Plan Review Details - Permit 06020651
Plan Review Stops For Permit 06020651
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-17 Cont ID  
Sent By hpiskura Date 2006-08-17 Time 11:16 Rev Time 0.00
Received By hpiskura Date 2006-08-17 Time 11:15 Sent To  
Notes
2006-08-17 00:00:00REVISIONS DATED 7/10/06 AND 8/2/06 OK
 HHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-20 Cont ID  
Sent By shill Date 2006-06-20 Time 17:48 Rev Time 0.00
Received By shill Date 2006-06-20 Time 17:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By shill Date 2006-05-05 Time 09:57 Rev Time 0.00
Received By shill Date 2006-05-05 Time 09:57 Sent To  
Notes
2006-05-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)DECLARE OCCUPANT LOAD FBC1004.
  
 3.)DECLARE CONSTRUCTION TYPE FOR
 CURRENT CODE, FBC6.DECLARE MINIMUM
 REQUIRED FOR BUILDING HEIGHT AND AREA.
  
 4.)DECLARE NUMBER OF STORIES.YOU
 HAVE DECLARED A TYPE IV, SBC, BUT SOFFIT
 DETAIL SHOWS COMBUSTIBLE FRAMING.
  
 5.)THE SALES COUNTER IS TO COMPLY WITH
 FBC11-7.1.2(1), SHOW DIMENSIONS.
  
 6.)PROVIDE DIMENSION FOR TURNING
 RADIUS D8, ENLARGED BATHROOM DETAIL.
 ALSO PROVIDE WALL DIMENSIONS, NOT SHOWN
 ON THE FLOOR PLAN OR THE ENLARGED
 DETAIL.
  
 7.)THE VALUE APPEARS LOW.PROVIDE A
 BREAKDOWN OF COSTS, OR PROVIDE A MORE
 REALISTIC VALUE, OR AN ESTIMATE USING
 MARSHALL & SWIFT WILL BE DONE FOR YOU.
  
 8.)SEE FBC11-4.1.6(2).SHOW
 ACCESSIBLE ENTRANCE, ACCESSIBLE ROUTE,
 PARKING.THE ACCESSIBLE RESTROOM
 APPEARS TO BE EXISTING, IS THIS CORRECT?
  
 9.)DECLARE GOVERNING CODE.
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-24 Cont ID  
Sent By btrobaug Date 2006-08-24 Time 13:40 Rev Time 0.75
Received By btrobaug Date 2006-08-24 Time 13:31 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-17 Cont ID  
Sent By btrobaug Date 2006-08-17 Time 13:34 Rev Time 1.00
Received By btrobaug Date 2006-08-17 Time 11:33 Sent To B
Notes
2006-08-17 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE NOW LOADS ON PANEL "B",
 PLEASE SUBMIT SCHEDULE AND CALCULATION
 FOR SAME.
  
 2} THERE IS A SYMBOL TO THE RIGHT OF
 CKTS A14,16 & A18,20 THAT DOES NOT
 APPEAR ON THE LEGEND, BUT CONTAINS A 30
 AMP 3 WIRE,50 AMP 3 WIRE, 30 AMP 4 WIRE
 AND 50 AMP 4 WIRE CIRCUITS. PLEASE
 IDENTIFY PANEL AND CIRCUIT NUMBERS FOR
 THOSE CIRCUITS, THERE ARE NO 3 POLE 30
 AMP CIRCUITS IN THE PANELS SCHEDULES.
  
 3} CIRCUITS A4,16 AND A18,20 ARE
 SPECIFIED AT 220 VOLTS, THE SYSTEM IS
 120/208, WHAT IS THE SOURCE FOR 220 VOLT
 RECEPTACLES?
  
 4} CIRCUITS A 27,29,30,31,32,33 ARE
 SHOWN AS NO LOAD SPARES IN PANEL"A", BUT
 NOW SHOW AS RECEPTACLES ON THE PLAN.
 THEY ARE ALSO SHOWN AS EXISTING, BUT
 DID NOT APPEAR ON THE OIGINAL PLANS.
 PLEASE CLARIFY NEW OR EXISTING, ADD TO
 PANEL SCHEDULE, AND RECALCULATE THE LOAD
 PER 220.
  
 5} PLEASE INDICATE THE ADDED TRACK
 LIGHTING CIRCUIT(S) NUMBERS AND PANEL
 DESIGNATION, CALCULATE PER 220.12(B).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-28 Cont ID  
Sent By dpalmer Date 2006-06-28 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 19:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-12 Cont ID  
Sent By dpalmer Date 2006-06-12 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2006-06-12 Time 11:36 Sent To  
Notes
2006-06-12 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NO HAND DRAWN
 CHNAGES ARE PERMITTED ON PLAN UNLESS
 EACH AND EVERY CHANGE IS SIGNDED AND
 DATED BY THE ENGINEER OF RECORD.
 A PHOTO-COPY OF PLANS MAY BE DONE AND
 THEN HAVE THE DESIGNER RE-SIGN, DATE AND
 SEAL SHEETS. FS 481.221, 471.025
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE PROVIDE MIN CONTROLS REQUIRED,
 SCHEDULING, LOCATIONS OF DEVICES AND
 TIMED ON/OFF AND LOCATIONS AND TIME
 LIMITS OF OVER RIDES DEVICES.
 ** THIS WAS NOT IN FIRST REVIEW NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By dpalmer Date 2006-03-20 Time 18:54 Rev Time 0.00
Received By dpalmer Date 2006-03-20 Time 18:20 Sent To  
Notes
2006-03-20 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED, DATED AND SEALED BY THE
 ENGINEER OF RECORD, (CHANE ENGINEERING)
 FS 471.025
  
 2)NOTE: PLEASE COMPLETE CIRCUITING ON
 PLANS FOR NEW LIGHTING AND CORRELATE
 WITH THE SUBMITTED PANEL SCHEDULE.
 PLEASE CIRCUIT NEW EXIT/EM LTS TO LOCAL
 CIRCUIT. IT WAS NOTED THAT A NOTE IS
 SHOWN ON PLANS TO CONNECT TO LOCAL AREA
 LTS, HOWEVER THE CIRCUITS SHOULD BE
 SHOWN FOR THESE.700.12E
  
 3) NOTE: PLEASE CLARIFY IF THERE ARE NEW
 OR EXISTING SHOW WINDOW RECEPTS.?
 210.62, 220.12
 THESE WILL BE REQUIRED IF NOT EXISITNG.
  
 ** PLEASE SEE IF THERE ARE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS ARE REQUIRED TO BE
 SUBMITTED BACK FOR REFERENCE. THESE
 SHEETS SHOULD BE SEPARATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-17 Cont ID  
Sent By mwennerg Date 2006-08-17 Time 15:03 Rev Time 0.00
Received By mwennerg Date 2006-08-17 Time 15:03 Sent To  
Notes
2006-08-17 00:00:00REVISIONS DATED 7/10/06 AND 8/2/06.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-04-11 Cont ID  
Sent By mwennerg Date 2006-04-11 Time 10:44 Rev Time 0.00
Received By mwennerg Date 2006-04-11 Time 10:44 Sent To  
Notes
2006-04-11 00:00:00******APPROVED******
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEM REMODEL.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS TO
 BE MOUNTED AT DISTANCES NOT TO EXCEED
 75' TRAVEL DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-09 Cont ID  
Sent By adarroug Date 2006-08-18 Time 08:27 Rev Time 0.00
Received By btrobaug Date 2006-08-09 Time 08:27 Sent To PC
Notes
2006-08-09 00:00:00WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 17:42 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 17:42 Sent To E
Notes
2006-06-25 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 08:43 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 08:43 Sent To  
Notes
2006-06-12 00:00:00TO "COMM" BD#9
2006-05-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-08 Cont ID  
Sent By adarroug Date 2006-05-05 Time 11:13 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 18:50 Sent To  
Notes
2006-03-16 00:00:00TO "COMM" BD#15
2006-02-15 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-20 Cont ID  
Sent By hmoser Date 2006-03-20 Time 09:22 Rev Time 0.00
Received By hmoser Date 2006-03-20 Time 09:22 Sent To  
Notes
2006-03-20 00:00:00NO MECHANICAL REQUIRED.3/20/06 HM.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-05-06 Cont ID  
Sent By pschmitz Date 2006-05-06 Time 08:05 Rev Time 0.00
Received By pschmitz Date 2006-05-06 Time 08:05 Sent To  
Notes
2006-05-06 00:00:00ANY CHANGES TO BREAK ROOM SINK, SHALL
 COMPLY WITH SEC. 11.4-24