Plan Review Details - Permit 06020800
Plan Review Stops For Permit 06020800
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2009-01-29 Cont ID  
Sent By jgomez Date 2009-01-29 Time 16:26 Rev Time 0.00
Received By jgomez Date 2009-01-29 Time 16:25 Sent To P
Notes
2009-01-29 16:26:10THIS IS A PLUMBING REVISION, NOT BUILDING REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-13 Cont ID  
Sent By jgomez Date 2008-03-13 Time 14:18 Rev Time 0.00
Received By jgomez Date 2008-03-13 Time 14:18 Sent To PC
Notes
2008-03-13 14:18:54LOW WALL REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-02 Cont ID  
Sent By lmartine Date 2006-10-02 Time 11:07 Rev Time 0.00
Received By lmartine Date 2006-10-02 Time 11:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-25 Cont ID  
Sent By jgomez Date 2006-08-25 Time 14:44 Rev Time 3.00
Received By jgomez Date 2006-08-25 Time 07:51 Sent To  
Notes
2006-08-25 00:00:00BUILDING REVIEW 3RD CHECKLIST:
 1- A BULDING PERMIT CAN'T BE ISSUED IF
 ENERGY CALCULATIONS HAVE GROSS ERRORS.
 SEE SECTION 13-103.3 FBC 2004.
 ON PREVIOUS CHECKLIST I ASKED ENGINEER
 TO CHECK SEC. 13-601 FBC 2004 FOR PROPER
 WAY OF CALCULATING OVERHANG LENGTH AND
 HEIGHT. ENERGY CALCULATIONS SUBMITTED
 STILL SHOW INCORRECT OVERHANG AND LENGTH
 DIMENSIONS. NEED TO REVISE AS REQUIRED.
  
 NOTE:
 * ENGINEER TO SEE ATTACHED COPY OF THE
 FLORIDA STATUTE 553.80(2)(B)REGARDING
 DESIGN PROFESSIONALS DOCUMENTS AND FINES
 FOR REPETITIVE PLAN REVIEWS.
  
 2- REVISE SURVEY: PROPERTY IS NOT
 LOCATED IN FLOOD ZONE "C". PROPERTY IS
 LOCATED IN FLOOD ZONE "B" AS PER
 COMMUNITY PANEL NO 120229-0015-B AND
 DATED MARCH 1ST, 1979.
  
 3- TRUSS PACKAGE:
 A) TRUSS ENGINEER TO FOLLOW CHAPTER 471
 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-23.002
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS. RUBBER STAMP SIGNATURE IS NOT
 ALLOWED.
  
 B) IF ENGINEER DOESN'T WANT TO SIGN AND
 SEAL EACH DRAWING, THEN HE NEEDS TO
 PROVIDE ALL INFORMATION REQUIRED ON SEC.
 61G15-31.003(4)(A)
  
 C) PROVIDE CORRECT MEAN ROOF HEIGHT.
 SEE PLANS.
  
 4- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS OF RECORDING IF WORK IS
 NOT STARTED. SEE SECTION 713.13(2) OF
 FLORIDA STATUTES. NEED RE-RECORDED NOC.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-16 Cont ID  
Sent By jgomez Date 2006-06-15 Time 14:49 Rev Time 4.00
Received By jgomez Date 2006-06-15 Time 14:49 Sent To  
Notes
2006-06-15 00:00:00BUILDING REVIEW 2ND CHECKLIST
 1- REVISE ENERGY CALCULATIONS:
 A) A/C AREA DOESN'T MATCH PLANS.
  
 B) ENGINEER WHO PREPARED CALCULATIONS
 NEED TO PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND FAC 61G15-23.002.
  
 C) COMPLETE ALL INFORMATION ON TOP OF
 FORM.
  
 D) CALCULATIONS SHOWING ORIENTATION OF
 BUILDING DON'T MATCH PLANS. CALCULATIONS
 NEED TO BE DONE FOR WORST CASE SCENARIO
 OR ACTUAL BUILDING ORIENTATION.
  
 E) REVISE OVERHANG LENGHT AND OVERHANG
 HEIGHT TO MATCH PLANS. SEE SECTION
 13-601 FBC 2004 FOR PROPER WAY OF
 CALCULATING OVERHANG LENGTH AND HEIGHT.
  
 F) GLASS AREA IS INCORRECT. SEE SECTION
 13-601.2.A.3.3 FBC 2004 FOR PROPER WAY
 OF CALCULATING GLASS AREA.
  
 NOTE:
 ENGINEER TO SEE ATTACHED COPY OF FLORIDA
 STATUTE 553.80(2)(B) REGARDING DESIGN
 PROFESSIONAL DOCUMENTS.
  
 2- A) PLANS NEED THE PALM BEACH COUNTY
 IMPACT FEE STAMP AND
 B) PROVIDE COPY OF IMPACT FEES PAID
 RECEIPT.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
 RESPONSE SAYING INSTALLATION AS PER
 PRODUCT APPROVAL DOENS'T PROVIDE
 INFORMATION REQUIRED TO BE SPECIFIED BY
 THE DESIGNER. PRODUCT APPROVAL IS ONLY
 TO COMPLY WITH DESIGNER SPECS.
  
 4- STAIR DETAILS:
 A) INTERIOR STAIRS EXCEED THE 24-25
 RATIO REQUIRED BY SEC. R311.5.3.2.
  
 B) PROVIDE SPECS SHOWING THAT 4" SPHERE
 CAN'T PASS THRU. SEC. R12.2.
  
 C) SHOW HANDRAIL IN EXTERIOR STAIRS.
  
 5- PROVIDE COMPLETE SECTIONS/DETAILS AND
 SPECS FOR CHIMNEY CONSTRUCTION. DRAWING
 SUBMITTED DOESN'T PROVIDE ANY
 INFORMATION FOR SIZES AND FASTENING OF
 WOOD FRAMING. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 6- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ALL TRUSS AND STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS. PRODUCT APPROVALS
 SUBMITTED DON'T COVER ALL OF THEM.
  
 B) PRECAST LINTELS. NOA SUBMITTED IS
 EXPIRED.
  
 C) LARGE FIXED WINDOWS C AND D. PRODUCT
 APPROVALS SUBMITTED DON'T COVER THIS
 OVERSIZE WINDOWS.
  
 D) FLAT ROOF SYSTEM. PROVIDE
 CALCULATIONS PER RAS 117 AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF
 THE NOA. CALCULATIONS MUST BE SIGNED AND
 SEALED BY ANY ONE OF THE PROFESSIONALS
 LISTED IN LIMITATION #7.
  
 E) SPECIFY SIZE OF MULLION AND FASTENERS
 FOR WINDOWS C AND D. PROVIDE PRODUCT
 APPROVAL IF MULLION SIZE IS BIGGER THAN
 1". SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 7- PROVIDE COMPLETE DETAILS FOR STEEL
 COLUMNS. MISSING TOP CONNECTION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- PROVIDE SURVEY FOR PROPOSED LAYOUT.
 STILL SUBMITTING OLD LAYOUT.
  
 9- OWES $1200.74 FOR UPDATED VALUATION
 AND RADON FEES. THIS COULD NOT BE DONE
 ON FIRST REVIEW BECAUSE AREA TABULATION
 WAS INCORRECT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By jgomez Date 2006-03-20 Time 17:07 Rev Time 4.00
Received By jgomez Date 2006-03-20 Time 17:07 Sent To  
Notes
2006-03-20 00:00:00BUILDING REVIEW CHECKLIST;
 1- ONLY TWO SETS OF PLANS AND PRODUCT
 APPROVALS ARE REQUIRED.
  
 2- NOC IS EXPIRED AFTER 90 DAYS IF WORK
 IS NOT COMMENCED. NEED RE-RECORDED ONE.
  
 3- A) BUILDING AREAS SHOWN ON PAGE A-1
 DON'T ADD UP. REVISE AS REQUIRED.
 B) SHOW AREA TABULATION IDENTIFYING
 AREAS SEPARATELY. EG: 1ST FLOOR AREA,
 2ND FLOOR AREA, GUEST COTTAGE, ETC. TO
 PROPERLY VALUATE PROJECT AND AREAS TO BE
 CONSIDERED FOR RADON FEES. SEC. 108.3
 CITY AMENDMENTS TO FBC 2004.
 C) RESUBMIT SHEET WITH IMPACT FEES
 PAID STAMP FOR THE FILE WHEN DRAWING IS
 REVISED.
  
 4- PROVIDE COPY OF IMPACT FEES PAID
 RECEIPT.
  
 5- SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SECTION 106.1.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 6- A) WINDOWS IN SECOND FLOOR BEDROOMS
 NUMBERED 200 AND 2004 DON'T MEET THE
 REQUIREMENTS FOR EMERGENCY EGRESS. SEC.
 R10 2004 RESIDENTIAL CODE. (TYPICALLY 24
 SH WINDOWS DON'T MEET THE EGRESS
 REQUIREMENTS) REVISE AS REQUIRED TO SHOW
 COMPLIANCE WITH THIS SECTION.
 B) WINDOWS IN LIBRARY ROOM DON'T MEET
 THE EGRESS REQUIREMENTS EITHER, IF ROOF
 USED FOR SLEEPING PURPOSES. IF THIS ROOM
 IS NOT INTENDED FOR SLEEPING, THEN,
 ARCHITECT TO CLEARLY SPECIFY ON PLANS
 THAT ROOM IS NOT TO BE USED FOR SLEEPING
 PURPOSES.
  
 7- PROVIDE COMPLETE SECTION/DETAILS THRU
 INTERIOR STAIRS & EXTERIOR STAIRS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 AND
 SEC. R311 2004 RESIDENTIAL CODE.
  
 8- A) SPECIFY ATTIC ACCESS SIZE IN MAIN
 HOUSE. SEC. R807 2004 RESIDENTIAL CODE.
 B) PROVIDE ATTIC ACCESS SIZE AND
 LOCATION IN 2ND FLOOR ABOVE GARAGE.
 SECTION R807 2004 RESIDENTIAL CODE.
 C) PROVIDE ATTIC ACCESS SIZE AND
 LOCATION AT 1ST FLOOR LIBRARY WING AREA.
 SEC. R807 2004 RESIDENTIAL CODE.
  
 9- PROVIDE SMOKE DETECTORS AS REQUIRED
 BY SEC. R313 2004 RESIDENTIAL CODE.
  
 10- SHEET A2.4: A) SPECIFY FIREBLOCKING
 MATERIAL AND LOCATION IN DETAIL 2.
 B) SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION IN CONCEALED SPACES IN ALL
 BUILDING SECTIONS & FIREPLACES/CHIMNEYS.
 SEC. R602.8 2004 RESIDENTIAL CODE.
  
 11- PROVIDE COMPLETE SECTIONS/DETAILS
 AND SPECS FOR CHIMNEYS CONSTRUCTION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 12- CLARIFY IF ATTIC VENTILATIONIS 4"
 CONTINUOUS OR IT'S SPACED THROUGHOUT
 ROOF. SPECIFY SIZE AND EXACT LOCATION.
 SEC. R806 2004 RESIDENTIAL CODE.
  
 13- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL (GO TO WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD FLORIDA PRODUCT APPROVALS.
 DADE COUNTY NOA'S ALONE ARE NOT
 AUTOMATICALLY STATEWIDE FLORIDA PRODUCT
 APPROVALS) AS REQ'D BY RULE 9B-72 FOR:
 A) FLAT ROOF. AND CLEARLY SPECIFY
 APPROVED ASSEMBLY TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH GENERAL
 LIMITATION #7 OR #9.
 B) ALL TRUSS ANCHORS AND STRUCTURAL
 CONNECTORS SPECIFIED ON PLANS.
 C) ENTRY DOOR.
 D) ROOF TILE.
 E) PRECAST LINTELS.
 F) FRENCH DOORS WITH AND WITHOUT
 SIDELITES. AND CLEARLY IDENTIFY GLASS
 TYPE TO BE USED TO VERIFY COMPLIANCE
 WITH CALCULATED DESIGN PRESSURES.
 ***NOTE: 3 DIFFERENT DADE COUNTY NOA'S
 WERE SUBMITTED. SUBMIT ONLY THE ONE THAT
 IS GOING TO BE INSTALLED.
 G) FIXED WINDOWS.
 H) LARGE FIXED WINDOWS AS SPECIFIED
 FOR WINDOWS MARKED C AND D IN WINDOW
 SCHEDULE. ***NOTE: SEE DADE COUNTY NOA
 FOR MAXIMUM SIZE LIMITATIONS.
 I) SINGLE HUNG WINDOWS.
 J) WINDOW MULLIONS.
 K) GARAGE DOORS. ***NOTE: SEE
 ELEVATIONS FOR TYPE OF DOORS SHOWN.
  
 14- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING (TYP. DONE WITH THE
 STANDARD REVIEW STAMP) ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004
  
  
 15- EXTERIOR ELEVATIONS: SHOW HEIGHT OF
 CHIMNEYS TO VERIFY COMPLIANCE WITH
 CLEARANCES SHOWN ON FIGURE R1003.1 OF
 2004 RESIDENTIAL CODE.
  
 16- BALCONY GUARDRAILS TO SHOW
 CLEARANCES TO VERIFY COMPLIANCE WITH
 SEC. R312 2004 RESIDENTIAL CODE.
  
 17-A) PROVIDE SECTION/DETAILS FOR DOORS
 AND WINDOWS STRUCTURAL BUCKS. SEE
 PRODUCT APPROVAL FOR REQUIRED SIZE AND
 SEC. R613.6.2 2004 RESIDENTIAL CODE FOR
 PROPER INSTALLATION.
 B) PROVIDE GARAGE DOOR STRUCTURAL
 BUCK DETAIL. SECTION 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 18- SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY WWM SUPPORTS AS REQUIRED BY SEC.
 R506.2.4 EXCEPTION #2 OF 2004
 RESIDENTIAL CODE.
  
 19- DRAWING S-2: A) SPECIFY SPACING FOR
 2"X4" BLOCKING TO SUPPORT WINDOW IN WOOD
 FRAMED ARCH DETAIL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 B) REVISE ELEVATION FOR PRECAST
 LINTEL PCL7. SEE PLANS FOR SIZE OF
 GARAGE DOOR.
  
 20- DRAWING S-3: A) LAYOUT SHOWN BY
 STAIRCASE DOESN'T MATCH ARCHITECTURAL
 PLANS. REVISE AS REQUIRED.
 B) DETAIL 03/S3 DOESN'T WORK. SEE
 ARCHITECTURAL PLANS. THERE IS NOT
 CONCRETE BLOCK WALL ON SECOND FLOOR.
 REVISE AS REQUIRED.
 C) CLARIFY WHY SPECIFYING ONLY ONE
 2X8 LEDGER TO SUPPORT 2ND FLOOR TRUSSES,
 WHILE DETAIL 04/S3 SHOWS DOUBLE LEDGER
 TO SUPPORT ROOF JACKS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 D) FLAT ROOF ABOVE LIBRARY AND GUEST
 ROOM DON'T MATCH ARCHITECTURAL PLANS.
 REVISE AS REQUIRED.
 E) DETAIL 05/S3: HOW ARE ANCHOR BOLTS
 EMBEDED 6". SEE SLAB THICKNESS, COLUMN
 PLATE SIZE AND CB7 SIZE. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 F) BEAMS SPECIFIED ON SECOND FLOOR
 PLAN DON'T MATCH THOSE SHON ON SECTIONS
 AND DETAILS. EG: SEE SECTION B ON SHEET
 S-5. REVISE ALL BEAMS SHOWN IN FRAMING
 PLANS TO MATCH DETAILS.
 G) PROVIDE SECTION DETAIL THRU
 EXTERIOR WALL ABOVE COVERED PATIO TO
 SHOW INSTALLATION OF PCL6, TB6 AND
 BALCONY CONCRETE SLAB. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 21- PROVIDE COMPLETE WALL SECTION THRU
 INTERIOR METAL STUDS BEARING WALLS. SHOW
 HOW ARE FLOOR TRUSSES SUPPORTED AND
 FASTENED. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 22- MISSING FOOTING FOR STAIRS AT GARAGE
 AREA. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 23- PROVIDE COMPLETE DETAILS FOR STEEL
 COLUMNS. MISSING TOP CONNECTION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 24- PROVIDE SOIL TEST REPORT.
  
 25- PROVIDE SURVEY FOR PROPOSED LAYOUT.
 OLD LAYOUT SUBMITTED IS NOT GOOD IF
 HOUSE IS DEMOLISHED. MAKE SURE NEW
 SURVEY HAS ORIGINAL SIGNATURE AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTES
  
 26- ENERGY CALCULATIONS: A) A/C AREA
 DOESN'T MATCH PLANS.
 B) ENGINEER WHO PREPARED ENERGY CALCS
 NEED TO PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES
 AND FLORIDA ADMINISTRATIVE CODE.
 C) SPECIFY HOW IS R5 INSULATION
 ACHIEVED FOR CONCRETE SLAB?.
 D) SPECIFY HOW IS R17 INSULATION
 ACHIEVED FOR EXTERIOR CONCRETE BLOCK
 WALLS?
 E) COMPLETE ALL INFORMATION ON TOP OF
 FORM.
 F) OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORM.
  
 27- STRUCTURAL DRAWINGS TO HAVE PROJECT
 CORRECT AND COMPLETE ADDRESS AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTES AND
 FLORIDA ADMINISTRATIVE CODE.
  
 28- PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS.
  
 29- DRAWING A3.1: LEGEND DON'T MATCH
 ELEVATIOONS. EG: SEE ITEM #009. CALLS
 FOR IMPACT RESISTANT DOORS. ELEVATION
 SHOWS CHIMNEY. REVISE ALL NOTES AS
 REQUIRED.
  
 30- DRAWING S-6: UPDATE CODES. SEE
 COMMENTS ON PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-23 Cont ID  
Sent By btrobaug Date 2006-05-23 Time 17:26 Rev Time 2.00
Received By btrobaug Date 2006-05-23 Time 17:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By dpalmer Date 2006-03-01 Time 07:33 Rev Time 0.00
Received By dpalmer Date 2006-02-28 Time 20:14 Sent To M
Notes
2006-03-01 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE ZONING NOTES AS THIS
 WILL AFFECT THE ELECTRICAL PLANS AND
 DESIGN OF REAR BLDG.
  
 2)NOTE: PLEASE SEE FS 471.025 WHICH
 REQUIRES A LEGAL "SIGNATURE" FOR
 ENGINEER, THIS APPEARS TO BE "INITIALS"?
 IF INDEED THIS IS THE LEGAL SIGNATURE ,
 PLEASE PROVIDE A SIGNED,DATED AND SEALED
 LETTER FOR VERIFICATION.
 PLEASE BE SURE LETTER IS PROPERLY
 NOTORIZED UNDER FS 117.05.
 ** PLEASE KNOW, THIS WILL BE PLACED IN
 OUR SIGNATURE FILE FOR ANY FUTURE
 REFERENCE.
  
 3)NOTE: PLEASE HAVE PLANS REFERENCE THE
 CURRENT NFPA-70 IN ADOPTION, WHICH IS
 THE 2002 EDITION.
  
 4)NOTE: PLEASE SEE SMOKE DETECTOR
 REQUIRED PER NFPA-72 11.5.1.1 IS TO BE
 LOCATED AT THE FIRST FLR, IN THE
 IMEDIATE VICINITY OF THE STAIRS LEADING
 TO THE FLOOR ABOVE. A SD SHOWN ON PLANS
 DOES NOT APPEAR TO BE ON FIRST FLR?
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 210.8A6, WHICH
 REQUIRES ALL COUNTERSPACE RECEPTS IN
 KITCHEN AREASTO BE GFI/GFI PROTECTED.
 PLEASE SEE REDLINED PLANS, PENINSULAR.
  
 6)NOTE: PLEASE SEE 210.52D FOR MISSING
 BATH GFI TO BE LOCATED WITHIN 3' OF LAV.
 REDLINED.
  
 7)NOTE: PLEASE SEE 210.11C3 WHICH
 REQUIRESDEDICATED BATH(S) CIRCUIT(S).
 PLEASE SEE THESE CAN NOT SERVE ANY OTHER
 AREAS,A ND MUST BE 20A AND #12 AWG.
 PLEASE ADJUST , AS PANEL SCHEDULES
 INDICATE 15A, #14 ETC.
  
 8)NOTE: PLEASE CORRELATE THE NUMBER OF
 A/C SYSTEMS ON PLANS WITH PANEL
 SCHEDULE.
 PLEASE SEE THREE SYSTEMS ARE SHOWN ON
 PANELS "A" AND "B", HOWEVER ONLY TWO
 SYSTEMS ARE SHOWN ON PLANS. THIS DOES
 NOT INCLUDE THE SYSTEM IN GARAGE /APT.
 ** PLEASE VERIFY IF ONLY TWO SYSTEMS IN
 MAINHOUSE THE HEAT/KW RATINGS OF
 HEATSTRIP. ONE SHOWS 5KW AND THE OTHER
 6KW WHICH SEEMS LOW FOR A HOUSE OF THIS
 SIZE. THIS IS ONLY A NOTE, AND DOES NOT
 APPLY FOR CODE COMPLIANCE.
  
 9)NOTE: PLEASE SEE CIRCUITING AS
 INDICATED ON PLANS AND PANEL SCHEDULES
 AND THE 2002 NEC 210.12B FOR ARC FAULT
 PROTECTION OF ALL "OUTLETS" IN BEDRMS.
 PLEASE KNOW THIS INCLUDES , SD'S
 RECEPTS, LTS, FANS ETC.
 PLEASE ADJUST ALL CIRCUITING ON PANEL
 SCHEDULES OR PLANS.
  
 10)NOTE: PLEASE LABEL ACCORDINGLY TO THE
 LOCATIONS AS NOTED ON PLANS. BEDRMS
 RECEPTS, MASTER BEDRM LTS ETC.
 ** PLEASE KNOW THIS MAY VERY WELL CHANGE
 AS THE WIRING OF STRUCTURE MAY VARY FROM
 ACTUAL PLANS AND REVISIONS CAN BE
 SUBMITTED AT A LATER DATE.215.5
  
 11)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN THE GENERAL LIGHTING LOADS
 @ 3W/PER SQ FT AS THESE RECESSED LTS GO
 ABOVE THE NORMAL LOADS.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 12)NOTE: PLEASE CORRELATE THE LOADS ON
 PANEL SCHEDULES AND LOAD CALCULATIONS.
 PLEASE SEE SOME LOADS ON PANELS WHICH
 ARE NOT ON LOAD CALCS. PLEASE ALSO CARRY
 THIS ADJUSTED LOAD THROUGH TO MAIN HOUSE
 SERVICE.
 (HEAT PUMP, JOCKEY PUMP.
  
 13)NOTE: PLEASE VERIFY THE SIZE OF THE
 GDO'S MOTORS AS BOTH MOTORS SEEM TO BE
 SHOWN ON THE SAME CIRCUIT?
 PLEASE SEE TABLE TO MOTORS AND MULTIPLE
 MOTORS ON A SINLGE BRANCH CIRCUIT.
 430.148
  
 14)NOTE: PLEAS NOTE AND VERIFY THE
 FOOTER STEEL ATDETACHED BLDG. PLEASE
 SEE 250.32 WHICH REQUIRES AN ATTACHMENT
 AT THE GARAGE LOCATION AND A CONNECTION
 TO ANY(METAL)CWP WHICH MAY NOT
 CONTINOUS FROM MAIN HOUSE.
  
 15)NOTE: PLEASE PROVIDE A MEANS OF
 CONTROLING THE EGRESS LT AT THE GARAGE
 APT FOR OUTSIDE STAIRS. THIS ADDITIONAL
 SWITCH SHOULD BE LOCATED AT THE BOTTOM
 OF THE STAIRS.
 210.70,LS 101 7.8
  
 16)NOTE: PLEASE SEE FAC 61G1-16.004
 WHICH REQUIRES THE ADDRESS/LOCAITON FO
 PROJECT ON PLANS.
 PLEASE SEE THE ADDRESS OF 214 10TH ST AS
 NOTED.
  
 17)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE CU-1 CIRCUITS AND ANY OTHER
 AS REDLINED ON PLANS.
  
 18)NOTE: PELASE VERIFY THE DINING RM
 CIRCUITS , AS AN RECEPTS SHALL BE ON ONE
 OR MORE OF THE SMALL APPLIANCE CIRCUITS
 PROVIDED.
 PLEASE SEE 210.52B1, ONE CIRCUIT DOES
 NOT SEEM TO BE ON A SM APPL CIRCUIT.
  
 19)NOTE: PLEASE CORRELATE ALL PANELS
 WITH RISER DIAGRAM. PLEASE SEE PANEL "C"
 AS 225A AND 150A,PANEL "B" AS 150A AND
 200A, ETC.
 PLEASE ADJUST. 215.5
  
 20)NOTE: PLEASE PROVIDE A MCB AT PANEL
 "C" AT GARAGE/ APT BLDG. THIS IS BEING
 CONSIDE DETACHED AS DEFINITIONS SET
 FORTH IN FBC 2004.
 225.31
  
 21)NOTE: PLEASE SEE NOTICE OF
 COMMENCEMENT AS SUBMITTED HAS SINCE
 EXPIRED AND A NEW RE-RRECORDED NOC WILL
 BE REQUIRED BEFORE PICKING UP PERMIT.
 PLEASE SEE FS 713.13(2) WHICH STATES, IF
 WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING SUCH NOC, THE NOC SHALL BECOME
 VOID.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS. (ZONING AS
 NOTED ETC).
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 SHEETS FOR REFERENCE.
 PLEASE BE SURE THIS IS DONE AS THIS WILL
 HELP TO ALLEAVIATE ANY DELAYS IN REVIEW
 TIMES AND PROCESSING PROJECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-02-28 00:00:00IN ELEC FOR REVIEW.
 NOTES WILL FOLLOW, AS REVIEW IS IN
 PROGRESS.

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2009-03-16 Cont ID  
Sent By lwagner Date 2009-03-16 Time 10:50 Rev Time 0.00
Received By lwagner Date 2009-03-13 Time 09:04 Sent To  
Notes
2009-03-13 09:16:39REVISION OK
  
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
  
  

Review Stop G GAS REVIEW
Rev No 5 Status N Date 2009-03-13 Cont ID  
Sent By lwagner Date 2009-03-13 Time 09:18 Rev Time 0.00
Received By lwagner Date 2009-03-05 Time 11:27 Sent To  
Notes
2009-03-06 15:33:00REFERENCE:
 FBC 2004 FUEL GAS
  
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2009-02-09 Cont ID  
Sent By kstevens Date 2009-02-09 Time 10:24 Rev Time 0.00
Received By kstevens Date 2009-02-09 Time 10:24 Sent To  
Notes
2009-02-09 10:25:05DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. SHT P2 GAS RISER DIAGRAM. THE FOLLOWING INFORMATION
 IS REQUIRED ON THE RISER DIAGRAM AND IN THE GAS SYSTEM
 CALCULATIONS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- NOT ALL LENGHTS ARE INDICATED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- NOT ALL PIPE
 SECTIONS SHOW THE MATERIAL.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- FURTHEST DISTANCE IS
 INDICATED AS 94 FEET, BUT ADDING UP ALL SHOWN LENGTH
 MEASUREMENTS IT APPEARS TO BE ABOUT 147 FEET. THIS CAN
 BE VERIFIED WHEN COMMENT 4(A) IS ADDRESSED. WHEN
 SCALING THE PIPING ON SHT P1 (1/4"-FT), IT APPEARS THAT
 SOME LENGTHS FROM THE METER TO THE POOL HEATERS ARE
 INCORRECT. PLEASE RECHECK THE LENGTHS. -- INDICATE THE
 DISTANCE FROM THE 2PSI REGULATOR TO THE FURTHEST FIRE
 PLACE.
  
 D. THE PIPING TO THE POOL HEATERS IS SHOWN AS 2PSI AS
 NO REGULATORS ARE SHOWN AT THE HEATERS. PLEASE CLARIFY
 THE INLET PRESSURE TO THE POOL HEATERS.
  
 E. A SHUT OFF VALVE IS REQUIRED DOWNSTREAM OF THE GAS
 REGULATORS. SECTION 409.4. -- ALSO A UNION IS REQUIRED
 DOWNSTREAM OF THE SHUTOFF VALVE FOR THE GAS REGULATOR
 FOR THE SUPPLY LINE FEEDING THE FIREPLACES/GRILL/DOUBLE
 BURNER.
  
 F. SUBMIT MANUF. SPECIFICATIONS FOR THE GAS PRESSURE
 REGULATORS. PLEASE INDICATE THE MODEL NUMBER OF EACH
 REGULATOR AS SOME REGULATORS ARE FOR INDIVIDUAL
 APPLIANCES AND SOME REGULATORS ARE FOR MULTIPLE
 APPLIANCES. SECTIONS 106.1.2 & 409.1.1. REGULATORS
 SHALL BE LISTED.
  
 G. SHT P1, PLASTIC PIPE SHALL BE INSTALLED OUTSIDE
 UNDERGROUND ONLY. PLASTIC PIPE SHALL NOT BE USED WITHIN
 OR UNDER ANY BUILDING OR SLAB PER SECTION 404.14.1.
 PLEASE INDICATE IF THE PIPING WILL BE UNDER ANY SLAB OR
 PORTION OF THE BUILDING. IF NOT INDICATE WHAT THE POOL
 DECK WILL BE BUILD OUT OF AS WELL AS THE AREA BETWEEN
 THE HOUSE AND THE GARAGE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-08-08 Cont ID  
Sent By jleech Date 2007-08-08 Time 08:22 Rev Time 0.00
Received By jleech Date 2007-08-08 Time 07:18 Sent To  
Notes
2007-08-08 08:22:54AS BUILT RISER DIAGRAM

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-06-06 Cont ID  
Sent By jleech Date 2006-06-06 Time 09:28 Rev Time 0.00
Received By jleech Date 2006-06-06 Time 09:28 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By jleech Date 2006-03-03 Time 12:05 Rev Time 0.00
Received By jleech Date 2006-03-03 Time 12:05 Sent To B
Notes
2006-03-03 00:00:00DENIED;
 1.PIPING UNDER THE SLAB MUST BE
 REMOVABLE FROM SLEEVED, SLEEVING MUST BE
 VENTED TO THE OUTSIDE. SLEEVES MUST HAVE
 A BENDING RADIUS LARGE ENOUGH TO ACEPT
 THE BENDING RADIUS OF AN APPROVED
 FLEXABLE PIPE.
 2.SHOW COMBUSTION AIR CALCULATIONS FOR
 WATER HEATER VENTS THRU WALL.
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 4.SHOW ALL CUT SECTIONS OF PIPE ON GAS
 RISER.
 5.NO PROVISIONS HAVE BEEN MADE FOR
 FUTURE POOL HEATER, GAS B-B-Q OR
 GENERATOR. IF ADDED LATER PIPE SIZES
 WILL CHANGE.
 6.PIPE SIZING IS NOT CORRECT. 1 1/4"
 GALV IS REQUIRED FROM METER TO "TEE" FOR
 FIREPLACES.
 GAS PLAN TEVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 09:13 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 09:13 Sent To G
Notes
2009-02-27 09:13:36TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-01-29 Cont ID  
Sent By adarroug Date 2009-01-29 Time 15:47 Rev Time 0.00
Received By adarroug Date 2009-01-29 Time 15:47 Sent To B
Notes
2009-01-29 15:47:36TO "JGIMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 09:19 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 09:19 Sent To Z
Notes
2008-03-07 09:20:09TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 09:36 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 09:36 Sent To M
Notes
2007-08-10 09:36:34TO TG'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-26 Cont ID  
Sent By adarroug Date 2007-07-26 Time 09:21 Rev Time 0.00
Received By adarroug Date 2007-07-26 Time 09:21 Sent To P
Notes
2007-07-26 09:21:55TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 15:27 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 15:27 Sent To M
Notes
2007-07-13 15:28:02TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 18:30 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 18:30 Sent To B
Notes
2006-09-23 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 13:46 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 13:46 Sent To P
Notes
2006-08-02 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 12:38 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 12:38 Sent To E
Notes
2006-05-23 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 14:31 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 14:30 Sent To Z
Notes
2006-05-15 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-20 Cont ID  
Sent By jgomez Date 2006-03-20 Time 17:07 Rev Time 0.00
Received By jgomez Date 2006-02-19 Time 12:42 Sent To  
Notes
2006-02-19 00:00:00TO "SFR" BOX "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-08-10 Cont ID  
Sent By tgordon Date 2007-08-10 Time 12:02 Rev Time 0.30
Received By tgordon Date 2007-08-10 Time 12:02 Sent To  
Notes
2007-08-10 12:03:18REVISION TO MECH. PLAN PAGE M1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-07-16 Cont ID  
Sent By tgordon Date 2007-07-16 Time 16:35 Rev Time 0.30
Received By tgordon Date 2007-07-16 Time 16:35 Sent To  
Notes
2007-07-16 16:41:21MECHANICAL REVISION
 *** DENIED ***
 1) REVISED MECHANICAL PLANS NEED TO BE SEALED BY THE
 ENGINEER J. DAVID PUGA, AS PLANS ON FILE ARE SEALED.
 PLEASE ALSO ENTER ENGINEERS INFORMATION IN THE TITLE
 BLOCK.
  
 2) NEED TO SHOW THE CFM'S OF ALL SUPPLY AIR GRILLS (SEE
 SECOND FLOOR PLAN).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-24 Cont ID  
Sent By tgordon Date 2006-05-24 Time 15:43 Rev Time 0.45
Received By tgordon Date 2006-05-24 Time 15:43 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By tgordon Date 2006-03-01 Time 16:12 Rev Time 1.15
Received By tgordon Date 2006-03-01 Time 16:12 Sent To P
Notes
2006-03-01 00:00:00*** DENIED ***
 1) THE DOOR FROM THE HALL TO THE LAUNDRY
 ROOM WILL NEED TO BE LOUVERED, OR THE
 RETURN AIR GRILL WILL NEED TO BE LARGER
 (A 5 TON SYSTEM REQUIRES ABOUGHT 725
 SQUARE INCHES).
  
 2) THE TRANSFER RETURN AIR DUCT (FLEX)
 IN MASTER SUITE IS TO SMALL FOR 605
 CFM'S SUPPLY AIR SEE NOTE #3 (A)&(C)
 EXCEPT.
  
 3)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 4) THE MASTER BATHROOM (HIS) NEEDS AN
 EXHUST FAN IN THE SINK AREA DUE TO THE
 SHOWER, PER 2004 FBC/M 402.3.1 .
  
 5) PLEASE CORRECT THE "KW" SIZES ON THE
 A/C EQUIPMENT SCHEDULE ON PAGE M3 TO
 KILOWATTS.
  
 6) PLEASE SHOW THE SENSIBLE COOLING
 BTU'S ON THE A/C EQUIPMENT SCHEDULE.
  
 7) PLEASE PROVIDE THE MANUFACTURE'S
 SPECIFICATION SHEETS SHOWING THE TOTAL,
 SENSIBLE, AND LATENT COOLING BTU'S AS
 THE LATENT COOLING BTU'S ON THEMANUAL
 J APPEAR VERY HIGH.
  
 8) PLEASE SHOW THE COPPER LINE SIZES ON
 THE A/C EQUIPMENT SCHEDULE.
  
 9) BOOSTER FANS ARE NOT PERMITTED IN
 DRYER VENTS AS THEY VOID THE DRYER
 WARRANTY PLEASE CORRECT.
  
 10) PLEASE SUBMITT MANUFACTURE'S SPEC'S
 AND INSTALLATION INSTRUCTIONS FOR EACH
 GAS FIRE PLACE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-03-13 Cont ID  
Sent By lwagner Date 2009-03-13 Time 09:20 Rev Time 0.00
Received By lwagner Date 2009-03-13 Time 09:20 Sent To G
Notes
2009-03-13 09:21:39REVISION OK

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-02-09 Cont ID  
Sent By kstevens Date 2009-02-09 Time 08:56 Rev Time 0.00
Received By kstevens Date 2009-02-09 Time 08:56 Sent To  
Notes
2009-02-09 10:23:23DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P1, P2, P3 & P4 THE SIGNATURE OF THE ENGINEER
 OF RECORD DOES NOT MATCH THE SIGNATURE ON THE PLANS ON
 FILE FOR PUBLIC RECORD. PER FAC 61G15-23.002(1)(2) THE
 PROFESSIONAL ENGINEER SHALL SIGN HIS NAME. IT APPEARS
 THAT INITIALS HAVE BEEN USED TO SIGN THE REVISION
 SHEETS. PLEASE AFFIX THE SIGNATURE ON EACH SHEET. FS
 471.025.
  
 2. SHT P2 WATER RISER DIAGRAM. AIR CHAMBERS ARE NOT
 APPROVED. SECTION 604.9. WATER HAMMER ARRESTORS SHALL
 BE INSTALLED ON ALL QUICK CLOSING VALVES, (ICE MAKERS,
 DISH WASHERS, OR WASH MACHINES). IF WATER HAMMER
 ARRESTORS ARE INSTALLED, THEY SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE CEILING.
 PDI-WH 201.
  
 3. SHT P2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 CHANGES SHOWN ON THE FLOOR PLAN. PLEASE CORRECT THE
 FOLLOWING:
 A. THE FIRST FITTING AND PIPING AS THE SANITARY ENTERS
 THE BUILDING WAS DELETED ON THE FLOOR PLAN BUT IS STILL
 SHOWN ON THE RISER DIAGRAM.
 B. THE PIPING TO THE KITCHEN SINK WAS CHANGED ON THE
 FLOOR PLAN BUT NOT ON THE RISER DIAGRAM.
 C. THE LAV ARM IN THE TOILET ROOM BY THE WASH MACHINE
 DOES NOT REFLECT THE FLOOR PLAN.
 D. THE 3" WASTE LINE UP DOWNSTREAM OF THE LAST BATHROOM
 SHOWN ON THE FLOOR PLAN IS NOT SHOWN ON THE RISER
 DIAGRAM.
 SECTIONS 106.1.1 & 701.1.
  
 4. SHT P2 GAS RISER DIAGRAM. THE FOLLOWING INFORMATION
 IS REQUIRED ON THE RISER DIAGRAM AND IN THE GAS SYSTEM
 CALCULATIONS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- NOT ALL LENGHTS ARE INDICATED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- NOT ALL PIPE
 SECTIONS SHOW THE MATERIAL.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- FURTHEST DISTANCE IS
 INDICATED AS 94 FEET, BUT ADDING UP ALL SHOWN LENGTH
 MEASUREMENTS IT APPEARS TO BE ABOUT 147 FEET. THIS CAN
 BE VERIFIED WHEN COMMENT 4(A) IS ADDRESSED. WHEN
 SCALING THE PIPING ON SHT P1 (1/4"-FT), IT APPEARS THAT
 SOME LENGTHS FROM THE METER TO THE POOL HEATERS ARE
 INCORRECT. PLEASE RECHECK THE LENGTHS. -- INDICATE THE
 DISTANCE FROM THE 2PSI REGULATOR TO THE FURTHEST FIRE
 PLACE.
  
 D. THE PIPING TO THE POOL HEATERS IS SHOWN AS 2PSI AS
 NO REGULATORS ARE SHOWN AT THE HEATERS. PLEASE CLARIFY
 THE INLET PRESSURE TO THE POOL HEATERS.
  
 E. A SHUT OFF VALVE IS REQUIRED DOWNSTREAM OF THE GAS
 REGULATORS. SECTION 409.4. -- ALSO A UNION IS REQUIRED
 DOWNSTREAM OF THE SHUTOFF VALVE FOR THE GAS REGULATOR
 FOR THE SUPPLY LINE FEEDING THE FIREPLACES/GRILL/DOUBLE
 BURNER.
  
 F. SUBMIT MANUF. SPECIFICATIONS FOR THE GAS PRESSURE
 REGULATORS. PLEASE INDICATE THE MODEL NUMBER OF EACH
 REGULATOR AS SOME REGULATORS ARE FOR INDIVIDUAL
 APPLIANCES AND SOME REGULATORS ARE FOR MULTIPLE
 APPLIANCES. SECTIONS 106.1.2 & 409.1.1. REGULATORS
 SHALL BE LISTED.
  
 G. SHT P1, PLASTIC PIPE SHALL BE INSTALLED OUTSIDE
 UNDERGROUND ONLY. PLASTIC PIPE SHALL NOT BE USED WITHIN
 OR UNDER ANY BUILDING OR SLAB PER SECTION 404.14.1.
 PLEASE INDICATE IF THE PIPING WILL BE UNDER ANY SLAB OR
 PORTION OF THE BUILDING. IF NOT INDICATE WHAT THE POOL
 DECK WILL BE BUILD OUT OF AS WELL AS THE AREA BETWEEN
 THE HOUSE AND THE GARAGE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-08-21 Cont ID  
Sent By jleech Date 2006-08-21 Time 07:26 Rev Time 0.00
Received By jleech Date 2006-08-21 Time 07:26 Sent To B
Notes
2006-08-21 00:00:00NEW SHEETS OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-06 Cont ID  
Sent By jleech Date 2006-06-06 Time 09:28 Rev Time 0.00
Received By jleech Date 2006-06-06 Time 09:28 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By jleech Date 2006-03-03 Time 11:55 Rev Time 0.00
Received By jleech Date 2006-03-03 Time 11:55 Sent To B
Notes
2006-03-03 00:00:00DENIED;
 1.AUTOMATIC CLOTHES WASHER IS MISSING
 FROM RISER DIAGRAM.
 2.PLEASE MAKE A NOTE ON WATER SERVICE
 THAT A BACKFLOW PREVENTOR IS REQUIRED AT
 THE WATER METER PER CITY UTILITIES
 DEPARTMENT (WATER).
 3.GENERAL PLUMBING NOTE # 9. PVC PIPE IS
 NOT LISTED IN YOUR NOTES BUT IS LISTED
 IN TABLE 702.2. IF PVC IS EXCEPTABLE
 PLEASE LIST IN NOTE. IF NOT PLEASE LIST
 IN NOTES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2008-04-10 Cont ID  
Sent By choops Date 2008-04-10 Time 09:59 Rev Time 0.00
Received By choops Date 2008-04-10 Time 09:59 Sent To PC
Notes
2008-04-10 10:00:27***APPROVED - REVISION - REMOVING LOW WALL/WATER
 FEATURE AT FRONT OF PROPERTY, TWO (2) COLUMNS AT A
 HEIGHT OF 3 FT. TO REMAIN.***
  

Review Stop Z ZONING
Rev No 3 Status F Date 2008-03-10 Cont ID  
Sent By choops Date 2008-03-10 Time 13:55 Rev Time 0.00
Received By choops Date 2008-03-10 Time 13:55 Sent To B
Notes
2008-03-10 13:58:29***FAILED - REVISION - REMOVING LOW WALL/WATER FEATURE
 AT FRONT OF PROPERTY, TWO (2) COLUMNS AT A HEIGHT OF 3
 FT. TO REMAIN.***
  
  
 1)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS/COLUMNS/SHRUBS WHICH RESTRICT ACCESS.
  
 2)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED 3' COLUMNS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - JG

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-23 Cont ID  
Sent By mmclean Date 2006-05-23 Time 12:27 Rev Time 0.00
Received By mmclean Date 2006-05-23 Time 11:39 Sent To I
Notes
2006-05-23 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/GATE/WALL/FENCE.
 NOTE: THE GATE/WALL/FENCE MUST HAVE
 UTILITY EASEMENT APPROVAL FROM THE CITY
 OF WEST PALM UTILITY DEPT.
 NOTE: THE MAXIMUM HEIGHT ALLOWED WITHIN
 THE FIRST 25FT FRONT SETBACK IS 4FT AND
 BEYOND THE 25FT SETBACK 6FT.
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By mmclean Date 2006-02-27 Time 14:48 Rev Time 0.00
Received By mmclean Date 2006-02-27 Time 14:48 Sent To E
Notes
2006-02-27 00:00:00DENIED,
 1. NEED TO PROVIDE THE DIMENSION FOR THE
 PROPOSED DRIVEWAY (LENGTH & WIDTH)
 **MUST MAITAIN 1000SQ FT OR 75% OF
 LANDSCAPE WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK**
 2. THE ACCESSORY BUILDING (OUTBUILDING)
 CAN ONLY BE 900SQ FT TOTALLY. 2ND STORY
 CAN ONLY BE A TOTAL OF 450SQ FT, WHICH
 IS INCLUDED IN THE 900SQ FT TOTAL. NEED
 TO REDUCE STRUCTURE.
 3. NEED TO REMOVE THE BREEZWAY ATTACHED
 TO ACCESSORY STRUCTURE INORDER TO MEET
 THE SETBACK FOR ACCESSORY STRUCTURE.
 4. IF THE BREEZEWAY IS KEPT MUST MEET
 THE REAR SETBACK FOR THE PRINCIPLE
 STRUCUTRE OF 35FT IN REAR.
 5. NEED TO PROVIDE THE SIDE SETBACK OF
 THE ACCESSORY STRUCTURE (OUTBUILDING).
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/GATE/WALL/FENCE.
 NOTE: THE GATE/WALL/FENCE MUST HAVE
 UTILITY EASEMENT APPROVAL FROM THE CITY
 OF WEST PALM UTILITY DEPT.
 NOTE: THE MAXIMUM HEIGHT ALLOWED WITHIN
 THE FIRST 25FT FRONT SETBACK IS 4FT AND
 BEYOND THE 25FT SETBACK 6FT.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720