| 2006-03-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 R4101 SWIMMING POOLS |
| | |
| | PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING |
| | INFORMATION REQUIRED FOR PLAN REVIEW: |
| | |
| | 1) COMPLY WITH FBC-2004 SEC. R4101 PRI- |
| | VATE SWIMMING POOLS. (ADD TO NOTES) |
| | 2) PAGE 3 OF 4 STATES "MAXIMUM |
| | UNDERWATER LENGTH OF VENT PIPING 30 |
| | FEET, PAGE 1 OF 4 VENT PIPE APPEARS TO |
| | BE LONGER THAN 30 FEET. PLEASE SUPPLY |
| | ENGINEERED TABLE FOR "VENT PIPE MAXIMUM |
| | LENGTH" INDICATING PUMP SIZE, AVERAGE |
| | FLOW (GPM), AND MAXIMUM LENGTH OF 1-1/2" |
| | PVC VENT PIPE, FROM WHERE IT STARTS TO |
| | WHERE IT TERMINATES. COMPLY WITH 3 SE- |
| | COND RELEASE. |
| | 3) FBC-2004R4101.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER.(ADD TO NOTES, AND DETAILS |
| | REQUIRED) |
| | 4) FBC-2004 R4101.9 WATER SUPPLY, LOCAL |
| | ORD. #2853, BACKFLOW REQUIRED ON WATER |
| | SERVICE. (ADD TO NOTES) |
| | 5) FBC-2004 R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL REQUIRED) |
| | 6) FBC-2004 R4101.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF.(MANUFACTURE CUT SHEETS SUBMITTAL |
| | REQUIRED) |
| | 7) FBC-2004 R4101.15 GAS PIPING SHALL |
| | COMPLY WITH FBC-2004 FUEL GAS. SEPERATE |
| | PLANS AND PERMIT REQUIRED.(ADD TO NOTES) |
| | |
| | END OF COMMENTS: |
| | |