Plan Review Details - Permit 06020956
Plan Review Stops For Permit 06020956
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-30 Cont ID  
Sent By amorse Date 2007-08-30 Time 15:02 Rev Time 0.00
Received By amorse Date 2007-08-30 Time 15:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-20 Cont ID  
Sent By amorse Date 2007-03-20 Time   Rev Time 0.00
Received By amorse Date 2007-03-20 Time 17:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-11-06 Cont ID  
Sent By alange Date 2006-11-06 Time 13:06 Rev Time 0.00
Received By alange Date 2006-11-06 Time 12:41 Sent To  
Notes
2006-11-06 13:07:38DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.ENERGY CALCS HAVE NOT BEEN RESUBMITTED.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-11 Cont ID  
Sent By alange Date 2006-07-11 Time 13:09 Rev Time 2.00
Received By alange Date 2006-07-11 Time 13:09 Sent To  
Notes
2006-07-11 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS
 PER 2004 FBC.COMPLETE TOP OF FORM.
  
 5.PRODUCT APPROVALS SUBMITTED ARE
 INCOMPLETE.
 -ROOFING PRODUCT APPROVALS MISSING STATE
 PRODUCT APPROVALS.
 - SELECT ROOFING ASSEMBLY USED ON FLAT
 ROOF PRODUCT APPROVAL.
 -PELLA PRODUCT APPROVALS MISSING QUALITY ASSURANCE,
 NOA.
 -CLOPLAY MISSING STATE PRODUCT APPROVAL.
 -LINTELS NEED BOTH NOA AND STATE PRODUCT APPROVAL.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1 PRIOR
 TO INSTALLATION.
  
 10.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE SEE ASCE 7-98
 SOULD BE ASCE 7-02.
  
 NEW COMMENT;
 A.WINDOWS IN BEDROOM 1 DO NOT MEET
 EGREES REQUIREMENTS.R-310.
 B.R311.5.8.1 SPIRAL STAIRWAYS.
 SPIRAL STAIRWAYS ARE PERMITTED, PROVIDED
 THE MINIMUM WIDTH SHALL BE 26 INCHES
 WITH EACH TREAD HAVING A 7?-INCHES
 MINIMUM TREAD DEPTH AT 12 INCHES FROM
 THE NARROWER EDGE. ALL TREADS SHALL BE
 IDENTICAL, AND THE RISE SHALL BE NO MORE
 THAN 9? INCHES . A MINIMUM HEADROOM OF 6
 FEET 6 INCHES SHALL BE PROVIDED. SHOW
 DETAILS ON PLANS.
  
  
 *COMPLETE THE FOLLOWING BEFORE
 RESUBMITTING*:
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-29 Cont ID  
Sent By alange Date 2006-03-29 Time 11:21 Rev Time 2.75
Received By alange Date 2006-03-29 Time 11:09 Sent To  
Notes
2006-03-29 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS, WINDOWS, STRAPS AND
 TIE-DOWNS, IMPACT PROTECTION, ROOF,
 OVERHEAD DOOR, AND LINTELS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 11.SHOW FINISH FLOOR HEIGHT IN GARAGE
 CONVERSION TO LIVING SPACE.IS THE
 FINISHED FLOOR ON GRADE?
  
 12.SAFTEY GLAZING REQUIRED NEAR TUB
 LOCATIONS PER. 2004 FBC R-308.4
  
 13.R311.5.1 STAIRWAY WIDTH.
 STAIRWAYS SHALL NOT BE LESS THAN 36
 INCHES IN CLEAR WIDTH AT ALL POINTS
 ABOVE THE PERMITTED HANDRAIL HEIGHT AND
 BELOW THE REQUIRED HEADROOM HEIGHT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-04-20 Cont ID  
Sent By btrobaug Date 2007-04-20 Time 14:55 Rev Time 1.00
Received By btrobaug Date 2007-04-20 Time 14:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-04-13 Cont ID  
Sent By btrobaug Date 2007-04-13 Time 11:43 Rev Time 2.00
Received By btrobaug Date 2007-04-13 Time 07:27 Sent To PC
Notes
2007-04-13 11:15:45 
  
  
 DENIED
  
 AS PER NOTE #4- 3/9/06, NOTE #2 -6/2106, AS A NOTE ON
 10/23/06 AND FINALLY AS A PROVISO PENDING FLOOR PLAN
 DESIGNATION CORRECTION ON 1/10/07 ZONING HAS
 CONTINUALLY NOTED THAT ONLY ONE KITCHEN WAS ALLOWED IN
 THE GUEST UNIT. THE LOWER UNIT ON SHEET E-3 HAS NEVER
 BEEN CHANGED TO CORRELATE WITH SHEET A-2.
  
 NOTE #4-6/24/06, NOTE#3-10/27/06 AND A COMMENT THAT THE
 COMMENTS FROM PREVIOUS REVIEWS WERE NOT ADDRESSED ON
 3/19/07, ON THE ELECTRICAL REVIEWS INDICATED THE SAME
 DISCREPANCY, BUT SHEET E-3 SHOWING THE KITCHEN WAS
 RESUBMITTED FOR THE FOURTH TIME ON 4/6/07.
  
 DO NOT RESUBMIT SHEET E-3 WITH A KITCHEN ON THE 1ST
 FLOOR OF THE GUEST HOUSE. REMOVE THE FULL SIZE
 REFRIGERATOR, REMOVE THE SMALL APPLIANCE CIRCUITS AND
 CORRECT THE LOAD CALCULATIONS AFFECTED BY THIS CHANGE.
  
  
 CONTACT THE ARCHITECT TO CONFIRM ROOM DESIGNATIONS AND
 LAYOUT IF NECESSARY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-03-19 Cont ID  
Sent By btrobaug Date 2007-03-19 Time 12:24 Rev Time 0.50
Received By btrobaug Date 2007-03-16 Time 17:19 Sent To B
Notes
2007-03-19 12:20:14 
  
 THERE HAVE BEEN NO ELECTRICAL SHEET CHANGES SINCE THE
 LAST REVIEW. SEE DATES ON SHEETS. THERE ARE SEVERAL
 SETS FROM PREVIOUS REVIEWS RESUBMITTED. REMOVE ALL OLD
 SHEETS FROM THE PLANS, INSERT NEW CODE COMPLIANT
 SHEETS. 10/27/06.
  
 ADDRESS ALL NOTES FROM PREVIOUS REVIEWS. PLEASE NOTE
 THAT 250.24 AND 250.6.} THE EQUIPMENT GROUND BETWEEN
 THE METER AND DISCONNECT ON THE RISER DIAGRAM CREATES A
 PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE
 REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE
 TO BE RAN FROM THE FIRST MEANS OF DISCONNECT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-12 Cont ID  
Sent By btrobaug Date 2006-10-27 Time 14:31 Rev Time 0.75
Received By btrobaug Date 2006-10-27 Time 12:36 Sent To M
Notes
2006-10-27 14:31:24 
  
 DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 1} 250.64 GROUNDING ELECTRODE CONDUCTOR
 INSTALLATION.(C) CONTINUOUS. THE GROUNDING ELECTRODE
 CONDUCTOR SHALL BE INSTALLED IN ONE CONTINUOUS LENGTH
 WITHOUT A SPLICE OR JOINT, UNLESS SPLICED ONLY BY
 IRREVERSIBLE COMPRESSION-TYPE CONNECTORS LISTED FOR THE
 PURPOSE OR BY THE EXOTHERMIC WELDING PROCESS.
  
 2} THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR OF A
 GROUNDED OR UNGROUNDED AC SYSTEM SHALL NOT BE LESS THAN
 GIVEN IN TABLE 250.66.( 1/0 MINIMUM FOR 400 MCM COPPER
 CONDUCTORS.)
  
 3} THE ROOM DESIGNATIONS ON THE ELECTRICAL PLAN FOR THE
 GUEST HOUSE ARE NOT THE SAME AS ON THE ARCHITECTURALS.
 SEE A2 AND E3, ALSO SEE ZONING NOTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 15:57 Sent To P
Notes
2006-06-24 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE BE SURE TO COMPLETELY
 REMOVED ANY OF THE OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 THIS WILL HELP TO AVOID ANY DELAYS IN
 PROCESSING PROJECT.
 ** ONE COPY OF ANY OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED SEPARATELY
 FOR REFERENCE.
  
 2) NOTE: PLEASE SEE FIRM ON "S" SHEETS
 WHICH IS MISSING THE REQUIRED
 CERTIFICATE OF AUTHORIZATION # AS
 REQUIRED PER FAC 61G15-23.002, FS
 471.023
 THIS IS ONLY NOTED, HOWEVER IS REQUIRED
 EVEN IFCOMMENT IS NOT MADE BY OTHER
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE PLANS SHALL
 REFERENCE THE CURRENT CODES IN EFFECT.
 PLEASE SEE PLANS NOW INDICATE THE
 "LATEST CODES". WE ARE NOT CURRENTLY
 UNDER THE LATEST CODES AS THEY HAVE NOT
 YET BEEN ADOPTED BY THE STATE OF
 FLORIDA.
 PLEASE SEE THE FOLLOWING AT A MIN SHOULD
 BEON PLANS. 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72.
  
 4) NOTE: PLEASE SEE ZONING COMMENTS AS
 THESE WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS.
  
 5) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROLS IN MANY LOCATIONS.
 PLEASE SEE CONTROL REQUIRED AT FIRST FLR
 AT CABANA LEADING TO 2ND FLR FOR STAIR
 LTS. PLEASE SEE MISSING 1ST AND 2ND FLR
 CONTROL AT SPIRAL STAIRS SHOWN AT MAIN
 HOUSE.
 PLEASE SEE MISSING CONTROL EXISTING FROM
 BEDRM #2 INTO HALL AS THE 3-WAY IS DOWN
 THE HALL.
 PLEASE SEE ALL RMS AT GUEST HOUSE AND
 APT WHICH INDICATE A SW FOR A FAN AND A
 FAN J-BOX ONLY??
 PLEASE KNOW, A LT FIXTURE WILL BE
 REQUIRED OR 1/2 SWITCHED RECEPT.
 PLEASE SEE OTHER LOCATIONS IN MAIN HOUSE
 ALSO BUT MAINLY CABANA HOUSE.
 210.70, LS 101 7.8, RESIDENTIAL CHAPTER
 24.
  
 6) NOTE: PLEASE SEE SD'S ARE NOT SHOWN
 WITH CIRCUITING , HOWEVER PANEL
 SCHEDULES ARE SHOWING THESE ON A
 DEDICATED CIRCUIT. PLEASE KNOW, THE SD'S
 IN EACH DWELLING CAN BE CIRCUITED TO ONE
 OF THE ARC FAULT PROTECTED BEDRM
 LIGHTING/RECEPT CIRCUITS. THIS WILL
 ALLEAVIATE THE TURNING OFF OF THIS
 CIRCUIT AND LEAVING THE ENTIRE DWELLING
 WITH OUT SD PROTECTION. ( THIS WOULD
 ALSO ALLEAVIATE THE ADDITIONAL AFCI
 BRKR)
 215.5
  
 7) NOTE: PLEASE SEE CABANA SEEMS TO SHOW
 DOORS IN FRONT OF RANGE? PLEASE VERIFY
 COMBUSTIBLES AND LOCATION AS SHOWN.
 THIS IS ONLY NOTED.
  
 8) NOTE: PLEASE SEE DRYER IN CAB SHOWS
 50A BRKR FOR 30A DRYER?? PLEASE SEE MAX
 OCPFOR 30A RECEPT.
 PLEASE ALSO SEE DRYER IN MAIN HOUSE
 WHICH INDICATES 50A OCP ON 30A RECEPT.
 PLEASE SEE 210.21 WHERE THIS IS NOT
 PERMITTED.
  
 9) NOTE: PLEASE SEE MIN VA TO BE FIGURED
 FOR DRYER. 5KW 220.18
  
 10) NOTE: PLEASE SEE 210.52, 210.11C1,
 220.16 FOR MIN OF 1.5KW TO BE FIGUURED
 FOR WASHER/LAUNDRY CIRCUIT.(SHOWS .9)FOR
 BOTH DWELLINGS.
  
 11) NOTE: PLEASE SEE CABANA, MAX OCP FOR
 WH IS 150%, HOWEVER OCP EXCEEDS THIS ,
 AS THE 3.5 KW UNIT SHOWS 2-POLE 30A
 BRKR. (MAX 25A).
 422.11
  
 12) NOTE: PLEASE SEE 408.4 WHERE THE
 PANEL SCHEDULE SHALL BE SPECIFIC FOR
 ROOMS AND ALL AREAS. PLEASE ALSO
 IDENTIFY THE "BATH GFI" CIRCUITS.
 IE: BEDRM #3 RECEPTS , LIV RM LTS ETC
 ** IT IS KNOWN, THAT DURING CONSTRUCTION
 THESE CIRCUITS MAY CHANGE AND CAN BE
 REVISED AT A LATER DATE.
  
 13) NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 IN BEDRM #2 (MAIN HOUSE)
  
 14) NOTE: PLEASE SEE MISSSING HALLWAY
 RECEPT PER 210.52H CAB 2ND FLR)
  
 15) NOTE: PLEASE SPECIFY SIZE OF
 METERBANK AS A 325A SERVICE IS BEING
 PROVIDED.
 PLEASE SEE MIN SIZE OF THE SEC'S SHALL
 BE 350 MCM BASED ON 310.15B6.
 PLEASE SEE THE RISER SIZE WILL ALSO
 CHANGE PER TABLES (9).
 PLEASE SEE 240.4, 310.15B6,215.5
  
 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 17) NOTE: PLEASE SEE RISER IS SHOWING
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 METER TO MAINS. PLEASE SEE THE EQP GRNDS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
 250.6,250.24B
  
 18) NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCES REQUIRED FOR CLOSET LTS.
 PLEASE SEE GUEST HOUSE AS THESE ARE
 RIGHT NEXT TO SHELVES WHICH ARE NOT
 PERMITTED.
  
 19) NOTE: PLEASE SEE GROUNDING ELECTRODE
 RISER SHALL INCLUDE ANY NEW FOOTER STEEL
 AS REQUIRED PER 250.50.
  
 20) NOTE: PLEASE SEE DISCONNECT AND AHU
 IN UPSTAIRS CLOSET SEEMS TO BE LOCATED
 NOT TO MEET 110.26. PLEASE ALSO SEE
 240.24D AS OCP IS NOT PERMITTED IN A
 CLOTHES CLOSET.
  
 21) NOTE: PLEASE SEE THIS WOULD ALSO
 INCLUDE ANY CLOSET WHERE OCP FOR WATER
 HEATERS ARE LOCATED.
 PLEASE ALSO SEE MIN SEPARATIONS REQUIRED
 PER 422.17
  
 ** PLEASE SUBMIT THE ABOVE FOR REVIEW
 AND IF THERE ARE ANY QUESTIONS OR
 COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-23 Cont ID  
Sent By btrobaug Date 2006-03-23 Time 12:00 Rev Time 1.50
Received By btrobaug Date 2006-03-23 Time 07:03 Sent To M
Notes
2006-03-23 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 250.52(A)(3) CONCRETE-ENCASED
 ELECTRODE. AN ELECTRODE ENCASED BY AT
 LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED
 WITHIN AND NEAR THE BOTTOM OF A CONCRETE
 FOUNDATION OR FOOTING THAT IS IN DIRECT
 CONTACT WITH THE EARTH, CONSISTING OF AT
 LEAST 6.0 M (20 FT) OF ONE OR MORE BARE
 OR ZINC GALVANIZED OR OTHER ELECTRICALLY
 CONDUCTIVE COATED STEEL REINFORCING BARS
 OR RODS OF NOT LESS THAN 13 MM (? IN.)
 IN DIAMETER, OR CONSISTING OF AT LEAST
 6.0 M (20 FT) OF BARE COPPER CONDUCTOR
 NOT SMALLER THAN 4 AWG. REINFORCING BARS
 SHALL BE PERMITTED TO BE BONDED TOGETHER
 BY THE USUAL STEEL TIE WIRES OR OTHER
 EFFECTIVE MEANS. INDICATE ON RISER.
  
 2)(A) GROUNDING ELECTRODE. WHERE TWO OR
 MORE BUILDINGS OR STRUCTURES ARE
 SUPPLIED FROM A COMMON AC SERVICE BY A
 FEEDER(S) OR BRANCH CIRCUIT(S), THE
 GROUNDING ELECTRODE(S) REQUIRED IN PART
 III OF THIS ARTICLE AT EACH BUILDING OR
 STRUCTURE SHALL BE CONNECTED IN THE
 MANNER SPECIFIED IN 250.32(B) OR (C).
 WHERE THERE ARE NO EXISTING GROUNDING
 ELECTRODES, THE GROUNDING ELECTRODE(S)
 REQUIRED IN PART III OF THIS ARTICLE
 SHALL BE INSTALLED. SHOW ON RISER.
  
 3} THE FEED FROM PANEL A TO PANEL B IS 3
 #2'S ON THE RISER AND 2 #6'S ON PANEL
 SCHEDULE "A", CIRCUITS 11,13.
  
 4} THE BATH GFI (RM 107), IS ON CIRCUIT
 "A 16", WHICH IS SHARED BY OUTSIDE
 RECEPTACLES INVIOLATION OF
 210.11(C)(3)-BATH CIRCUITS.
  
 5} THE RECEPTACLE IN THE KITCHEN ON
 CIRCUIT "A28" SHOULD BE ON A SMALL
 APPLIANCE CIRCUIT PER 210.52(B)(1).
  
 6} BEDROOM #2 NEEDS 2 ADDED RECEPTACLES
 TO COMPLY WITH 210.52(A)(2). SEE
 REVIEWED SET.
  
 7} THE JACUZZI MUST BE GFI PROTECTED PER
 680.44.
  
 REGARDING THE APARTMENTS IN THE SEPARATE
 STRUCTURE: SHEET"E-3".
  
 1} THE SMOKE DETECTORS MUST BE ON ARC
 FAULT PROTECTED. ALSO NOTE THAT THE
 FIRST FLOOR DETECTORS ARE ON THE SECOND
 FLOOR PANEL.
  
 2} THE UPPER BATH CIRCUIT MUST COMPLY
 WITH 210.11(C)(3). SEE CIRCUIT # D-18
 FEEDS THE SMOKE DETECTORS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-02-22 Cont ID  
Sent By ptjomsto Date 2006-02-22 Time 16:08 Rev Time 0.00
Received By ptjomsto Date 2006-02-22 Time 16:08 Sent To  
Notes
2006-02-22 00:00:00HISTORIC APPROVED BY F MITTNER

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 08:23 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 08:23 Sent To B
Notes
2007-08-27 08:24:08TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-04-06 Cont ID  
Sent By spalmer Date 2007-04-06 Time 17:13 Rev Time 0.00
Received By spalmer Date 2007-04-06 Time 17:13 Sent To E
Notes
2007-04-06 17:14:12TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 17:46 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 17:46 Sent To Z
Notes
2006-12-17 17:46:16TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 15:34 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 15:34 Sent To E
Notes
2006-10-24 15:35:05TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-13 Cont ID  
Sent By adarroug Date 2006-10-13 Time 16:51 Rev Time 0.00
Received By adarroug Date 2006-10-13 Time 16:51 Sent To Z
Notes
2006-10-13 16:51:57TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 11:45 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 11:45 Sent To E
Notes
2006-06-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-16 Cont ID  
Sent By adarroug Date 2006-06-16 Time 15:46 Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 15:46 Sent To Z
Notes
2006-06-16 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-16 Cont ID  
Sent By adarroug Date 2006-03-16 Time 09:40 Rev Time 0.00
Received By adarroug Date 2006-03-16 Time 09:40 Sent To E
Notes
2006-03-16 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 10:35 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 10:35 Sent To  
Notes
2006-03-10 00:00:00TO "HISTORIC" DEPARTMENT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-29 Cont ID  
Sent By alange Date 2006-03-29 Time 11:09 Rev Time 0.00
Received By alange Date 2006-02-25 Time 13:16 Sent To  
Notes
2006-02-25 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-16 Cont ID  
Sent By tgordon Date 2007-03-16 Time 16:43 Rev Time 0.25
Received By lmartine Date 2007-03-16 Time 16:43 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-10-30 Cont ID  
Sent By btrobaug Date 2006-10-30 Time 08:52 Rev Time 0.35
Received By tgordon Date 2006-10-30 Time 09:15 Sent To P
Notes
2006-10-30 09:26:11*** DENIED ***
 1) ENERGY CALCULATIONS HAVE NOT BEEN RE-SUBMITTED,
 PLEASE SUBMIT ENERGY CAL'S, PER 2004 FBC 13-101.2.2.
  
 2) SEE PAGE M-1 DESIGN SERVICES MEP LLC, SEE PAGES M-2
 AND M-3 DESIGN SERVICES MEP ENGINEERING, IF THEY ARE AN
 ENGINEERING COMPANY THEN THEY NEED THERE LICENSE NUMBER
 AND CERTIFICATE OF AUTHORIZATION NUMBER ON THE PLANS,
 PER FAC 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By tgordon Date 2006-07-10 Time 10:36 Rev Time 0.45
Received By tgordon Date 2006-07-10 Time 10:36 Sent To B
Notes
2006-07-10 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 3-23-06
 NOTE #1, ENERGY CALCULATIONS NEED TO BE
 SIGNED BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 2) AS REQUESTED IN LAST REVIEW 3-23-06
 NOTE #3, PLEASE SUBMIT DETAILED
 MANUFACTURE'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR PRE-FAB
 FIREPLACE.
  
 3) AS REQUESTED IN LAST REVIEW 3-23-06
 NOTE #5, RETURN AIR TRANSFER GRILL TO
 MASTER SUITE IS TO SMALL, SEE NOTE #5
 (B)&(C) MASTER SUITE (INCLUDES BATHROOM
 & CLOSET) PLEASE CORRECT.
  
 4) PLEASE PROVIDE COMBUSTION AIR FOR GAS
 CLOTHES DRYER IN MAIN HOUSE SECOND FLOOR
 AND ANY OTHER GAS APPLIANCES, PER 2004
 FBC/M 1701.1 .
  
 5) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-23 Cont ID  
Sent By tgordon Date 2006-03-23 Time 14:18 Rev Time 1.00
Received By tgordon Date 2006-03-23 Time 14:18 Sent To P
Notes
2006-03-23 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A . AND
 ALSO SIGNED BY OWNER/AGENT.
  
 2) PLEASE SHOW ON A/C EQUIPMENT LIST ALL
 NEW AND EXISTING A/C SYSTEMS, AND
 DESIGNATE IF NEW OR EXISTING AND ALL
 PERTINENT INFORMATION.
  
 3) NEED TO SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR FIRE PLACE IN FAMILY
 ROOM.
  
 4) PLEASE EXPLAIN WHY THE GAS LINE IS
 RUNNING UP TO THE SECOND FLOOR.
  
 5) THE RETURN AIR GRILL TO THE MASTER
 BEDROOM IS TO SMALL, PLEASE CORRECT. SEE
 NOTE #6 (C) EXCEPT.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-03 Cont ID  
Sent By jleech Date 2006-11-03 Time 07:10 Rev Time 0.00
Received By jleech Date 2006-11-03 Time 07:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 07:16 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 07:16 Sent To M
Notes
2006-07-08 00:00:00DENIED;
 1.PAGE A-3 SECONDARY DRAIN PROTECTION IS
 REQUIRED FOR FLAT PART OF ROOF. SHOW SQ.
 FT. OF ROOF SIZE ROOF DRAINS SHOW PIPING
 AND TERMANATION. SEE FBC-2004 PLUMBING
 CHAPTER 11, TABLES 1106.2 AND 1106.3 AND
 SEC 1107.
 2.PAGE P-2 WATER RISER; SHOW EXPANTION
 TANK AS REQUIRED BY SEC 607.3. IS WATER
 HEATER ON FIRST FLOOR FOR BOTH
 APARTMENTS?
 3.SANITARY RISER DIAGRAM BACK BUILDING;
 AUTOMATIC CLOTHES WASHER DRAIN TO BE 3"
 SEE SEC. 406.3.
 4. RISER DIAGRAM SHOWS 2 EXISTING
 SANITARY SEWERS IS THIS TRUE?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-27 Cont ID  
Sent By jleech Date 2006-03-27 Time 10:12 Rev Time 0.00
Received By jleech Date 2006-03-27 Time 10:12 Sent To B
Notes
2006-03-27 00:00:00DENIED;
 1.PLANS REVIEWED UNDER THE FBC-2004
 CODE.
 2.WATER HAMMER ARRESTORS REQUIRED FOR
 ICEMAKER LINE AND HOT WATER (KITCHEN)
 3.WATER ISOMETRIC FIRST FLOOR BATHROOM,
 NO WATER TO TOILET.
 4.BACK HOUSE IS NOT SHOWN ON SANITARY OR
 WATER ISOMETRICS. PLEASE SHOW HOW WATER
 IS DISTRIBUTED TO THE BACK HOUSE. IF
 BOTH BUILDINGS ARE ON ONE METER A
 BACKFLOW IS REQUIRED . (UTILITY ORD.).
 ALSO A MEANS OF THERMAL EXPANSION IS
 REQUIRED PER FBC-2004 PLUMBING SEC.
 607.3. PLESE SHOW TIE-IN TO BUILDING
 SEWER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2007-01-10 Cont ID  
Sent By mmclean Date 2007-01-10 Time 15:20 Rev Time 0.00
Received By mmclean Date 2006-12-26 Time 16:08 Sent To I
Notes
2007-01-10 15:22:481/10/06 - PROVISO: ELECTRICAL PLANS MUST MATCH THE
 ARCHITECTUAL PLANS. NO 2/20, TWO KITCHENS, 2 SEPARATE
 APTS.
2006-12-26 16:09:58NEED TO CLARIFY THE PLANS WITH SHIRLEY & ANGELLA.
 PLANS FOR FLOOR GUEST PLANS AND ELECTRICAL PLANS DOES
 NOT MATCH.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-10-23 Cont ID  
Sent By mmclean Date 2006-10-23 Time 16:15 Rev Time 0.00
Received By mmclean Date 2006-10-23 Time 16:15 Sent To I
Notes
2006-10-23 16:29:20DENIED,
 1. THE REQUESTED SURVEY IS NOT ENCLOSED IN PACKAGE. 2.
 THE ELEVATION PLANS FOR REAR STRUCTURE STILL SHOWS THE
 FOUNTAIN (COMMENTS INDICATED THAT THE FOUNTAIN IS BEING
 REMOVED).
 3. PLEASE CLARIFY THE A-2 (GUEST HOUSE) 1ST FLOOR, THE
 PROPOSED GARAGE IS NOT SHOWING AS A FUNCTIONAL GARAGE,
 THE GARAGE DOOR IS SHOWN.
 4. PLEASE CLARIFY THE USE OF THE THE SECTION BELOW THE
 GARAGE.
 5. THE LIVING AREA SHOWS AN X THROUGH, PLEASE CLARIFY.
 6. NEED HISTORIC TO REVIEW THE REVISIONS THAT ARE BEING
 SUBMITTED.
 7. THE ORIGINAL PERMIT APPLICATION WAS NOT RETURNED
 WITH RESUB PLANS.
  
 NOTE: CANNOT ADD ANY SQUARE FOOTAGE TO THE EXISTING
 GUEST STRUCTURE, OVER THE 1000SQ FT REQUIREMENTS.
  
 NOTE: CANNOT HAVE TWO COOKING FACILITY WITHIN THE
 EXISTING GUEST STRUCTURE (ONLY 1 KITCHEN).
  
 NOTE: MUST PULL A SEPARATE PERMIT FOR THE PROPOSED
 POOL.
  
 NOTE: MUST PULL A SEPARATE PERMIT FOR FENCE/WALL/GATE
 WITH UTILITY EASEMENT APPROVALS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2006-06-21 Cont ID  
Sent By mmclean Date 2006-06-21 Time 11:11 Rev Time 0.00
Received By mmclean Date 2006-06-21 Time 11:11 Sent To I
Notes
2006-06-21 00:00:00DENIED,
 1. THE PROPOSED FOUNTAIN ON ACCESSORY
 STRUCTURE MUST BE SHOWN ON THE
 SURVEY(ATTACHED TO EXISTING REAR
 STRUCTURE).
 2. MUST REMOVE THE REF. ON THE 1ST FLOOR
 OF THE EXISTING REAR STRUCTURE.MAY
 HAVE A U/C REF (ONLY 1 COOKING FACILTY
 ALLOWED).
 3. MUST SHOW THE A/C UNIT ON THE
 SITEPLAN WITH SETBACK.
 NOTE: SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
 4. THE FOOTPRINT OF THE SITEPLAN DOES
 NOT MATCH TO THE FLOOR PLAN A-1 (LOGGIA
 & BALCONY.
 5 MUST SHOW ON SITEPLAN THE LOGGIA WITH
 2ND STORY BALCONY AND PROVIDE THE
 DISTANCE FROM THE EXISTING REAR
 STRUCTURE.
 6. PLEASE INCLUDE A COPY OF THE EXISTING
 SURVEY.
 7. HISTORIC MUST REVIEW THE REVISED
 PLANS BEFORE PLANS ARE P/U AND RESUB.
  
 NOTE: THE COVERED ENTRY SHALL NOT EXTEND
 FARTHER THAN 3FT INTO ANY SETBACK
 (SEC-305(2)
 NOTE. A SEPERATE PERMIT MUST BE PULLED
 FOR FOUNTAIN/POOL/DECK.
 NOTE A SEPERATE PERMIT MUST BE PULLED
 FOR THE CBS WALL/FENCE WITH UTILTITY
 EASEMENT APPROVAL FROM CITY OF WEST PALM
 BEACH UTILITY DEPT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By mmclean Date 2006-03-09 Time 16:37 Rev Time 0.00
Received By mmclean Date 2006-03-09 Time 16:37 Sent To I
Notes
2006-03-09 00:00:00DENIED, - SF14
 1. THE SITEPLAN PROVIDE DOES NOT SHOW
 THE SETBACKS CLEARLY (EG THE FRONT
 SETBACK).
 2. CANNOT ADD ANY MORE SQUARE FOOTAGE TO
 EXISTING STRUCTRE, ALREADY OVER THE
 REQUIRED SQUARE FOOTAGE (1000SQ FT).
 3. MUST PROVIDE THE DIMENSION OF
 PROPOSED WALKWAY (WIDTH & LENGTH).
 4. ACCESSORY STRUCTURE IS ONLY ALLOWED
 ONE KITCHEN, PLEASE COULD YOU PROVIDE
 PROOF OF PERMIT APPROVING A SECOND
 KITCHEN IN ACCESSORY STRUCUTRE.
 5. MUST PULL A SEPERATE PERMIT FOR
 WALL/GATE/FENCE WITH EASEMENT APPROVAL
 FROM THE CITY OF WEST PALM BEACH UTILITY
 DEPT.
 6. NEED TO HAVE HISTORIC TO REVIEW PLANS
 FOR APPROVAL.(BEFORE SUBMITTING BACK IN
 FOR FURTHER PERMITTING REVIEW)
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
  