Plan Review Details - Permit 06020972
Plan Review Stops For Permit 06020972
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-01-08 Cont ID  
Sent By rmcdouga Date 2007-01-08 Time 18:33 Rev Time 0.00
Received By rmcdouga Date 2007-01-08 Time 18:33 Sent To  
Notes
2007-01-08 18:48:57REVISION DENIED BY BUILDING
  
 1) THE SCOPE OF THE WORK HAS BEEN INCREASED, SUCH THAT
 IT EXCEEDS THE VALUE OF WORK DECLARED ON THE ORIGINAL
 PERMIT APPLICATION. PLEASE PROVIDE THE COST OF THE
 ADDITIONAL WORK , SO THAT THE PERMIT VALUE CAN BE
 ADJUSTED APPROPRIATLY.
  
 2) SPECIFY THE WIND DESIGN DATA FOR THE EXTERIOR WORK
 ON SHEET A3.2. SEE FBC 1603.1.4.
  
 3) SPECIFY THE ATTACHMENTS FOR THE METAL STUDS TO THE
 MASNORY AND THE PLYWOOD TO THE METAL STUDS. SPECIFY
 FASTENER TYPE, SIZE, EMBED DEPTH, SPACING, ETC.
  
 4) PROVIDE PRODUCT APPROVALS FOR ROOFING MATERIALS OR
 APPLY UNDER SEPARATE PERMIT.) WPB ADMIN CODE 106.3*
 PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-07 Cont ID  
Sent By rmcdouga Date 2006-06-07 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2006-06-07 Time 13:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-05-17 Cont ID  
Sent By rmcdouga Date 2006-05-17 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2006-05-17 Time 10:38 Sent To  
Notes
2006-05-17 00:00:00DENIED BY BUILDING
  
 1) SUBMIT PRODUCT APPROVALS FOR THE NEW
 EXTERIOR WINDOWS AND DOORS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE WWW.
 FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 (IF YOU FIND THAT THE QUOTED WEB PAGE IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
  
 2) FBC 106.3.3* (CITY AMENDMENTS)
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THE CITY OF WEST PALM BEACH IS
 LOCATED IN THE WIND-BORNE DEBRIS REGION.
 FBC 1609.1.4 REQUIRES EXTERIOR GLAZING
 TO BE IMPACT RESISTANT OR PROTECTED WITH
 IMPACT RESISTANT COVERINGS. THE USE OF
 REMOVABLE STORM PANELS OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES ON COMMERCIAL
 BUILDINGS REQUIRE THE APPROVAL OF THE
 BUILDING OFFICIAL (CALL FOR DETAILS).
  
 4) SPECIFY THE TYPE OF CONSTRUCTION OF
 THE STRUCTURE USING FBC 2004
 DESIGNATION. SEE 2004 FBC 602.
  
 5) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR THE NEW EXTERIOR
 WINDOW/DOOR OPENINGS AND THE EXISTING
 OPENINGS WHERE WINDOWS/DOORS ARE BEING
 REPLACED. SEE FBC 1603.1.4(5).
  
 6) PROVIDE BUCK FASTENING DETAILS FOR
 NEW WINDOW AND DOOR OPENINGS. SEE FBC
 1714.5.4.2
  
 7) SPECIFY THE FIRE SEPARATION DISTANCE
 AND SHOW COMPLIANCE WITH ALLOWABLE AREA
 OF OPENINGS IN NORTH WALL WHERE OPENINGS
 ARE BEING ADDED AND INCREASED. SEE FBC
 704.8, 704.3 AND 702.
  
 8) FBC 1013.2 EGRESS THROUGH
 INTERVENING SPACES.
 EGRESS FROM A ROOM OR SPACE SHALL NOT
 PASS THROUGH ADJOINING OR INTERVENING
 ROOMS OR AREAS, EXCEPT WHERE SUCH
 ADJOINING ROOMS OR AREAS ARE ACCESSORY
 TO THE AREA SERVED; ARE NOT A
 HIGH-HAZARD OCCUPANCY AND PROVIDE A
 DISCERNIBLE PATH OF EGRESS TRAVEL TO AN
 EXIT. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR
 SPACES USED FOR SIMILAR PURPOSES. AN
 EXIT ACCESS SHALL NOT PASS THROUGH A
 ROOM THAT CAN BE LOCKED TO PREVENT
 EGRESS. MEANS OF EGRESS FROM DWELLING
 UNITS OR SLEEPING AREAS SHALL NOT LEAD
 THROUGH OTHER SLEEPING AREAS, TOILET
 ROOMS OR BATHROOMS. THIS SECTION DOES
 NOT ALLOW EGRESS THROUGH A KITCHEN IN A
 BUSINESS OCCUPANCY. IF THIS IS A
 BREAKROOM WITH NO STOVE OR OVEN THEN
 EGRESS THROUGH IT WILL BE PERMITTED.
 CHANGE ROOM DESIGNATION ON THE PLAN.
  
 9) 1005.2 DOOR ENCROACHMENT.
 DOORS OPENING INTO THE PATH OF EGRESS
 TRAVEL SHALL NOT REDUCE THE REQUIRED
 WIDTH TO LESS THAN ONE-HALF DURING THE
 COURSE OF THE SWING. WHEN FULLY OPEN,
 THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO THE REQUIRED WIDTH.
 SEE DOOR TO ACCESSIBLE TOLIET ROOM. THE
 REQUIRED EGRESS WIDTH IS 36" AND THE
 SWING OF THE ACCESSIBLE TOLIET ROOM DOOR
 REDUCES THE EGRESS PATH OF TRAVHIS IEL
 BY MORE THAN ONE-HALF. PLEASE CORRECT.
  
  
 10) FBC 11-7.2 SALES AND SERVICE
 COUNTERS, TELLER WINDOWS, INFORMATION
 COUNTERS.
 (2)AT TICKETING COUNTERS, TELLER
 STATIONS IN A BANK, REGISTRATION
 COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS, AND OTHER
 COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES
 ARE SOLD OR DISTRIBUTED, EITHER:
 (I)A PORTION OF THE MAIN COUNTER
 WHICH IS A MINIMUM OF 36 INCHES (915 MM)
 IN LENGTH SHALL BE PROVIDED WITH A
 MAXIMUM HEIGHT OF 36 INCHES (915 MM); OR
  
 (II)AN AUXILIARY COUNTER WITH A
 MAXIMUM HEIGHT OF 36 IN (915 MM) IN
 CLOSE PROXIMITY TO THE MAIN COUNTER
 SHALL BE PROVIDED; OR
 (III)EQUIVALENT FACILITATION SHALL
 BE PROVIDED (E.G., AT A HOTEL
 REGISTRATION COUNTER, EQUIVALENT
 FACILITATION MIGHT CONSIST OF:
 (1)PROVISION OF A FOLDING SHELF
 ATTACHED TO THE MAIN COUNTER ON WHICH AN
 INDIVIDUAL WITH DISABILITIES CAN WRITE,
 AND
 (2)USE OF THE SPACE ON THE SIDE OF
 THE COUNTER OR AT THE CONCIERGE DESK,
 FOR HANDING MATERIALS BACK AND FORTH).
 ALL ACCESSIBLE SALES AND SERVICE
 COUNTERS SHALL BE ON AN ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 .
 REVISE RECEPTION DESK TO COMPLY.
  
 11) PLEASE REMOVE ALL OLD SHEETS THAT
 HAVE BEEN REVISED FROM THE PLANS AND
 INSERT THE NEW SHEETS SO THAT TWO
 COMPLETE SETS OF PLANS ARE CREATED. TWO
 COMPLETE SETS OF PLANS ARE REQUIRED TO
 BE SUBMITTED FOR PERMIT.
  
 NOTE: ITEMS 1-10 WERE REQUESTED IN THE
 PREVIOUS REVIEW BUT HAVE NOT BEEN
 ADDRESSED. A RESPONSE LETTER STATING HOW
 THE COMMENTS WERE ADDRESSED WILL BE
 HELPFUL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-19 Cont ID  
Sent By rmcdouga Date 2006-04-19 Time 14:50 Rev Time 0.00
Received By rmcdouga Date 2006-04-19 Time 07:02 Sent To  
Notes
2006-04-19 00:00:00DENIED BY BUILDING
  
 1) SUBMIT PRODUCT APPROVALS FOR THE NEW
 EXTERIOR WINDOWS AND DOORS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE WWW.
 FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 (IF YOU FIND THAT THE QUOTED WEB PAGE IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
  
 2) FBC 106.3.3* (CITY AMENDMENTS)
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THE CITY OF WEST PALM BEACH IS
 LOCATED IN THE WIND-BORNE DEBRIS REGION.
 FBC 1609.1.4 REQUIRES EXTERIOR GLAZING
 TO BE IMPACT RESISTANT OR PROTECTED WITH
 IMPACT RESISTANT COVERINGS. THE USE OF
 REMOVABLE STORM PANELS OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES ON COMMERCIAL
 BUILDINGS REQUIRE THE APPROVAL OF THE
 BUILDING OFFICIAL (CALL FOR DETAILS).
  
 4) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
 INCLUDE THE PRINTED NAME OF THE
 ARCHITECT IN THE TITLE BLOCK.
  
 5) PROVIDE A LIFE SAFETY PLAN SHOWING
 THE COMMON PATH OF TRAVEL AND TRAVEL
 DISTANCE. SEE 2004 FBC CHAPTER 10.
 NOTE: BASED ON OCCUPANCY, OCCUPANT LOAD
 AND TRAVEL DISTANCE IT APPEARS THAT ONLY
 ONE EXIT IS REQUIRED.
  
 6) SPECIFY THE TYPE OF CONSTRUCTION OF
 THE STRUCTURE. SEE FBC 602.
  
 7) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR THE NEW EXTERIOR
 WINDOW/DOOR OPENINGS AND THE EXISTING
 OPENINGS WHERE WINDOWS/DOORS ARE BEING
 REPLACED. SEE FBC 1603.1.4(5).
  
 8) PROVIDE BUCK FASTENING DETAILS FOR
 NEW WINDOW AND DOOR OPENINGS. SEE FBC
 1714.5.4.2
  
 9) SPECIFY THE FIRE SEPARATION DISTANCE
 AND SHOW COMPLIANCE WITH ALLOWABLE AREA
 OF OPENINGS IN NORTH WALL WHERE OPENINGS
 ARE BEING ADDED AND INCREASED. SEE FBC
 704.8, 704.3 AND 702.
  
 10) FBC 1013.2 EGRESS THROUGH
 INTERVENING SPACES.
 EGRESS FROM A ROOM OR SPACE SHALL NOT
 PASS THROUGH ADJOINING OR INTERVENING
 ROOMS OR AREAS, EXCEPT WHERE SUCH
 ADJOINING ROOMS OR AREAS ARE ACCESSORY
 TO THE AREA SERVED; ARE NOT A
 HIGH-HAZARD OCCUPANCY AND PROVIDE A
 DISCERNIBLE PATH OF EGRESS TRAVEL TO AN
 EXIT. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR
 SPACES USED FOR SIMILAR PURPOSES. AN
 EXIT ACCESS SHALL NOT PASS THROUGH A
 ROOM THAT CAN BE LOCKED TO PREVENT
 EGRESS. MEANS OF EGRESS FROM DWELLING
 UNITS OR SLEEPING AREAS SHALL NOT LEAD
 THROUGH OTHER SLEEPING AREAS, TOILET
 ROOMS OR BATHROOMS.
  
 11) 1005.2 DOOR ENCROACHMENT.
 DOORS OPENING INTO THE PATH OF EGRESS
 TRAVEL SHALL NOT REDUCE THE REQUIRED
 WIDTH TO LESS THAN ONE-HALF DURING THE
 COURSE OF THE SWING. WHEN FULLY OPEN,
 THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO THE REQUIRED WIDTH.
 SEE DOOR TO ACCESSIBLE TOLIET ROOM.
  
 12) 11-7.2 SALES AND SERVICE COUNTERS,
 TELLER WINDOWS, INFORMATION COUNTERS.
 (2)AT TICKETING COUNTERS, TELLER
 STATIONS IN A BANK, REGISTRATION
 COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS, AND OTHER
 COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES
 ARE SOLD OR DISTRIBUTED, EITHER:
 (I)A PORTION OF THE MAIN COUNTER
 WHICH IS A MINIMUM OF 36 INCHES (915 MM)
 IN LENGTH SHALL BE PROVIDED WITH A
 MAXIMUM HEIGHT OF 36 INCHES (915 MM); OR
  
 (II)AN AUXILIARY COUNTER WITH A
 MAXIMUM HEIGHT OF 36 IN (915 MM) IN
 CLOSE PROXIMITY TO THE MAIN COUNTER
 SHALL BE PROVIDED; OR
 (III)EQUIVALENT FACILITATION SHALL
 BE PROVIDED (E.G., AT A HOTEL
 REGISTRATION COUNTER, EQUIVALENT
 FACILITATION MIGHT CONSIST OF:
 (1)PROVISION OF A FOLDING SHELF
 ATTACHED TO THE MAIN COUNTER ON WHICH AN
 INDIVIDUAL WITH DISABILITIES CAN WRITE,
 AND
 (2)USE OF THE SPACE ON THE SIDE OF
 THE COUNTER OR AT THE CONCIERGE DESK,
 FOR HANDING MATERIALS BACK AND FORTH).
 ALL ACCESSIBLE SALES AND SERVICE
 COUNTERS SHALL BE ON AN ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 .
 REVISE RECEPTION DESK TO COMPLY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By rmcdouga Date 2006-03-13 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2006-03-13 Time 16:10 Sent To  
Notes
2006-03-14 00:00:00DENIED
  
 1) THE REQUIRED EXITS FOR THE ADJACENT
 OCCUPANCY MUST BE MAINTAINED DURING
 DEMOLITION AND CONSTRUCTION.
  
 2)PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT TWO COPIES OF STATE PRODUCT
 APPROVALS FOR THE NEW EXTERIOR WINDOW.
  
 3) THE PRINTED NAME OF THE ARCHITECT
 SIGNING AND SEALING THE DRAWINGS IS
 REQUIRED. SEE FAC 61G-16.004.
  
 4) MANEUVERING CLEARANCES AT DOORS
 MINIMUM OF 18" ON PULL SIDE OF DOORS
 REQUIRED BY 11-4.13.6. INDICATE THIS AT
 DOOR #2. CLARIFY DOOR SCHEDULE NOTE 2 ON
 A3.0.
  
 5) SHOW LOCATIONS OF EXIT LIGHTS. SEE
 FBC 1006.3.
  
 6) SPECIFY THE WALL AND CEILING FINISH
 CLASSES THAT ARE ALLOWED BY CODE. SEE
 FBC 803.
  
 7) PROVIDE A LIFE SAFETY PLAN SHOWING
 THE COMMON PATHS OF TRAVEL, ETC. TO THE
 EXITS. SEE FBC CHAPTER 10 MEANS OF
 EGRESS.
  
 8) REVISE NOTES ON SHEET A1.0 TO COMPLY
 WITH 2004 FBC. SECTIONS HAVE CHANGED.
  
 9) REVISE CONSTRUCTION TYPE TO CONCUR
 WITH 2004 FBC. TYPE IV UNPROTECTED
 EQUATES TO TYPE II B. SEE FBC CHAPTER 3.
  
 10) THE NOTE ON A1.0 STATES THAT NO FIRE
 SPRINKLER SYSTEM IS REQUIRED. SPECIFY IF
 THE STRUCTURE IS SPRINKLERED OR
 UNSPRINKLERED. THE NOTES GIVE TRAVEL
 DISTANCES, DEAD ENDS, BUILDING AREA,
 ETC. BASED ON A FULLY SPRINKLERED
 BUILDING.
  
 11) COMMON PATH OF TRAVEL IS NOT TO
 EXCEED 75' IF BUILDING IS NOT
 SPRINKLERED PER FBC 1013.3.
  
 12) TRAVEL DISTANCE FOR UNSPRINKLERED
 BUILD IS 200' AND DEAD END CORRIDOR
 LENGTH IS 20'.
  
 13) THE EGRESS CAPACITY CALCUATION ON
 A1.0 HAS 19 PERSONS WHERE IT SHOULD HAVE
 BEEN 24. PLEASE CORRECT. SEE NOTATIONS
 ON PLAN.
  
 14) THE OCCUPANCY AREA MODIFICATION NOTE
 ON A1.0 IS INCOMPLETE. IN ADDITION TO
 FIRE SPRINKLERS THE ONE STORY BUILDING
 WITH A BUSINESS OCCUPANCY IS REQUIRED TO
 BE SURROUNDED AND ADJOINED BY PUBLIC
 WAYS OR YARDS NOT LESS THAN 60' IN WIDTH
 IN ORDER TO HAVE UNLIMITED AREA PER FBC
 507.2
  
 15) A TENANT SEPARATION WALL WITH A ONE
 HOUR FIRE-RESISTANCE RATING IS REQUIRED
 BETWEEN THIS SPACE AND THE ADJACENT
 TENANT. SEE FBC 708.1 AND 708.3.
  
 16) CORRECT WINDLOAD INFORMATION ON
 SHEET A1.0. THE WINDSPEED FOR WEST PALM
 BEACH IS 140 MPH. THE WINDSPEED MAP IN
 THE 2004 FBC IS FIGURE 1609.
  
 17)11-4.1.6(2) DUTY TO PROVIDE
 AN ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 SUBMIT A COST BREAKDOWN SHOWING THAT 20%
 OF THE CONSTRUCTION COST HAS BEEN SPENT
 ON ACCESSIBILITY.
  
 18)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-01-05 Cont ID  
Sent By btrobaug Date 2007-01-05 Time 14:46 Rev Time 0.50
Received By btrobaug Date 2007-01-05 Time 07:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-11 Cont ID  
Sent By btrobaug Date 2006-09-11 Time 15:27 Rev Time 1.00
Received By btrobaug Date 2006-09-11 Time 12:18 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-05 Cont ID  
Sent By btrobaug Date 2006-05-05 Time 18:16 Rev Time 0.50
Received By btrobaug Date 2006-05-05 Time 17:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-14 Cont ID  
Sent By btrobaug Date 2006-04-14 Time 14:06 Rev Time 1.00
Received By btrobaug Date 2006-04-14 Time 07:40 Sent To  
Notes
2006-04-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE REFERENCE TO ARTICLE
 250.30(A)(4)IN THE RISER DIAGRAM, DOES
 NOT APPLY. THIS METER AND DISCONNECT ARE
 NOT A SEPERATE SYSTEM AS THEY ARE FED
 FROM THE SAME TRANSFORMER AS THE REST OF
 THE SERVICE EQUIPMENT.
 THIS SERVICE SHOULD BE GROUNDED AT A
 COMMON LOCATION . PLEASE INDICATE GEC
 SYSTEM (EXISTING) ON THE RISER. ADDING
 THE GROUNDING POINT INDICATED WILL
 PROBABLY CREATE A PARALLEL GROUND PATH
 IN VIOLATION OF 250.6.
  
 2} THE REFERENCE IN THE ELECTRICAL NOTE
 #1 IS INCORRECT. 2004 FBC, 2002 NEC IS
 CURRENT.
  
 3} BRANCH-CIRCUIT CONDUCTORS SHALL HAVE
 AN AMPACITY NOT LESS THAN THE MAXIMUM
 LOAD TO BE SERVED. WHERE A BRANCH
 CIRCUIT SUPPLIES CONTINUOUS LOADS OR ANY
 COMBINATION OF CONTINUOUS AND
 NONCONTINUOUS LOADS, THE MINIMUM
 BRANCH-CIRCUIT CONDUCTOR SIZE, BEFORE
 THE APPLICATION OF ANY ADJUSTMENT OR
 CORRECTION FACTORS, SHALL HAVE AN
 ALLOWABLE AMPACITY NOT LESS THAN THE
 NONCONTINUOUS LOAD PLUS 125 PERCENT OF
 THE CONTINUOUS LOAD. 210.19(A)(1),
 INCLUDE IN LOAD CALCULATIONS.
  
 4} SHOW COMPLIANCE OF THE ENERGY CODE
 DIAGRAMMATICALLY IF APPLICABLE. SEE
 CHAPTER 13 FBC.(500 SQ FT.).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-02-24 Cont ID  
Sent By btrobaug Date 2006-02-24 Time 11:33 Rev Time 0.75
Received By btrobaug Date 2006-02-24 Time 10:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-12-22 Cont ID  
Sent By mwennerg Date 2006-12-22 Time 13:26 Rev Time 0.00
Received By mwennerg Date 2006-12-22 Time 13:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-06-07 Cont ID  
Sent By rmcdouga Date 2006-06-07 Time 13:49 Rev Time 0.00
Received By rmcdouga Date 2006-06-07 Time 13:48 Sent To  
Notes
2006-06-07 00:00:00NEW PAGES STAMPED BY M. WENNERGREN

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-05-08 Cont ID  
Sent By nmccray Date 2006-05-08 Time 10:44 Rev Time 0.00
Received By nmccray Date 2006-05-08 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-18 Cont ID  
Sent By mwennerg Date 2006-04-18 Time 11:24 Rev Time 0.00
Received By mwennerg Date 2006-04-18 Time 11:24 Sent To  
Notes
2006-04-18 00:00:00******PROVISO******
  
 1) PLEASE SEE COMMENT #3 FROM PREVIOUS
 REVIEW HAS NOT BEEN ADDRESSED. PLEASE
 INDICATE EMERGENCY LIGHT LOCATIONS IN
 NEW AND EXISTING CORRIDORS. PLANS WILL
 BE STAMPED WHEN RETURNED FOR OTHER
 REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By nmccray Date 2006-02-27 Time 13:48 Rev Time 0.00
Received By nmccray Date 2006-02-27 Time 10:32 Sent To  
Notes
2006-02-27 00:00:00DENIED:
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE, 2003 EDITION AND NFPA 1
 UNIFORM FIRE CODE, 2003 EDITION.
  
 2) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 3) PLEASE PROVIDE EMERGENCY LIGHTS IN
 THE EXISTING AND NEW CORRIDOR.
  
 4) INTERIOR WALL AND CEILING FINISH
 MATERIAL COMPLYING WITH SECTION 10.2
 SHALL BE CLASS A OR CLASS B IN EXITS AND
 IN EXIT ACCESS CORRIDORS.
  
 5) ADDRESS IS REQUIRED MINIMUM 6" IN
 HEIGHT.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 16:11 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 16:11 Sent To E
Notes
2006-12-27 16:11:17TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 13:24 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 13:24 Sent To  
Notes
2006-12-21 09:21:50TO "BOB"#6
2006-12-05 13:25:12WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-11 Cont ID  
Sent By btrobaug Date 2006-09-11 Time 15:31 Rev Time 0.00
Received By btrobaug Date 2006-09-11 Time 15:31 Sent To E
Notes
2006-09-11 00:00:00 
 TO MY DESK, 8/22/06 PLANS DUPLICATED,
 SENT BACK TO JACK MORGAN , ELEC REVIEWED
 WITH MEP'S SUBMITTED THIS DATE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 10:40 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 10:40 Sent To E
Notes
2006-08-23 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 15:53 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 15:53 Sent To B
Notes
2006-06-05 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-29 Cont ID  
Sent By adarroug Date 2006-04-29 Time 16:22 Rev Time 0.00
Received By adarroug Date 2006-04-29 Time 16:19 Sent To  
Notes
2006-04-29 00:00:00TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-12 Cont ID  
Sent By adarroug Date 2006-04-12 Time 09:34 Rev Time 0.00
Received By adarroug Date 2006-04-12 Time 09:33 Sent To  
Notes
2006-04-12 00:00:00TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-14 Cont ID  
Sent By rmcdouga Date 2006-03-14 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2006-02-24 Time 09:23 Sent To  
Notes
2006-02-24 00:00:00TO "BOB"#1

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-09-12 Cont ID  
Sent By hmoser Date 2006-09-12 Time 09:09 Rev Time 0.00
Received By hmoser Date 2006-09-12 Time 09:09 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-03 Cont ID  
Sent By tgordon Date 2006-05-03 Time 16:46 Rev Time 0.20
Received By tgordon Date 2006-05-03 Time 16:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-04-13 Cont ID  
Sent By tgordon Date 2006-04-13 Time 13:40 Rev Time 0.30
Received By tgordon Date 2006-04-13 Time 13:40 Sent To  
Notes
2006-04-13 00:00:00*** DENIED ***
 1) PLEASE SHOW MAIN RETURN AIR GRILL AND
 SIZE FOR OPEN OFFICE AREA ON MECH.
 PLANS.
  
 2) RETURN AIR TRANSFER GRILLS ARE UNDER
 SIZED FOR THE EXISTING KITCHEN, ADMIN.
 OFFICE, AND PARTNER'S OFFICE #107 SEE
 NOTE #3 (B).
  
 3)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-02-28 Cont ID  
Sent By tgordon Date 2006-02-28 Time 09:30 Rev Time 0.30
Received By tgordon Date 2006-02-28 Time 09:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-09-12 Cont ID  
Sent By jleech Date 2006-09-12 Time 09:45 Rev Time 0.00
Received By jleech Date 2006-09-12 Time 09:45 Sent To  
Notes
2006-09-12 00:00:00REVISIONS OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-05-08 Cont ID  
Sent By jleech Date 2006-05-08 Time 07:33 Rev Time 0.00
Received By jleech Date 2006-05-08 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-12 Cont ID  
Sent By jleech Date 2006-04-12 Time 14:14 Rev Time 0.00
Received By jleech Date 2006-04-12 Time 14:14 Sent To  
Notes
2006-04-12 00:00:00DENIED;
 NO PLUMBING PLANS WITH NEW SETS OF
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By jleech Date 2006-03-06 Time 08:41 Rev Time 0.00
Received By jleech Date 2006-03-06 Time 08:41 Sent To  
Notes
2006-03-06 00:00:00DENIED;
 1.BREAK SINK IS NOT SHOWN ON DEMO SHEET,
 BUT SINK IS SHOWN ON PLUMBING RISER
 DIAGRAMS. PLEASE SHOW COMPLIANCE WITH
 FBC-2004 CHAPTER 11 SEC 11-4.24.1 THRU
 11-4.24.7. SHOW DETAIL.
 2.MINIMUM PLUMBING FIXTURES TABLE 403.1
 REQUIRES A DRINKING FOUTAIN. NO DRINKING
 FOUNTAIN SHOWN ON DRAWINGS.
 3.PAGE P-3 WATER HEATER DETAIL,(NOTE ON
 DETAIL "PAN DRAIN TO MOP SINK" PLEASE
 SHOW LOCATION OF MOP SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695