Plan Review Details - Permit 06021026
Plan Review Stops For Permit 06021026
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-15 Cont ID  
Sent By rmcdouga Date 2006-03-15 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2006-03-15 Time 10:42 Sent To  
Notes
2006-03-15 00:00:00DENIED
  
 1) PROJECT INVOLVES A CHANGE OF
 OCCUPANCY. THE PLANS WILL NEED TO BE
 REVIEWED BY PALM BEACH COUNTY TO
 DETERMINE IF ANY IMPACT FEES ARE DUE.
 BOTH SETS OF PLANS ARE REQUIRED TO BE
 REVIEWED AND STAMPED BY THE COUNTY AND A
 COPY OF THE IMPACT FEE RECIEPT TO BE
 SUBMITTTED FOR PERMIT.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SPECIFY THE CONSTRUCTION TYPE OF THE
 EXISTING STRUCTURE BASED ON FBC 2004
 DESIGNATIONS. SEE FBC 602.
  
 4) SPECIFY THE NUMBER OF STORIES. SEE
 FBC CHAPTER 50O.
  
 5) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT THE
 COVERSHEETS WITH THE FL# FOR THE
 EXTERIOR DOOR.
  
 6) SUBMIT FIRE SPRINKLER PLANS PER FBC
 106.3.5.
  
 7) FBC 436.7 REQUIRES A FIRE ALARM
 SYSTEM.
  
 8) FBC 436.7.1.2 REQUIRES FIRE ALARM
 SYSTEM TO TRANSMIT AUTOMATICALLY TO THE
 FIRE DEPARTMENT.
  
 9) FBC 436.7.2 REQUIRES A SMOKE
 DETECTION SYSTEM INSTALLED IN ACCORDANCE
 WITH NFPA 72.
  
 10) FBC 436.8 STATES THAT EVERY INTERIOR
 CORRIDOR SHALL BE CONSTRUCTED OF WALLS
 HAVING NOT LESS THAN A ONE HOUR
 FIRE-RESISTANCE RATING. EXCEPTIONS APPLY
 FOR APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEMS.
  
 11) FBC 1033.6 EVERY ROOM OR SPACE
 NORMALLY SUBJECT TO CLIENT OCCUPANCY,
 OTHER THAN BATHROOMS, SHALL HAVE AT
 LEAST ONE OUTSIDE WINDOW FOR EMERGENCY
 RESCUE AND VENTILATION. SEE EXCEPTIONS.
  
 12) FOR THE PURPOSE OF DETERMINING MEANS
 OF EGRESS REQUIREMENTS FBC 1004.1.2
 REQUIRES 20 NET SQUARE FEET PER OCCUPANT
 FOR DAY CARE OCCUPANCIES.
  
 13) SPECIFY THE SIZES OF EXISTING EXIT
 DOORS. SEE FBC 1008.1 AND 1008.1.1.
  
 14) THE EXIT DISCHARGE EGRESS COURT AT
 THE REAR SHALL COMPLY WITH FBC 1023.5.
  
 15) THE GATES AT THE EGRESS COURT SHALL
 COMPLY WITH FBC 1008.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
 6)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By btrobaug Date 2006-02-27 Time 10:04 Rev Time 1.00
Received By btrobaug Date 2006-02-27 Time 06:33 Sent To  
Notes
2006-02-24 00:00:00 
 1} PLEASE INDICATE COMPLIANCE WITH
 CHAPTER 13 OF THE FBC REGARDING ENERGY
 CODES.
 SEE 13-413,414 AND 415.
  
 2} PLEASE SHOW CIRCUITING FOR THE EXIT
 AND EMERGENCY LIGHTS IN COMPLIANCE WITH
 700.12(E) NEC.
  
 3} INDICATE GUTTER SIZE IN COMPLIANCE
 WITH ARTICLE 376.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By nmccray Date 2006-03-06 Time 13:39 Rev Time 0.00
Received By nmccray Date 2006-03-02 Time 15:58 Sent To  
Notes
2006-03-06 00:00:00DENIED:
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE, 2003 EDITION AND NFPA 1
 UNIFORM FIRE CODE, 2003 EDITION.
  
 2) BASE ON SECTION 16.1.4.1 GENERAL.
 OCCUPANCIES THAT INCLUDE PART-DAY
 PRESCHOOLS, KINDERGARTENS, AND OTHER
 SCHOOLS WHOSE PURPOSE IS PRIMARILY
 EDUCATIONAL, EVEN THOUGH THE CHILDREN
 WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL
 AGE, SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTER 14. UNDER CHAPTER 14 NEW
 EDUCATIONAL OCCUPANCIES REQUIRES THE
 WIDTH OF THE CORRIDORS TO BE MINIMUM OF
 SIX (6) FEET (72") WIDE.
  
 3) PLEASE REFER CHAPTER 14 OF NFPA 101
 LIFE SAFETY CODE, 2003 EDITION FOR OTHER
 REQUIREMENTS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEMS REMODEL.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-15 Cont ID  
Sent By rmcdouga Date 2006-03-15 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2006-02-24 Time 10:25 Sent To  
Notes
2006-02-24 00:00:00TO "BOB"#2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-02-28 Cont ID  
Sent By tgordon Date 2006-02-28 Time 10:36 Rev Time 0.30
Received By tgordon Date 2006-02-28 Time 10:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-07 Cont ID  
Sent By jleech Date 2006-03-07 Time 09:21 Rev Time 2.50
Received By jleech Date 2006-03-07 Time 09:21 Sent To  
Notes
2006-03-07 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM, AUTOMATIC
 CLOTHES WASHER DRAIN TO BE 3" PER.
 FBC-2004 PLUMBING SEC. 406.3.
 2.TABLE 403.1.3(E) MINIMUM PLUMBING
 FIXTURES. TWO DRINKING FOUNTAINS ARE
 REQUIRED.
 3.WATER RISER DIAGRAM, WATER HAMMER
 ARRESTORS ARE REQURED ON THE AUTOMATIC
 CLOTHES WASHERS AND ON KITCHEN SINK SEC.
 604.9. PLEASE SHOW ON PLANS.
 4.WATER HEATER DETAIL SHOWS A
 RECIRCULATION PUMP, WATER RISER DOES NOT
 SHOW REQUIRED PIPING. PLEASE CORRECT.
 5.SHOW SIZING CALCULATIONS FOR WATER
 SEVICE, SEE APPENDIX E.
 6.HANDICAP BATHROOM FACILITIES ARE
 REQUIRED FOR CHILDREN AGES 2 THRU 5.
 PLEASE SHOW ON DETAIL AND ON FLOOR PLAN.
 SHOW CLEAR FLOOR SPACE, TURNING RADIUS,
 DOOR SWING, AND GRAB BARS. FOR
 REQUIREMENTS GO ON LINE TO:
 HTTP://WWW.ACCESS-BOARD.GOV/INDEXES/PUBS
 TTP://WWW.ACCESS-BOARD.GOV/INDEXES/PUBSI
 TP://WWW.ACCESS-BOARD.GOV/INDEXES/PUBSIN
 P://WWW.ACCESS-BOARD.GOV/INDEXES/PUBSIND
 ://WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDE
 //WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX
 /WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.
 WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.H
 WW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.HT
 W.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.HTM
 7.THE SINKNEXT TO THE REF. IN
 KITCHENETTE MUST COMPLY WITH FBC-2004
 CHAPTER 11 SEC. 11-4.23.3 KNEE CLEARENCE
 UNDER SINK. DOORS MUST BE REMOVED FOR
 FRONTAL APPROACH
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-22 Cont ID  
Sent By mmclean Date 2006-03-22 Time 07:36 Rev Time 0.00
Received By mmclean Date 2006-03-22 Time 07:36 Sent To B
Notes
2006-03-22 00:00:00DENIED,
 1. NEED TO SHOW THE LAYOUT OF THE PLAY
 GROUND EQUIPMENT ON THE AREA INDICATED
 ON A-1 (4,970S.F - 3,555SF 45ST PER
 CHILD).
 2. PLEASE PROVIDE THE APPROVAL FROM THE
 STATE FOR THE PLAY AREA.
  
 MICHELLE MCLEAN
 ZONING TECHNICAN
 805-6720