Plan Review Details - Permit 06020589
Plan Review Stops For Permit 06020589
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-05 Cont ID  
Sent By jgomez Date 2006-09-05 Time 17:53 Rev Time 2.00
Received By jgomez Date 2006-09-05 Time 17:53 Sent To M
Notes
2006-09-05 00:00:00BUILDING REVIEW PROVISO:
 1- PROVIDE COMPLETE AND CORRECT
 INFORMATION FOR STORM SHUTTERS UNDER A
 SEPARATE PERMIT AS AGREED ON WITH
 CONTRACTOR OVER THE PHONE.
  
 2- DADE COUNTY NOA SUBMITTED FOR
 ALUMINUM MULLIONS IS EXPIRED. PROVIDE
 CURRENT DADE COUNTY NOA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-29 Cont ID  
Sent By jgomez Date 2006-06-29 Time 18:44 Rev Time 2.00
Received By jgomez Date 2006-06-29 Time 18:44 Sent To  
Notes
2006-06-29 00:00:00PLAN BUILDING REVIEW 2ND CHECKLIST:
 1- NOC IS EXPIRED AFTER 90 DAYS OF BEEN
 RECORDED IF WORK IS NOT COMMENCED. NEED
 RE-RECORDED NOC. SEE SEC. 713.13. 9(2)
 OF FLORIDA STATUTES.
  
 2- PROVIDE SPECS/SECTION/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 3- PROVIDE PRODUCT APPROVAL FOR:
 A) SINGLE HUNG WINDOWS. DADE COUNTY NOA
 SUBMITTED IS EXPIRED AND IT DOESN'T
 MATCH THE NOA SUBMITTED TO OBTAIN THE
 FLORIDA PRODUCT APPROVAL. RESUBMIT.
 B) CONCRETE LINTELS. DADE COUNTY NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL
 WAS NOT SUBMITTED IN THIS PACKAGE. BUT,
 NEED TO GET ANOTHER PRODUCT APPROVAL
 BECAUSE DADE COUNTY NOA IS EXPIRED
 ANYWAY.
 C) ALUMINUM SIDING. PRODUCT APPROVAL
 SUBMITTED IS FOR CEMENTITIOUS SIDING
 PRODUCTS, NOT ALUMINUM AS SPECIFIED ON
 PLANS. NEED SPECIFIED PRODUCT APPROVAL.
 D) ALL SIMPSON STRUCTURAL CONNECTORS
 AS SPECIFIED ON PLANS. PRODUCT APPROVALS
 SUBMITTED ARE FOR USP AND ONLY ONE WAS
 GOOD FOR THE USP HLPTA75 CONNECTOR. THE
 REST OF THE PRODUCT APPROVALS SUBMITTED
 WERE NOT SPECIFIED ON PLANS.
 E) ALUMINUM VENTS.
  
 4- DESIGNER OF RECORD TO APPROVE IN
 WRITTING ALL PRODUCT APPROVALS,
 INCLUDING THE STORM SHUTTERS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
 TYPICALLY THIS IS DONE USING THE
 STANDARD REVIEW STAMP USED FOR SHOP
 DRAWINGS REVIEW.
  
 5- STORM SHUTTERS:
 A) PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. IT DIDN'T INCLUDE THE DWGS.
 B) INSTALLATION SCHEDULE:
 * WHY THE DESIGN PRESSURES ARE N/A?.
 THIS IS THE MOST IMPORTANT INFORMATION
 TO VERIFY COMPLIANCE OF PRODUCT BASED ON
 THE CALCULATED DESIGN PRESSURES. NEED
 THIS INFORMATION. SEE PLANS.
 C) VERIFY SIZES FOR PANEL SPAN. EG:
 OPENINGS 12 AND 13. IF THE OPENINGS ARE
 5'X6'-8" HOW COME THE PANEL SPAN IS
 88"?. ALSO, THIS APPLIES TO 4' HIGH
 OPENINGS. WHY USING 68" LONG PANELS?.
  
 D) VERIFY STRUCTURE TO BE ATTACHED TO.
 THIS IS A CONCRETE BLOCK STRUCTURE, NOT
 POURED CONCRETE. REVISE AS REQUIRED.
  
 6- DRAWING A-1: A) PROVIDE COMPLETE
 DETAILS/SPECS FOR WOOD DECK OUTSIDE
 MASTER BEDROOM AND FOR WOOD STEPS AT
 REAR COVERED PORCH. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 AND R11.5.3.2.
 B) UPDATE CODE REFERENCE SPECIFIED FOR
 ATTIC ACCESS, FIREBLOCKING AND
 WINDOW/DOOR GLAZING PROTECTION. THIS
 IS A RESIDENCE THE CORRECT CODE THAT
 REGULATES DWELLINGS IS THE RESIDENTIAL
 2004 CODE, NOT THE FBC 2004. REVISE AS
 REQ'D AND CITE CORRECT CODE REFERENCE
 SECTIONS FROM THE RESIDENTIAL CODE.
  
 7- DRAWING SP-1: A) SURVEY DOESN'T MATCH
 PLANS. SEE PLANS FOR PORCH DIMENSIONS
 AND LOCATION.
 B) NORTH ARROW ORIENTATION ON SITE PLAN
 IS INCORRECT. SEE SURVEY FOR CORRECT
 ORIENTATION AND REVISE AS REQUIRED.
  
 8- DRAWING A-2: A) BEDROOM #1 WINDOW
 DOESN'T COMPLY WITH EGRESS SECTIONS
 R310.1.1 AND R310.1.2.BOTH WINDOWS IN
 FRONT ELEVATION ARE SHOWN AS 3'X4'
 WINDOWS. ACCORDING TO FLOOR PLAN WINDOW
 IS 3'X5'. CLARIFY/REVISE AS REQUIRED.
 B) LETTERS IDENTIFYING THE OPENINGS
 DON'T MATCH FLOOR PLAN. REVISE AS REQ'D.
 C) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVERS AT FRONT AND BACK
 ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004 AND SECTION R806.
  
 9- DRAWING A-3: A) SECTION "A":
 * THERE IS NOT POURED CONCRETE ARCH.
 SEE ELEVATIONS STRUCTURAL DWGS. REVISE.
 ** WHERE IS DETAIL SHT 5?
  
 10- DRAWING A-4: A) WALL SECTION "A".
 SPECIFY FIREBLOCKING MATERIAL AND
 REVISE REFERENCE FOR FIREBLOCKING. SEE
 RESIDENTIAL 2004 FOR CORRECT CODE
 SECTION.
 B) WALL SECTION "B" DOESN'T MATCH
 STRUCTURAL DRAWINGS AND ELEVATIONS. SEE
 ROOF PORCH BEAM AND REVISE AS REQUIRED.
  
 11- DRAWING S-2: A) TYP. ONE STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. PROVIDE SPECIFIC
 INFORMATION. SECTION R806 2004.
 B) DETAIL H: USP RT24 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
  
 12- DRAWING S-3: A) REVISE TRUSS ANCHOR
 SCHEDULE. UPLIFT CAPACITY DOESN'T MATCH
 UPLIFT CAPACITY SHOWN ON CURRENT USP
 CATALOGUE. REVISE AS REQUIRED OR PROVIDE
 COMPLETE ENGINEERING PACKAGE SHOWING WHY
 CHANGING THE VALUES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 13- ENERGY CALCULATIONS:
 A) IF THIS IS A MODEL HOUSE. ENERGY
 CALCULATIONS NEED TO BE DONE FOR WORST
 CASE SCENARIO OR MUST BE SITE SPECIFIC
 WITH CORRECT HOUSE ORIENTATION.
 CALCULATIONS SUBMITTED ARE NOT FOR WORST
 CASE SCENARIO AND THEY DON'T MATCH THE
 ACTUAL ORIENTATION OF THE HOUSE. SEE
 SURVEY FOR CORRECT ORIENTATION. PROVIDE
 CALCULATIONS THAT COMPLY WITH EITHER
 WAY.
 B) OVERHANG LENGTH AND HEIGHT DON'T
 MATCH PLANS. SEE SECTION 13-601.2.A.3
 FOR PROPER WAY OF CALCULATING OVERHANG
 LENGTH AND HEIGHT. AND REVISE AS
 REQUIRED.
  
 14- ARCHITECT'S TITLE BLOCK TO INCLUDE
 ALL INFORMATION REQUIRED BY CHAPTER 481
 FLORIDA STATUTES AND 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. SEE
 ATTACHED COPY.NEED NAME OF ARCHITECT
 SIGNING AND SEALING PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-11 Cont ID  
Sent By jgomez Date 2006-03-11 Time 18:57 Rev Time 3.00
Received By jgomez Date 2006-03-11 Time 18:57 Sent To  
Notes
2006-03-11 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE DRAINAGE PLANS AS REQUIRED BY
 SEC. R401.3 OF 2004 RESIDENTIAL CODE.
  
 2- PROVIDE STRUCTURAL BUCK DETAIL USING
 2X BUCK AS REQUIRED BY ENTRY DOOR
 PRODUCT APPROVAL SUBMITTED. SEE SECTION
 R613.6.2 2004 RESIDENTIAL CODE FOR
 PROPER BUCK INSTALLATION.
  
 3- OWES $363.68 FOR UPDATED VALUATION
 AND RADON FEES.
  
 4- PROVIDE SPECS/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 5- DRAWINGS S-2 AND S-3 ARE MISSING
 THE ENGINEER'S INFORMATION AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTES.
  
 6- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR FRENCH DOORS WITH TRANSOM
 ABOVE SINGLE UNIT AS SHOWN ON PLANS OR
 PROVIDE COMPLETE INFORMATION FOR
 STRUCTURAL MULLION AS REQUIRED BY SEC.
 R613.7 2004 RESIDENTIAL CODE.
 B) PROVIDE SAME INFORMATION AS
 REQUIRED ABOVE FOR SLIDING GLASS DOORS
 WITH TRANSOM ABOVE SINGLE ASSEMBLY AS
 SHOWN IN PLANS.
 C) SPECIFY SIZE OF FIXED WINDOW.
  
 7- ARCHITECT TO PROVIDE ALLINFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES AND 61G1-16.004 OF
 ADMINISTRATIVE CODE. SEE ATTACHED COPY.
  
 8- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 FOR:
 A) FRENCH DOORS WITH TRANSOM ABOVE.
 OR FRENCH DOORS ALONE. SEE ITEM #7 ABOVE
 B) SLIDING GLASS DOORS WITH TRANSOM
 ABOVE. OR SLIDING GLASS DOORS ALONE. SEE
 ITEM #7 ABOVE.
 C) STRUCTURAL MULLIONS. SEE ITEM #7.
 D) FIXED WINDOWS. SEE ITEM #7 ABOVE.
 E) ALL TRUSS CONNECTORS. SEE PLANS.
 F) SINGLE HUNG WINDOWS. DADE COUNTY
 NOA TO MATCH NOA SUBMITTED FOR FLORIDA
 APPROVAL. VISIT WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD CORRESPONDING NOA.
 G) ROOF SHINGLES. PROVIDE SAME NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
 H) PRECAST LINTELS.
 I) ALUMINUM VENTS.
 J) ALUMINUM SIDING.
  
 9- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 10- DRAWING 1: UPDATE BUILDING CODE
 DATA. SEE 2004 RESIDENTIAL CODE.
  
 11- DRAWING A-1: A) SPECIFY SAFETY GLASS
 FOR WINDOW IN BATHROOM. SEE PLANS. SEC.
 R308.4 2004 RESIDENTIAL CODE.
 B) UPDATE CODE REFERENCE FOR ATTIC
 ACCESS. SEE 2004 RESIDENTIAL CODE.
 C) UPDATE CODE REFERENCES SPECIFIED
 ON GENERAL NOTES AND SCHEDULE NOTES. SEE
 2004 RESIDENTIAL CODE.
  
 12- DRAWING A-2: A) WINDOW PRESSURES
 CHART AND LETTERS KEYED ON ELEVATIONS
 DON'T MATCH. REVISE AS REQUIRED.
 B) SPECIFY SIZE OF MANUFACTURED
 ALUMINUM LOUVER AT FRONT AND BACK. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 13- DRAWING A-3: A) WHERE IS DETAIL A-5"
 SPECIFIED ON PLANS?
 B) SECTION "A": 1) WHERE IS DETAIL
 SHT 5?
 2) WHERE IS DETAIL SHT 5 FOR WOOD
 COLUMN SURROUND?
 3) WHERE IS THE CONCRETE SIDEWALK?.
 SEE SITE PLAN.
 4) SPECIFY TREAD SIZE. SEE SEC.
 R311.5.3.22004 RESIDENTIAL CODE.
 5) ENTRY PORCH HAS NOT ARCHED BEAM.
 REVISE AS REQUIRED. SEE ELEVATION.
 6) SPECIFY FIREBLOCKING AT CONCEALED
 WALL AND SPACES. SEE PLANS AND SEC.
 R602.8 2004 RESIDENTIAL CODE.
  
 14- DRAWING A-4: A) WALL SECTION "A".
 UPDATE CODE REFERENCE SPECIFIED FOR
 FIREBLOCKING AND SPECIFY FIREBLOCKING
 MATERIAL. SEE 2004 RESIDENTIAL CODE.
 B) WALL SECTION "B". FOUNDATION PLAN
 DOESN'T MATCH PLANS. REVISE AS REQUIRED.
  
 15- DRAWING S-1: A) PROVIDE COMPLETE
 DETAILS AND SPECS FOR WOOD DECK AND WOOD
 STEPS AT REAR AREA. SEE SEC. R311.5.3.2
 2004 RESIDENTIAL CODE. SPECIFY ALL
 FASTENERS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
 B) THERE IS NOT A3 TRUSS CONNECTOR.
 SEE TRUSS ANCHOR SCHEDULE. REVISE
 CONNECTOR SPECIFIED AT REAR PORCH.
 C) WHERE ARE DETAILS A, C AND E?
 KEY DETAILS TO MATCH DRAWINGS.
  
 16- DRAWING S-2: A) TYP. 1 STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. ALSO, CONSIDER ALUMINUM
 VENTS FOR TOTAL VENTING AREA REQUIRED.
 SEC. R806 2004 RESIDENTIAL CODE.
 B) DETAIL D: 1) HOW IS 2"X6" SILL
 PLATE ATTACHED TO CONCRETE BEAM?
 2) HOW IS 2" X 6" "L" BRACE NAILED TO
 BOTTOM SILL?
 3) USP TA18 IS SHOWN AS BEING
 ATTACHED TO CONCRETE BEAM. SEE USP
 CATALOGUE FOR PROPER INSTALLATION, SIZE
 AND FASTENERS. REVISE AS REQUIRED.
 4) DETAIL A: SHOW COMPLETE DETAILS
 AND SPECS FOR CONCRETE STEPS AT ENTRY
 PORCH. ALSO, SEE SEC. R311.5.3.2 2004
 RESIDENTIAL CODE.
  
 17- DRAWING S-3: A) GENERAL NOTES:
 UPDATE ALL REFERENCE STANDARDS AND
 SPECIFIC EDITION TO BE USED. SEE 2004
 RESIDENTIAL CODE AND 2004 FBC CHAPTER
 35.
 B) UPDATE CODE SECTIONS REFERENCED
 FOR WIND LOADS, EMERGENCY EGRESS AND
 GLASS IMPACT PROTECTION NOTES.
 C) VENTILATION AND EGRESS ARE TWO
 DIFFERENT CODE ISSUES.REVISE AS REQ'D.
 D) TRUSS ANCHOR SCHEDULE: NUMBER OF
 NAILS AND UPLIFT LOADS TO MATCH CURRENT
 USP CATALOGUE. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR NUMBER
 AND UPLIFT LOADS THAT DIFFER THOSE
 PUBLISHED BY MANUFACTURER. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 E) DELETE NOTES CORRESPONDING TO
 STRUCTURE ADDITIONS. THEY DON'T APPLY TO
 THIS PROJECT.
  
 18- SURVEY TO HAVE SURVEYOR'S ORIGINAL
 SIGNATURE, NOT COPY, AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 19- STORM SHUTTERS:
 A) PROVIDE KEY PLAN.
 B) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. PROVIDE
 ALL INFORMATION.
  
 20- ENERGY CALCULATIONS:
 A) USE 2004 FORM, NOT 2001.
 B) OWNER/AGENT TO SIGN BOTTOM OF FORM
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 19:14 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 19:06 Sent To M
Notes
2006-05-14 00:00:00** REDLINED PLANS,
  
 PLEASE SEESD'S ARE NOW SHOWN
 ON CIRCUIT #2 WHICH DOES NOT INDICATE
 ARC FAULT PROTECTION AS REQ'D UDNER 2002
 NEC 210.12B.
 SD'S CAN BE ON A-2, HOWEVER A AFCI TYOE
 BRKR WILL THEN BE REQUIRED.
  
 PLEASE SEE BATHS ARE NOW INDICATING ARC
 FAULT FOR BATHRMS?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By dpalmer Date 2006-02-15 Time 19:59 Rev Time 0.00
Received By dpalmer Date 2006-02-15 Time 19:59 Sent To Z
Notes
2006-02-15 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE SEE MISSING FIRM LICENSE
 NUMBER ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. FAC 61G1-16.004, FS 481.219
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE
 SIGNED , DATED AND SEALED BY AN
 ELECTRICAL ENGINEER, HOWEVER PLANS DO
 NOT CONTAIN ANY TITLE BLOCK FOR SAID
 ENGINEER OF RECORD AS REQUIRED PER FAC
 61G15-23.002, FS 471.023
  
 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT
 SHOWN FOR FUTURE PHONE. IT IS KNOWN TO
 THIS OFFICE THE TELEPHONE COMPANY AND
 CABLE COMPANY REQUIRES A MIN OF 3/4"
 CONDUIT FOR UNDERGROUND INSTALLATIONS.
 THIS IS FOR INFORMATIONAL PURPOSE ONLY
 AS THIS IS NOT AN NEC REQUIREMENT.
  
 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE
 IN LOAD CALCS WITH LOAD ON PANEL
 SCHEDULE.
 PLEASE VERIFY IF INDEED A 40A BRKR WILL
 BE USED AS MOST RANGES REQUIRE A MIN OF
 50A. (RANGE RECEPT IS 50A)
 PLEASE ALSO VERIFY WIRING METHODS TO BE
 USED. PLANS INDICATE CONDUIT AND WIRING,
 HOWEVER IF ROMEX IS USED, THE #8 SHOWN
 WOULD BE REQUIRED TO BE INCREASED TO #6.
 SEE 310.16, 60 DEGREE COL.
 215.5
  
 5)NOTE: PLEASE SEE SD'S ARE SHOWN BEING
 WIRED TO MORE THAN ONE CIRCUIT. PLEASE
 KNOW, THESE ARE REQUIRED TO BE WIRED
 INLINE AND WILL NOT WORK AS SHOWN.
 PLEASE BE SURE CIRCUIT SI ONE CONTAINING
 ARC FAULT PROTECTION.
  
 6)NOTE: PLEASE SEE ITEMS LISTED
 "OFF"PANEL SCHEDULE.
  
 7)NOTE: PLEASE SEE BATH CIRCUIT SHOWN AS
 #15 AWG? MISPRINT.
 PLEASE ALSO SEE BATH CIRCUITS ARE SHOWN
 WITH ARC FAULT BRKRS?
  
 8)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE RECEPTS PER 210.52C1
  
 9)NOTE: PLEASE SEE MISSING REAR GFI
 RECEPT PER 210.52E
  
 10)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES LANSCAPE LTS, HOWEVER PLANS DO
 NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN
 ON PLANS, THEN LANDSCAPE LIGHTING WILL
 BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, WHICH WILL INCLUDE PERMIT, PLANS
 AND FEE.
  
 ** PLEASE VERIFY WIRING METHOD, AS PLANS
 INDICATE CONDUIT AND WIRING FOR ALL
 CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE
 PERMITTED.
 THIS IS ONLY A NOTE.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 08:52 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 08:52 Sent To P
Notes
2008-01-04 08:53:03TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 11:39 Sent To P
Notes
2007-08-28 11:39:55TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-07-02 Time 09:13 Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 09:13 Sent To P
Notes
2007-07-02 09:13:58TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 13:11 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 13:11 Sent To B
Notes
2006-08-24 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 16:53 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 16:53 Sent To E
Notes
2006-05-11 00:00:00TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 12:52 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 12:52 Sent To Z
Notes
2006-05-06 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-11 Cont ID  
Sent By jgomez Date 2006-03-11 Time 18:57 Rev Time 0.00
Received By jgomez Date 2006-02-15 Time 16:16 Sent To  
Notes
2006-02-15 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-07 Cont ID  
Sent By tgordon Date 2006-09-07 Time 09:17 Rev Time 0.30
Received By tgordon Date 2006-09-07 Time 09:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 09:07 Rev Time 0.30
Received By tgordon Date 2006-05-15 Time 09:07 Sent To P
Notes
2006-05-15 00:00:00*** DENIED ***
 1) MANUAL J CAL'S. ARE SHOWING 1,764 SQ.
 FT. UNDER AIR, E-CAL'S ARE SHOWING 1451
 SQ. FT. UNDER AIR , AND BUILDING PLANS
 PAGE A-1 ARE SHOWING 1451 SQ. FT. UNDER
 AIR. PLEASE CORRECT AND MAKE ANY
 MECHANICAL EQUIP. CORRECTIONS AS A
 RESULT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By tgordon Date 2006-02-27 Time 15:18 Rev Time 0.30
Received By tgordon Date 2006-02-27 Time 15:18 Sent To B
Notes
2006-02-27 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN INFOMATION ON THEMAND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 3) TOTAL BTU'S ON E-CAL'S. ARE 25,800
 AND THE TOTAL BTU'S ON THE MECHANICAL
 PLANS ARE 36,000. THE BTU'S ON THE PLANS
 CAN NOT BE OVER THE E-CAL'S, PER 2004
 FBC CH. 13 .
  
 4) THE JOB ADDRESS NEEDS TO BE ON THE
 MECHANICAL PLANS.
  
 5)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 6) CONTRACTOR'S LICENSENUMBER NEED TO
 BE ON MECHANICAL PLANS.
  
 7) PLEASE SHOW COPPER LINE SIZES ON
 MECH. PLANS.
  
 8) PLEASE SHOW CONDENSATE DRAIN LINE ON
 MECH. PLANS.
  
 9) RETURN AIR TRANSFER DUCT NOT SIZED
 FROM BEDROOM #1 TO BEDROOM #2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-01-10 Cont ID  
Sent By jleech Date 2008-01-10 Time 09:02 Rev Time 0.00
Received By jleech Date 2008-01-10 Time 09:02 Sent To  
Notes
2008-01-10 09:03:29ENGINEER LETTER REDUCING WIDTH OF SHOWER FROM 32" TO
 30"

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 13:08 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 13:08 Sent To  
Notes
2007-09-15 13:09:13REVISED RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-25 Cont ID  
Sent By jleech Date 2007-07-25 Time 12:22 Rev Time 0.00
Received By jleech Date 2007-07-25 Time 12:22 Sent To  
Notes
2007-07-25 12:37:25PLUMBING REVISION DENIED;
 1.SANITARY RISER DIAGRAM NOT TO FLOOR PLAN;
 A) FLOOR PLAN HAS 2 1/2 BATHS SRD HAS 2.
 B) KITCHEN IS IN FRONT OF HOUSE ON FP IN BACK
 ON SRD.
 C) LT REQ. OWN VENT NOT ON SAME WALL AS W/M.
 2. PLEASE REVISE PAGE P-1 FLAT DRAWING PIPE SIZING IS
 DIFFERENT THAN SANITARY RISER DIAGRAM, ALSO CHECK WATER
 PIPE SIZE 1" HOT WATER IS SHOWN IN ONE SPOT.
 3. IF 1/2 BATH HAS BEEN DELETED AND THE KITCHEN
 LOCATION HAS MOVED ALL PAGES SHOWING THE FLOOR PLAN
 NEED TO BE REVISED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By jleech Date 2006-05-16 Time 13:09 Rev Time 0.00
Received By jleech Date 2006-05-16 Time 13:09 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By jleech Date 2006-02-27 Time 07:30 Rev Time 0.50
Received By jleech Date 2006-02-27 Time 07:30 Sent To M
Notes
2006-02-27 00:00:00DENIED;
 1. SEE ELECTRICAL NOTE #1.
 2.BATHROOM # 1 SHOWER NOT VENTED.
 3.ONLY ONE WASHER SHOWN ON FLOOR PLANS 2
 SHOWN ON RISER DIAGRAM.
 4.WATER HAMMER ARRESTORS REQUIRED ON
 KITCHEN WATER SUPPLY LINES.
 5.CODE TO USE IS FBC-2004 PLUMBING NOT
 2001.
 6.DELETE NOTE 26. NO CROSS CONNECTIONS
 PERMITED IN THE POTABLE WATER SUPPLY.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-11 Cont ID  
Sent By mmclean Date 2006-05-11 Time 15:45 Rev Time 0.00
Received By mmclean Date 2006-05-11 Time 15:45 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-23 Cont ID  
Sent By mmclean Date 2006-02-23 Time 13:18 Rev Time 0.00
Received By mmclean Date 2006-02-23 Time 13:18 Sent To  
Notes
***NONE***