Plan Review Details - Permit 06020737
Plan Review Stops For Permit 06020737
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-17 Cont ID  
Sent By mjacobs Date 2006-02-17 Time 12:10 Rev Time 0.50
Received By mjacobs Date 2006-02-17 Time 11:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-16 Cont ID  
Sent By mjacobs Date 2006-02-16 Time 11:47 Rev Time 0.50
Received By mjacobs Date 2006-02-16 Time 11:24 Sent To PC
Notes
2006-02-16 00:00:001) THE PRODUCT APPROVAL IS INCOMPLETE.
 THE FIRST 8 PAGES WHICH CONTAIN THE
 DIFFERENT TYPES OF MATERIALS IS
 REEQUIRED ALSO, CHOOSE ONE OF THE
 APPROVED ASSEMBLIES WHICH WILL BE USED
 FOR THIS JOB.
  
 2) FBC 1609.6.5 IF THE SYSTEM SELECTED
 FROM THE SUBMITTED FLAT ROOF PRODUCT
 APPROVAL NOA HAS A MAXIMUM DESIGN
 PRESSURE OF LESS THAN -89 PSF AND CITES
 GENERAL LIMITATION #9 .GENERAL
 LIMITATION #9 PROHIBITS RATIONAL
 ANALYSIS OR EXTRAPOLATION TO ENHANCE THE
 UPLIFT PRESSURE AT PERIMETER AND CORNER
 AREAS BY REDUCING THE FASTENER SPACING
 IN THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS). EACH PRODUCT NEEDS
 THE STATE COVER SHEETS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-16 Cont ID  
Sent By mjacobs Date 2006-02-16 Time 11:24 Rev Time 0.00
Received By mjacobs Date 2006-02-16 Time 11:24 Sent To  
Notes
***NONE***