Plan Review Details - Permit 06020656
Plan Review Stops For Permit 06020656
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-06-28 Cont ID  
Sent By lmartine Date 2007-06-28 Time 19:10 Rev Time 0.00
Received By lmartine Date 2007-06-28 Time 19:10 Sent To  
Notes
2007-06-28 19:10:28RESTAMP

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-06-22 Cont ID  
Sent By lmartine Date 2007-06-22 Time 13:22 Rev Time 0.00
Received By lmartine Date 2007-06-22 Time 13:22 Sent To  
Notes
2007-06-22 13:25:18RESTAMP FAILED , ELECTRIC, MECHANICAL, AND PRODUCT
 APPROVALS ARE NOT THE SAME AS MOST CURRENT FILED .
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-11-20 Cont ID  
Sent By alange Date 2006-11-20 Time 13:51 Rev Time 0.00
Received By alange Date 2006-11-20 Time 13:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 16:08 Rev Time 0.00
Received By alange Date 2006-10-23 Time 16:08 Sent To  
Notes
2006-10-23 16:09:28DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (5 61)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-14 Cont ID  
Sent By alange Date 2006-06-14 Time 09:52 Rev Time 1.50
Received By alange Date 2006-06-14 Time 09:52 Sent To  
Notes
2006-06-14 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (5 61)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-15 Cont ID  
Sent By alange Date 2006-03-15 Time 11:36 Rev Time 2.50
Received By alange Date 2006-03-15 Time 11:36 Sent To  
Notes
2006-03-15 00:00:00 
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $127,891.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.ALSO COMPLETE FORM WITH
 ALL SIGNATURES REQUIRED.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 LINTELS, STRAPS AND TIEDOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 9. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.CHECK ALL CODE
 SECTIONS MENTIONED ON PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-30 Cont ID  
Sent By btrobaug Date 2006-05-30 Time 14:45 Rev Time 0.50
Received By btrobaug Date 2006-05-30 Time 14:26 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-21 Cont ID  
Sent By dpalmer Date 2006-02-21 Time 07:45 Rev Time 0.00
Received By dpalmer Date 2006-02-21 Time 07:05 Sent To Z
Notes
2006-02-21 00:00:00******** UNSAT ************
  
  
 1)NOTE: PLEASE SEE PLANS REFERENCE THE
 2001 FBC AND 2001 SBC.
 PLEASE KNOW, THE SBC WENT OUT OF USE TEO
 CODE CYCLES AGO. PLEASE ALSO KNOW, AS OF
 OCT 1ST, 2005 THE NEW FBC IS 2004
 PLEASE ALSO SEE PLANS INDICATE"PALM
 BEACH COUNTY" WHERE THE JOB IS LOCATED
 IN THE CITY OF WEST PALM BEACH.
  
 2)NOTE: PLEASE SEE MISSING KITCHEN GFI'S
 PER 210.52C1
  
 3)NOTE: PLEASE SEE MISSING KITCHEN
 PENINSULAR GFI PER 210.52C3
  
 4)NOTE: PLEASE SEE MISSING DEDICATED
 BATH CIRCUITS PER 210.52D,210.11C3, MUST
 BE 20A AND #12 MIN.
  
 5)NOTE: PLEASE SEE MISSING AIC RATING
 FOR MAINS AND AND SERVICE EQUIPMENT.
 110.9,215.5
  
 6)NOTE: PLEASE SEE 424.3B FOR OCP FOR
 AHU HEAT. PLEASE ALSO VERIFY THE SIZE OF
 THE HEAT FOR THIS SIZE OF A DWELLING
 UNIT. 5KW SEEMS LOW.
 PLEASE SEE 50A OCP IS HIGH FOR 5KW .
  
 7)NOTE: PLEASE SEE NUMEROUS 15A CIRCUITS
 ON PANEL SCHEDULE WHICH EXCEED THE
 BRANCH CIRCUIT RATING. PLEASE SEE 1440
 VA PER 15A CIRCUITS, 1920VA FOR 20A
 BRANCH CIRCUITS.
 240.4,310.16,ETC.
  
 8)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 WITH RESPECT TO THE CONSTRUCTION
 VALUATION. PER 108.3 FBC ADMINISTRATIVE
 SECTION ADOPTED INTO THE LOCAL
 AMENDMENTS.
  
 ** PLEASEBE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 13:29 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 13:29 Sent To B
Notes
2007-06-27 13:30:32TO "LMARTINEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 13:02 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 13:02 Sent To B
Notes
2007-05-29 13:03:18TO "LMARTINEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-05-16 Cont ID  
Sent By adarroug Date 2007-05-16 Time 09:43 Rev Time 0.00
Received By adarroug Date 2007-05-16 Time 09:43 Sent To M
Notes
2007-05-16 09:43:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 10:14 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 10:14 Sent To B
Notes
2006-11-17 10:14:36TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 15:50 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 15:50 Sent To Z
Notes
2006-11-13 15:53:05TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 11:38 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 11:38 Sent To B
Notes
2006-10-23 11:38:40TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-13 Cont ID  
Sent By adarroug Date 2006-10-13 Time 09:50 Rev Time 0.00
Received By adarroug Date 2006-10-13 Time 09:50 Sent To Z
Notes
2006-10-13 09:50:38TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 10:57 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 10:57 Sent To E
Notes
2006-05-26 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 11:56 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 11:55 Sent To Z
Notes
2006-05-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-15 Cont ID  
Sent By alange Date 2006-03-15 Time 11:47 Rev Time 0.00
Received By alange Date 2006-02-16 Time 10:25 Sent To  
Notes
2006-02-16 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-17 Cont ID  
Sent By tgordon Date 2007-05-17 Time 11:17 Rev Time 0.30
Received By tgordon Date 2007-05-17 Time 11:17 Sent To  
Notes
2007-05-17 11:19:08*** PROVISO ***
 1) CLOTHES DRYER VENT TERMINATION MUST NOT DISCHARGE
 NEAR A/C CONDENSER UNIT, PER 2004 FBC/M 501.2 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-31 Cont ID  
Sent By tgordon Date 2006-05-31 Time 08:26 Rev Time 0.30
Received By tgordon Date 2006-05-31 Time 08:26 Sent To P
Notes
2006-05-31 00:00:00*** PROVISO ***
 1) CLOTHES DRYER VENT TERMINATION MUST
 BE A MIN. OF 4 FT. FROM A/C CONDENSER
 UNIT, PER 2004 FBC/M 501.2 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-23 Cont ID  
Sent By tgordon Date 2006-02-23 Time 15:17 Rev Time 0.45
Received By tgordon Date 2006-02-23 Time 15:17 Sent To P
Notes
2006-02-23 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) ENERGY CALCULATIONS NEEED TO BE
 SIGNED BY PREPARER AND OWNER/AGENT.
  
 3) THE SEER ON THE ENERGY CAL'S. HAS
 BEEN ALTERED PLEASE DO NOT ALTER ON
 RESUBMITTED ENERGY CAL'S..
  
 4) NOTES ON PLANS REFER TO 2001 CODE
 PLEASE CHANGE TO 2004 CODE.
  
 5) NEED TO SHOW THE SIZE OF ALL THE
 RETURN AIR GRILLS NEAR THE AHU.
  
 6) ALL TRANSFER RETURN AIR DUCTS ARE TO
 SMALL, SEE NOTE #7.
  
 7) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-10 Cont ID  
Sent By jleech Date 2006-06-10 Time 08:44 Rev Time 0.00
Received By jleech Date 2006-06-10 Time 08:44 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-02-27 Cont ID  
Sent By jleech Date 2006-02-27 Time 07:12 Rev Time 0.00
Received By jleech Date 2006-02-27 Time 07:12 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-10-16 Cont ID  
Sent By mmclean Date 2006-10-16 Time 07:42 Rev Time 0.00
Received By mmclean Date 2006-10-16 Time 07:42 Sent To I
Notes
2006-11-16 07:45:30NOTE: THE PROPOSED A/C SHALL NOT BE CLOSER THAN 4.5FT
 FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-25 Cont ID  
Sent By mmclean Date 2006-05-25 Time 11:48 Rev Time 0.00
Received By mmclean Date 2006-05-25 Time 11:48 Sent To I
Notes
2006-05-25 00:00:00DENIED, 2ND REQUEST
 1. NEED TO PROVIDE THE DIMENSION OF THE
 PROPOSED DRIVEWAY (LENGTH & WIDTH)
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WHICHEVER IS LESS WITHIN THE
 25FT FRONT SETBACK
  
 2. THERE WAS NO SURVEY SUBMITTED IN THE
 RESUB PACKAGE.
 3. PLEASE PROVIDE TWO COPY OF THE SURVEY
 SHOWING THE PROPOSED WITH THE SETBACK OF
 THE STRUCTURE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-23 Cont ID  
Sent By mmclean Date 2006-02-23 Time 13:19 Rev Time 0.00
Received By mmclean Date 2006-02-23 Time 13:19 Sent To M
Notes
2006-02-23 00:00:00DENIED,
 1. NEED TO PROVIDE THE DIMENSION OF THE
 PROPOSED DRIVEWAY (LENGTH & WIDTH)
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WHICHEVER IS LESS WITHIN THE
 25FT FRONT SETBACK
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720