Plan Review Details - Permit 06020706
Plan Review Stops For Permit 06020706
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-20 Cont ID  
Sent By rmcdouga Date 2006-06-20 Time 08:40 Rev Time 0.00
Received By rmcdouga Date 2006-06-20 Time 08:40 Sent To  
Notes
2006-06-20 00:00:00NEW PAGE 2.1 IS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-24 Cont ID  
Sent By rmcdouga Date 2006-04-24 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2006-04-24 Time 14:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By rmcdouga Date 2006-03-06 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2006-03-06 Time 08:02 Sent To  
Notes
2006-03-06 00:00:00DENIED
  
 1) SPECIFY THE LOCATION OF FIRE OR
 FIRE/SMOKE RATED WALLS. SEE FBC 706.
  
 2) ONE HOUR FIRE TENANT SEPARATION IS
 REQUIRED FROM ADJACENT TENANTS. SPECIFY
 LOCATIONS WITH DASHED OR DOTTED LINES
 FOR CLARITY. SEE FBC 708.
  
 3) SPECIFY THE REQUIRED CLASS OF WALL
 AND CEILING FINISHES PER FBC 803.
  
 4) THE SINK AND CABINETS ARE REQUIRED TO
 COMPLY WITH ACCESSIBILITY REQUIREMENTS.
 SEE FBC 11-4.24 AND 11-4.32.4. PROVIDE
 ELEVATIONS.
  
 5)11-4.1.6(2) DUTY TO PROVIDE
 AN ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 SUBMIT A COST BREAKDOWN SHOWING THE 20%
 OF ALTERATION COST TO BE SPENT ON
 ACCESSIBILITY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-22 Cont ID  
Sent By jleahy Date 2006-06-22 Time 07:42 Rev Time 1.15
Received By jleahy Date 2006-06-22 Time 07:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-21 Cont ID  
Sent By jleahy Date 2006-04-21 Time 08:29 Rev Time 0.45
Received By jleahy Date 2006-04-21 Time 08:29 Sent To  
Notes
2006-04-21 00:00:00NO SIGNATURE FOR PLANS.
  
 LIGHTING TO BE INSTALLED PER CHAPTER 13
 OF THE 2004 FBC.
  
 JAKE
  
 644-7291

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-23 Cont ID  
Sent By jleahy Date 2006-02-23 Time 20:57 Rev Time 1.00
Received By jleahy Date 2006-02-23 Time 20:57 Sent To  
Notes
2006-02-23 00:00:00NEED TO SHOW BRANCH CIRCUIT NUMBERS FOR
 THE OUTLETS AND LIGHTS (NEW)
  
 PANEL SCHEDULE DOES NOT REFLECT LOADS
 SHOWN ON DRAWINGS. LIGHTS AND OUTLETS.
  
 NO LOW VOLTAGE SYSTEMS SHOWN NEW
 TELEPHONE COMPUTERS, ECT. ECT.
 NO ROUGH INSPECTION WITHOUT PLANS FOR
 LOW VOLTAGE.
  
 THERE IS NO SIGNATURE OF THE RESONSIBLE
 PARTY FOR THESE DRAWINGS.
  
 NEED TO SHOW THE LOCATION OF THE PANEL
 AND METER AND SERVICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 10:00 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 09:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-25 Cont ID  
Sent By mwennerg Date 2006-04-25 Time 11:15 Rev Time 0.00
Received By mwennerg Date 2006-04-25 Time 11:15 Sent To  
Notes
2006-04-25 00:00:00SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER/FIRE ALARM
 REMODEL IF APPLICABLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-02-17 Cont ID  
Sent By mwennerg Date 2006-02-17 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2006-02-17 Time 14:12 Sent To  
Notes
2006-02-17 00:00:00******PASSED******
  
 1) GENERALLY, IT WOULD APPEAR THAT THE
 MOST ACURATE OCCUPANCY CLASSIFICATION
 FOR THIS SPACE IS BUSINESS. THE
 CONFERENCE ROOM IS INCIDENTAL. OCCUPANT
 LOAD WAS CALCULATED AS BUSINESS.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHER IS
 REQUIRED. ACCESS TO AN EXTINGUISHER
 SHALL NOT EXCEED 75' TRAVEL DISTANCE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 10:26 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 10:26 Sent To M
Notes
2006-09-12 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-25 Cont ID  
Sent By adarroug Date 2006-08-25 Time 10:31 Rev Time 0.00
Received By adarroug Date 2006-08-25 Time 10:31 Sent To M
Notes
2006-08-25 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 13:37 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 13:37 Sent To  
Notes
2006-06-16 00:00:00TO "BOB"#2
2006-06-12 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 12:36 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 12:36 Sent To  
Notes
2006-04-19 00:00:00TO "BOB"#16
2006-04-17 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By rmcdouga Date 2006-03-06 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2006-02-17 Time 10:02 Sent To  
Notes
2006-02-17 00:00:00TO "BOB"#10

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 16:31 Rev Time 0.25
Received By tgordon Date 2006-09-12 Time 16:31 Sent To  
Notes
2006-09-12 00:00:00RVVISION TO MECH. PLANS PAGE 3-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-09-01 Cont ID  
Sent By tgordon Date 2006-09-01 Time 15:33 Rev Time 0.45
Received By tgordon Date 2006-09-01 Time 15:33 Sent To  
Notes
2006-09-01 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) PLEASE SHOW CFM'S AT SUPPLY AIR
 GRILLS, WITHOUT THAT INFOMATION WE CAN
 NOT TELL IF THE RETURN AIR DUCTS ARE THE
 RIGHT SIZE. AND PLEASE CORRECT RETURN
 AIR DUCT SIZES IF NEEDED.
  
 2) PLEASE SHOW HOW THE RETURN AIR IS
 GETTING BACK TO THE AIR HANDLER (DUCT
 SIZE).
  
 3) PLEASE SEE HIGH LIGHTS ON MECHANICAL
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-06-20 Cont ID  
Sent By tgordon Date 2006-06-20 Time 15:38 Rev Time 0.15
Received By tgordon Date 2006-06-20 Time 15:38 Sent To  
Notes
2006-06-20 00:00:00MECH. PLANS PASSED ON 4-19-06.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-19 Cont ID  
Sent By tgordon Date 2006-04-19 Time 16:01 Rev Time 0.20
Received By tgordon Date 2006-04-19 Time 16:01 Sent To  
Notes
2006-04-19 00:00:00*** PROVISO ***
 1) REVISED MECHANICAL PLANS TO BE
 SUBMITTED SHOWING HOW BALANCED RETURN
 AIR WAS INSTALLED BEFORE ROUGH
 MECHANICAL INSPECTION.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-17 Cont ID  
Sent By tgordon Date 2006-02-17 Time 11:53 Rev Time 0.30
Received By tgordon Date 2006-02-17 Time 11:53 Sent To  
Notes
2006-02-17 00:00:00*** DENIED ***
 1) EACH OFFICE WITH A DOOR WILL REQUIRE
 BALANCED RETURN AIR, PER 2004 FBC/M
 601.4 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-19 Cont ID  
Sent By jleech Date 2006-06-19 Time 13:51 Rev Time 0.00
Received By jleech Date 2006-06-19 Time 13:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-25 Cont ID  
Sent By jleech Date 2006-04-25 Time 07:03 Rev Time 0.00
Received By jleech Date 2006-04-25 Time 07:03 Sent To  
Notes
2006-04-25 00:00:00DENIED;
 BREAK SINK IS REQUIRED TO HAVE A FRONTAL
 APPROACH. FBC-2004 CHAPTER 11 SEC.
 11-4.24.3. KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINK. SHOW
 DETAIL OF CABINETS WITH DOORS, AND BASS
 OF CABINET REMOVED. CHANGE THE CLEAR
 FLOOR SPACE FROM SIDE APPROACH TO
 FRONTAL APPROACH ON PAGE 2.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By jleech Date 2006-03-01 Time 15:08 Rev Time 0.00
Received By jleech Date 2006-03-01 Time 15:08 Sent To  
Notes
2006-03-01 00:00:00DENIED;
 1.PAGE 2.1 SOUTH EAST SIDE NOTE
 "EXISTING PLUMBING" NOT SHOWN ON DEMO.
 SHEET. PLEASE SHOW WERE PLUMBING TIES
 INTO BOTH SANITARY AND WATER.
 2.BREAK SINK TO COMPLY WITH FBC-2004
 CHAPTER 11 SEWC.11-4.24.1 THRU 11-4.24.7
 SHOW DETAIL ON PLANS. SHOW ALL
 MEASUREMENTS REQUIRED AND NOTES FOR RAPS
 AND FAUCET HANDLES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695