Plan Review Details - Permit 06020895
Plan Review Stops For Permit 06020895
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-20 Cont ID  
Sent By nmccray Date 2006-04-20 Time 10:52 Rev Time 0.00
Received By nmccray Date 2006-04-20 Time 10:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-17 Cont ID  
Sent By mwennerg Date 2006-03-17 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2006-03-17 Time 15:01 Sent To  
Notes
2006-03-17 00:00:00******DENIED******
  
 1) PLEASE ILLUSTRATE THE LOCATIONS OF
 DUCT SMOKE DETECTORS. THE RISER DIAGRAM
 AND DRAWINGS INDICATE FIVE AC UNITS.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 3) FIRE ALARM TO BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE. UL CERTIFICATE
 WILL BE REQUIRED AT TIME OF FIRE ALARM
 FINAL INSPECTION.
  
 4) FIRE ALARM SYSTEM SHALL BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 5) SIGNED, SEALED AND DATED PLANS HAVE
 BEEN SUBMITTED, HOWEVER COPIES HAVE BEEN
 PROVIDED. PLANS MUST COMPLY WITH FAC
 61G15-23.001, AND MUST SHOW THE WORD
 "LICENSE" IN THE SEAL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-11 Cont ID  
Sent By adarroug Date 2006-04-11 Time 10:20 Rev Time 0.00
Received By adarroug Date 2006-04-11 Time 10:20 Sent To FIRE
Notes
2006-04-11 00:00:00TO "F' BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-11 Cont ID  
Sent By adarroug Date 2006-03-17 Time 10:22 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 14:21 Sent To  
Notes
2006-02-22 00:00:00TO "F" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved