Plan Review Details - Permit 06020899
Plan Review Stops For Permit 06020899
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-15 Cont ID  
Sent By jgomez Date 2006-03-15 Time 11:13 Rev Time 0.50
Received By jgomez Date 2006-03-15 Time 11:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-21 Cont ID  
Sent By jgomez Date 2006-02-21 Time 12:57 Rev Time 0.50
Received By jgomez Date 2006-02-21 Time 12:57 Sent To  
Notes
2006-02-21 00:00:00BUILDING REVIEW CHECKLIST:
 1- FLAT ROOF SYSTEM PRODUCT APPROVAL
 SUBMITTED IS MISING THE SPECIFIC
 APPROVED ASSEMBLY THAT IS GOING TO BE
 INSTALLED AND THE GENERAL LIMITATIONS
 PAGE. SEE ATTACHED COPY OF THE CITY
 POLICY FOR RE-ROOF PERMITS AND
 INFORMATION REQUIRED TO BE SUBMITTED FOR
 PERMITS.
  
 2- A) IF SELECTED APPROVED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #7, THEN
 THE REQUIRED CALCULATIONS FOR ENHANCED
 NAILING AT PERIMETER AND CORNER AREAS
 MUST BE SUBMITTED AND MUST BE PREPARED
 BY ONE OF THE PROFESSIONALS LISTED IN
 LIMITATION #7.
  
 B) IF SELECTED APPROVED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #9, THEN
 ADDITIONAL NAIL ENHANCING IS NOT
 ALLOWED. SEE GENERAL LIMITATION #9.
 THEREFORE, IT CAN'T BE USED IN THIS
 AREA.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  
  