Plan Review Details - Permit 06020582
Plan Review Stops For Permit 06020582
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-09 Cont ID  
Sent By amorse Date 2006-06-09 Time 14:52 Rev Time 0.75
Received By amorse Date 2006-06-09 Time 14:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-16 Cont ID  
Sent By amorse Date 2006-05-16 Time 06:38 Rev Time 1.50
Received By amorse Date 2006-05-16 Time 06:38 Sent To PC
Notes
2006-05-16 00:00:00 
  
 DENIED
  
 1) NOTE 5 ON PREVIOUS REVIEW WAS NOT
 ADDRESSED, ENERGY CALC'S SHALL BE SIGNED
 BY OWNER/AGENT. ALSO THE ENERGY CALC'S
 DO NOT MATCH THE DRAWINGS WITH RESPECT
 TO THE COOLING SYSTEM, DRAWINGS ARE 11
 SEER AND ENERGY CALC IS 13 SEER PLEASE
 CLARIFY AND CORRECT.
  
 2) REVISION 2 WAS ADDED TO A1 BUT WAS
 NOT LISTED ON THE TITLE BLOCK. ALSO BE
 AWARE THAT THE BLOCK FENCE SHALL BE
 PULLED UNDER A SEPARATE PERMIT THAT WILL
 REQUIRE AT A MINIMUM A CITY OF WEST PALM
 BEACH UTILITIES DEPT RELEASE (SEE
 PROVISO ON SURVEY BY ZONING DEPT.)
  
 3) REMOVE ALL OLD SHEETS EXCEPT THE 2
 COPIES OF A1 WITH COUNTY IMPACT FEE
 STAMPS AS THOSE SHALL BE ADDED TO PERMIT
 SETS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-27 Cont ID  
Sent By amorse Date 2006-03-27 Time 15:58 Rev Time 4.00
Received By amorse Date 2006-03-27 Time 15:58 Sent To PC
Notes
2006-03-27 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE
  
 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC (DRAWINGS CAN
 BE SUBMITTED WITH PLANS OR AS A SEPERATE
 SUBMITTAL BUT MUST BE REVIEWED BEFORE
 INSTALLATION)
  
 4) BATHROOM DOOR #103 SHALL COMPLY WITH
 R322.1.1 AND SHALL HAVE A CLEAR OPENING
 WIDTH OF 29"
  
 5) ENERGY CALC'S SHALL BE SIGNED AND
 DATED BY OWNER/AGENT
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7) PRODUCT APPROVALS FOR ROOFING ARE NO
 LONGER IN USE UNDER FL637 (CHECK FL 3506
 FOR SAME PRODUCTS AND THE MIAMI-DADE #
 THAT APPLIES TO EACH TYPE OF TILE) BE
 SURE TO MARK NOA FOR APPLICATION METHOD
 AND IF FOAM IS USED SUBMIT NOA
  
 NOTE:THE DRAWINGS SHOW BARREL TILE AND
 THE ROOF NOA IS FLAT NORDIC PLEASE
 CLARIFY
  
 8) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-12-07 Cont ID  
Sent By btrobaug Date 2006-12-07 Time 14:54 Rev Time 0.50
Received By btrobaug Date 2006-12-07 Time 14:19 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-03 Cont ID  
Sent By btrobaug Date 2006-05-03 Time 14:38 Rev Time 0.50
Received By btrobaug Date 2006-05-03 Time 13:15 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-23 Cont ID  
Sent By btrobaug Date 2006-02-23 Time 12:06 Rev Time 0.50
Received By btrobaug Date 2006-02-23 Time 10:49 Sent To M
Notes
2006-02-23 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SHOW THE DISCONNECTING MEANS
 PER 225.31 AND 225.32 AND GROUNDING PER
 250.32. SHOW THE DISCONNECT/PANEL
 LOCATION ON THE PLAN FOR THE GUEST
 HOUSE.
  
 2} THE LOAD CALCULATIONS DO NOT REFLECT
 ITEMS IN THE GUEST HOUSE. SMALL
 APPLIANCE CIRCUITS (2 MIN.) PER
 220.16(A), THERE IS NO CALC FOR ANY OVEN
 IN EITHER UNIT BUT ONE SHOWN IN THE
 GUEST HOUSE. NO DISPOSALS IN CALC, ONE
 SHOWN IN GUEST HOUSE. PLEASE VERIFY
 EXISTING ITEMS AT NAMEPLATE PER 220.30,
 AND RESUBMIT.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE FOR
 THE GUEST HOUSE PANEL SO THAT BRANCH
 CIRCUIT COMPLIANCE PER ARTICLE 210 CEN
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 14:01 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 14:01 Sent To E
Notes
2006-11-30 14:01:57TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 10:25 Rev Time 0.00
Received By adarroug Date 2006-06-06 Time 10:24 Sent To B
Notes
2006-06-06 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 11:29 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 11:29 Sent To E
Notes
2006-05-01 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-02-22 Time 11:13 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 11:13 Sent To E
Notes
2006-02-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-27 Time   Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 16:08 Sent To  
Notes
2006-02-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-12-11 Cont ID  
Sent By tgordon Date 2006-12-11 Time 10:36 Rev Time 0.20
Received By tgordon Date 2006-12-11 Time 10:36 Sent To  
Notes
2006-12-11 10:36:56REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-03 Cont ID  
Sent By tgordon Date 2006-05-03 Time 14:55 Rev Time 0.20
Received By tgordon Date 2006-05-03 Time 14:55 Sent To P
Notes
2006-05-03 00:00:00DUCTLESS A/C SYSTEM AND BATH EXHAUST
 FAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-03-07 Cont ID  
Sent By tgordon Date 2006-03-07 Time 15:47 Rev Time 0.30
Received By tgordon Date 2006-03-07 Time 15:47 Sent To B
Notes
2006-03-07 00:00:00DUCTLESS A/C SYSTEM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By jleech Date 2006-05-15 Time 12:37 Rev Time 0.00
Received By jleech Date 2006-05-15 Time 12:37 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-03-03 Cont ID  
Sent By jleech Date 2006-03-03 Time 14:58 Rev Time 0.00
Received By jleech Date 2006-03-03 Time 14:58 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-21 Cont ID  
Sent By mmclean Date 2006-02-21 Time 13:22 Rev Time 0.00
Received By mmclean Date 2006-02-21 Time 13:22 Sent To I
Notes
2006-02-21 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 CMU WALL/GATE/FENCE WITH EASEMENTS
 APPROVAL FROM CITY OF WEST PALM UTILITY
 DEPT, FPL, BELLSOUTH, ADELPHIA, FLORIDA
 PUBLIC UTILITES.