) PLEASE SEE ELECTRICAL REVIEW COMMENT
 REGARDING CODE EDITIONS AND MAKE
 APPROPRIATE CORRECTIONS. NFPA 101 AND
 NFPA 1, 2003 EDITIONS.
  
 5) IF NO FIRE ALARM SYSTEM, HOOD
 SUPPRESSION WILL BE REQUIRED TO DISPLAY
 OCCUPANT NOTIFICATION BY WAY OF
 AUDIBLE/VISUAL DEVICE. SYSTEM TO BE TIED
 INTO FIRE ALARM SYSTEM IF APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-08-06 Cont ID  
Sent By pschmitz Date 2006-08-06 Time 13:09 Rev Time 0.00
Received By pschmitz Date 2006-08-06 Time 13:09 Sent To  
Notes
2006-08-06 00:00:00PROVISO: EMERGENCY SOV, NOT UNDER HOOD.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-06 Cont ID  
Sent By pschmitz Date 2006-05-06 Time 13:56 Rev Time 0.00
Received By pschmitz Date 2006-05-06 Time 13:55 Sent To  
Notes
2006-05-06 00:00:00[email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
  
 UNSAT
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10)EMERGENCY HOOD SHUT OFF VALVE
 (E) AUTOMATIC SHUT OFF VALVE.
 NFPA-96 SEC 10.5.1, NFPA-1 SEC 50.4/7.1
 GAS EMERGENCY SOV TO BE 42" TO 48" AFF
  
 QUESTIONS 561-805-6692PAUL SCHMITZ

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 10:02 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 10:02 Sent To  
Notes
2007-01-10 10:03:07WAITING FOR "COMM" BD--PROJ TO PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 08:36 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 08:36 Sent To  
Notes
2006-11-15 10:56:39TO "COMM" BD#61
2006-11-13 08:36:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 10:17 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 10:17 Sent To  
Notes
2006-10-01 00:00:00TO COMM BOARD #47
2006-09-18 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 15:13 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 15:13 Sent To  
Notes
2006-06-28 00:00:00TO "COMM" BD#12
2006-06-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 20:00 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 20:00 Sent To  
Notes
2006-03-23 00:00:00TO COMM BOARD # 52, B

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-08 Cont ID  
Sent By shill Date 2006-05-08 Time 16:36 Rev Time 0.00
Received By shill Date 2006-02-28 Time 17:41 Sent To  
Notes
2006-02-28 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-12-12 Cont ID  
Sent By hmoser Date 2006-12-12 Time 08:49 Rev Time 0.00
Received By hmoser Date 2006-12-12 Time 08:49 Sent To  
Notes
2006-12-12 09:21:22PASS PRIVISO
 ACCORDING TO INSTALLATION INSTRUCTIONS THE ROOF TOP
 PACKAGE UNIT WILL PROVIDE UP TO 2,400 CFM. THE DESIGN
 CAPACITY OF THE UNIT IS GREATER THAN 2000 CFM, SO FAN
 SHUTDOWN IS REQUIRED. SECTION 606.2.1 2001 FBC (M) .
 ADDITIONAL PLANS AND PERMITS REQUIRED FOR HOOD,COOLERS
 AND SUPPRESSION.
 PLEASE REFER TO SECTION 606.4.1 SUPERVISION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
2006-11-28 20:06:31NEW SHEETS/INFORMATION

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-23 Cont ID  
Sent By hmoser Date 2006-10-23 Time 14:53 Rev Time 0.00
Received By hmoser Date 2006-10-23 Time 14:53 Sent To  
Notes
2006-10-23 15:15:53MECHANICAL PLANS WERE PASED ON 7/24/06 YOU MUST COMPLI
 WITH PERVISO .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-24 Cont ID  
Sent By hmoser Date 2006-07-24 Time 09:20 Rev Time 0.00
Received By hmoser Date 2006-07-24 Time 09:20 Sent To  
Notes
2006-07-24 00:00:00PASS PROVISO
 1) PLEASE REFER TO SECTION 606.2.1 SNOKE
 DETECTION SYSTEMS CONTROL AND 606.4.1
 SUPERVISON. 2004 FBC.(M)
 2) PLEASE SUBMIT PLANS AND HANGING
 DETAIL WITH THE HOOD PERMIT APPLICATION
 3) PLEASE SUBMIT A COPY OF MANUFACTURERS
 INSTALLATION INSTRUCTIONS FOR WALK IN
 COOLERS WITH PERMIT APPLICATION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-03 Cont ID  
Sent By hmoser Date 2006-04-03 Time 13:59 Rev Time 0.00
Received By hmoser Date 2006-04-03 Time 13:59 Sent To  
Notes
2006-04-03 00:00:00PLAN DENIED
 1) PLEASE PROVIDE A COPY OF
 MANUFACTURERS INSTALLATION INSTRUCTIONS
 OF A/C EQUIPMENT WITH PLANS.
 2) PLEASE REFER TO SECTION 606 AND
 606.4.1 2004 FBC(M)
 3) ADDITIONAL PERMITS REQUIRED FOR WALK
 IN COOLERS,HOOD,HOOD SUPPRESSION.
 4) PLEASE PRINT NAME AND PROVIED A
 SIGNATURE OF ARCHITTECT ON THE PLANS
 SECTION 106.3.4.3 ADMINISTRATION 2004
 EDITION FBC
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-12-02 Cont ID  
Sent By pschmitz Date 2006-12-02 Time 12:27 Rev Time 0.00
Received By pschmitz Date 2006-12-02 Time 12:27 Sent To  
Notes
2006-12-02 12:28:17DBPR AND GREASE TRAP APPROVALSIZE ARE NOW ATTACHERD
 TO THE PLANS AS PREVIOUSLY REQUESTED.PES

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-24 Cont ID  
Sent By kstevens Date 2006-10-24 Time 09:54 Rev Time 0.00
Received By kstevens Date 2006-10-24 Time 09:54 Sent To  
Notes
2006-10-24 10:32:11REFERENCE: FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 DENIED
  
 A. FROM PREVIOUS REVIEW:
  
 2) SHT P-2 PLANS SHALL BE ROUTED TO DBPR, BUSINESS &
 HOTEL DIVISION FOR REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED. THE TWO PAGE
 "WORKSHEETS" SHALL BE ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO THE CITY OF WEST PALM BEACH
 FOR REVIEW. PLEASE CONTACT DBPR AT (850) 487-1395.
  
 SPECIFICATION WORKSHEET FROM DBPR AND STAMPED PLANS ARE
 REQUIRED BEFORE PLUMBING PLAN REVIEW CAN BE APPROVED.
  
 **************NEW COMMENT**************
  
 1B. SEE ELECTRICAL PLAN REVIEW CONCERNING MISSING
 INFORMATION IN THE TITLE BLOCKS OF THE DESIGN
 PROFESSIONAL. ALSO SEE ELECTRICAL REVIEW COMMENTS
 CONCERNING "DESIGN FIRMS", ARCHITECTURAL BUSINESS
 LICENSE NUMBERS ETC. PER FAC 61G1-16.004(2) AND FS
 481.203, 481.223(1)(A), 481.229(1)(C), AND 481.219.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-06 Cont ID  
Sent By pschmitz Date 2006-08-06 Time 13:11 Rev Time 0.00
Received By pschmitz Date 2006-08-06 Time 13:11 Sent To  
Notes
2006-08-06 00:00:00 
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 UNSAT
  
 PREVIOUS NOTES NOT ADDRESED
  
 2) SHT P-2 PLANS SHALL BE ROUTED TO DBPR
 BUSINESS AND HOTEL DIVISION FOR
 REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED
 AND THE TWO PAGE ?WORKSHEETS?
 ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO CITY OF WEST
 PALM BEACH
 FOR REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
  
 SPECIFICATION WORKSHEET FROM DBPR AND
 STAMPED PLANS ARE REQUIRED BEFORE
 PLUMBING PLAN REVIEW CAN BE APPROVED.
  
 END OF COMMENTS,QUESTIONS 561 805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-06 Cont ID  
Sent By pschmitz Date 2006-05-06 Time 13:53 Rev Time 0.00
Received By pschmitz Date 2006-05-06 Time 12:56 Sent To  
Notes
2006-05-06 00:00:00 
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 UNSAT
  
 1) SHT P-2 GRASE TRAP TO BE SIZED BY
 W P BEACHWATERPLANT LAB SUPERVISOR
 INDUSTRIAL COORDINATOR, LYNN MASSON
 OFFICE 561-822-2271
 E-MAIL [email protected]
  
 2) SHT P-2 PLANS SHALL BE ROUTED TO DBPR
 BUSINESS AND HOTEL DIVISION FOR
 REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED
 AND THE TWO PAGE ?WORKSHEETS?
 ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO CITY OF WEST
 PALM BEACH
 FOR REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
  
 3) SHT A-1.0 REST ROOMS DOORS
 11-4.22.2 DOORS.ALL DOORS TO ACCESSIBLE
 TOILET ROOMS SHALL COMPLY WITH SECTION
 11-4.13. DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 4)SHT P-3 GAS RISER DIAGRAM
 SEE GAS PLAN REVIEW COMMENTS.
  
 5) SHT P-3 PLUMBING SPECIFICATIONS NOTE
 (8)REFERENCE TO AIR CHAMBERS PROVIDE A
 DETAIL COMPLYING WITH PRI STD-WH 201
 ALL AIR CHAMBERS SHALL BE ACCESSIBLE.
  
 6) SHT P-2 WATER HEATER
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 607.3.2 BACKFLOW PREVENTION DEVICE OR
 CHECK VALVE.
 WHERE A BACKFLOW PREVENTION DEVICE,
 CHECK VALVE OR OTHER DEVICE IS INSTALLED
 ON A WATER SUPPLY SYSTEM UTILIZING
 STORAGE WATER HEATING EQUIPMENT SUCH
 THAT THERMAL EXPANSION CAUSES AN
 INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 7) SHT P-3 WATER RISER
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED
 TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010.
 SHALL BE INSTALLED BETWEEN THE LAST TWO
 FIXTURES, NOT AT THE TOP OF THE RISER.
  
 END OF COMMENTS, QUESTIONS 561-805-6692