Plan Review Details - Permit 06020507
Plan Review Stops For Permit 06020507
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-10-06 Cont ID  
Sent By alange Date 2006-10-06 Time 08:06 Rev Time 0.00
Received By alange Date 2006-10-06 Time 08:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-09-05 Cont ID  
Sent By alange Date 2006-09-05 Time 09:59 Rev Time 0.50
Received By alange Date 2006-09-05 Time 09:59 Sent To  
Notes
2006-09-05 00:00:00COLUMN STIFFENING REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-22 Cont ID  
Sent By alange Date 2006-08-22 Time 08:51 Rev Time 1.50
Received By alange Date 2006-08-22 Time 08:51 Sent To I
Notes
2006-08-22 00:00:00DENIED
  
 1.SUBMIT PRODUCT APPROVALS FOR
 DOORS/STOREFRONT.
 ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.ADJUST PERMIT VALUATION AND PAY
 ADDITIONAL PERMIT FEES TO REFLECT THE
 THE ADDITIONAL SCOPE OF WORK.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-10 Cont ID  
Sent By alange Date 2006-08-10 Time 08:54 Rev Time 0.00
Received By alange Date 2006-08-10 Time 08:54 Sent To  
Notes
2006-08-10 00:00:00ROOF STRUCTURAL REVISIONS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-24 Cont ID  
Sent By alange Date 2006-05-24 Time 10:38 Rev Time 0.00
Received By alange Date 2006-05-24 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-18 Cont ID  
Sent By alange Date 2006-04-18 Time 10:42 Rev Time 4.50
Received By alange Date 2006-04-18 Time 10:31 Sent To  
Notes
2006-04-18 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PRODUCT APPROVALS REQUIRED FOR
 ROOFING, EXTERIOR DOORS, OVERHEAD DOORS,
 MODIFIED BITUMEN ROOF.NOTE:SELECT
 ASSEMBLY USED WITH MODIFIED BITUMEN
 ROOFING ON PRODUCT APPROVAL.
  
 3.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 5.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 6.BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM OF 1/8" SCALE FBC 106.1.3 WPB
 AMMENDMENTS TO THE 2004 FBC.
  
 7.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.SEE A-5 EGRESS
 DOOR CODE SECTIONS AND S-0.1 COMPONENTS
 AND CLADDING, AREA CALCS.
  
 8.SHOW PARKING LOT RESTRIPING DETAILS.
  
 9.SHOW DOOR BUCK DETAILS COMPLYING
 WITH FBC 1714.5.4.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-10-18 Cont ID  
Sent By dpalmer Date 2006-10-18 Time 07:16 Rev Time 0.00
Received By dpalmer Date 2006-10-17 Time 20:19 Sent To PC
Notes
2006-10-18 07:17:10REDLINED, FAIL SAFE INTERLOCK FOR MAINS AS REDLINED ON
 PREVIOUS PLANS TO BE FIELD VEIFIED PER 702.6
2006-10-17 20:32:53IN REVIEW, PLANS TO BE STAMPED ON 10/18/06 CALLED AND
 LEFT MESSAGE FOR JOE TO COME PICK UPREVISIONS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-21 Cont ID  
Sent By dpalmer Date 2006-08-21 Time 08:05 Rev Time 0.00
Received By dpalmer Date 2006-08-21 Time 07:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 14:37 Sent To PC
Notes
2006-08-16 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE ALL NEW OUTSIE
 LIGHTING, WALL LIGHTING ETC IS NOW BEING
 SHOWN NOT IN ORIGINAL SCOPE OF WORK.
 VALUE FOR SCOPE OF WORK NEEDS TO BE
 INCREASED, CALLED CONTRACTOR FOR VALUE
 NEEDED TO BE ADJUSTED BEFORE ONE IS
 ADJUSTED BASED ON MARSHALL'S /SWIFT
 GUIDE AS ADOPTED PER FBC 108.3.
 ONCE VALUE HAS BEEN ADJUSTED, PLANS CAN
 BE STAMPED AND RELEASED. PLANS ARE
 UPFRONT WAITING ON CONTRACTOR IN THE
 MEATIME. LEFT MESSAGE ON JOE HEDGES VM.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-02 Cont ID  
Sent By dpalmer Date 2006-08-02 Time 07:47 Rev Time 0.00
Received By dpalmer Date 2006-08-02 Time 07:39 Sent To  
Notes
2006-08-02 00:00:00REV'S OK, STAMPED FOR REVIED "CAFE'
 AREA.
 E.01, 3.2,4.1,6.2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-17 Cont ID  
Sent By dpalmer Date 2006-05-17 Time 18:18 Rev Time 0.00
Received By dpalmer Date 2006-05-17 Time 18:18 Sent To  
Notes
2006-05-17 00:00:00REDLINED PLANS.
  
  
 THE EMS SYSTEM/PANELS NOTED AS BY OTHERS
 SHALL BE UNDER A SEPARATE PERMIT, PLANS
 AND FEES. THIS MUST BE SUBMITTED FOR
 REVIEW AND ISSUED BEFORE ROUGH FOR
 BUILDING.
  
  
 REDLINED TO VIF 230.76. NO REV NEEDED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 10:26 Rev Time 0.00
Received By dpalmer Date 2006-03-20 Time 19:22 Sent To  
Notes
2006-03-21 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE SHEET A.0.1 WHICH
 REFERENCES THE FLORIDA FIRE PREVENTION
 CODE FOR THE ELECTRICAL CODE??
 PLEASE MAKE THE FOLLOWING REFERENCES FOR
 CODES ON ARCHITECTURAL SHEETS AND
 ELECTRICAL SHEETS.
 2002. NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLINGS UNITS
 FOR GFI PROTECTION.
  
 3) NOTE: PLEASE CLARIFY SOME FIXTURES
 IE: PLEASE SEE F1 WHICH MENTIONS THIS TO
 BE A PENDANT TYPE OF FIXTURE, HOWEVER
 PLANS INDICATE THESE AS2X4 LAYIN'S??
  
 4) NOTE: PLEASE PROVIDE MANUFEACTURES
 SPECS/CUT SHEETS ON LIGHTING CONTROL
 PANEL/ENERGY MANAGEMENT SYSTEM. PLEASE
 ALSO SUBMIT FOR EM INVERTER PANEL.
 215.5
 PLEASE BE SURE THESE INDICATE THE
 LISTING FROM A NRTL.
  
 5)NOTE; PLEASE PROVIDE SPECS/ CUT
 SHEETS FOR "KIRK KEY INTERLOCK" PLEASE
 PROVIDE INFORMATION THAT THE MAIN
 BREAKER STILL CONTAINS A MANUAL MEANS OF
 DISCONNECT LOCATED ON THE OUTSIDE OF THE
 EQUIPMENT. 230.76.230.79
  
 6)NOTE: PLEASE CALRIFY GROUND FAULT
 PROTECTION BEING INDICATED FOR BOTH
 MAINS. PLEASE SEE 230.95,240.13 ETC AS
 GF PROTECTION IS NOT REQUIRED, HOWEVER
 MAY BE INSTALLED.
 THIS IS ONLY A NOTE AND NO CHANGES ARE
 NEEDED. IF PLANS SHOWS THIS, THEN THEY
 WILL BE REQUIRED TO BE INSTALLED.
  
 7) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-413.1ABC.1, PLEASE SHOW WORST CASE
 SCENARIO FOR VOLTAGE DROP.
 PLEASE PROVIDE INFORMATION ON ROOMS
 WHICH ARE CONSIDERED SEPARATE SPACES.
 ELEC RM, BREAK, STORAGE.
 EVEN AS EXISTING, WITH THE SCOPE PF
 ELECTRICAL WORK BEING DONE , THESE AREAS
 WOULD BE REQUIRED TO MEET CURRNET CODE.
  
 8)NOTE: PLEASE INDICATE IF MAIN
 ELECTRICAL RM CONTAINS, AN EXISTING EM
 LT? IF NOT, ONE WILL BE REQUIRED.
 LS 101 7.8, 700.16 ETC.
  
 9)NOTE: PLEASE SEE EM LTS ARE REQUIRED
 TO BE CIRCUITED TO THE NORMAL LIGHTING
 BRANCH CIRCUIT IN ANY ONE AREA. 700.12E.
  
 10) NOTE: PLEASE SEE 210.62, 220.12 AS
 ANY WINDOW AREAS IN FRONT OF BLDG WILL
 REQUIRED "SHOW WINDOW" RECEPTS.
  
 11) NOTE: PLEASE VERIFY CONDUCTORS FROM
 WHAT WILL BE A TEMP GENERATOR GUTTER.
 PLEASE SEE THESE CONDUCTORS ARE SIZED
 FOR THE 1600'S AS SHOWN FOR "SB"?
 240.4,310.16
 AS THE GEN IS NOT PART OF THESE PLANS
 AND PERMIT AND IS ONLY GOING TO BE
 INSTALLED ON A "TEMP BASIS", NO
 PROVISIONS ARE PROVIDED FOR LIMITING THE
 OCP FOR THE FEEDERS.
  
 13) NOTE: PLEASE SEE IF GRND FAULT
 PROTECTION IS PROVIDED ON MAIN, PLEASE
 SEE THE POSSIBILTY OF AN ISSUE NOT
 SWITCHING THE NEUTRAL IN THE MAIN WHEN
 USING A GEN WHICH MAY OR MAY NOT HAVE
 GRND FAULT. PLEASE SEE 700.7D,700.26,
 NFPA-110 6.2.15*, 230.95B
  
 ** PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. PLEASE ONLY
 SUBMIT ON SET OF THE OLD/VOIDED REMOVED
 SHEETS.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2006-03-20 00:00:00IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-09-15 Cont ID  
Sent By mawillia Date 2006-09-15 Time 11:44 Rev Time 0.00
Received By mawillia Date 2006-09-15 Time 11:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-18 Cont ID  
Sent By mwennerg Date 2006-05-18 Time 15:29 Rev Time 0.00
Received By mwennerg Date 2006-05-18 Time 15:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-22 Cont ID  
Sent By mwennerg Date 2006-03-22 Time 15:12 Rev Time 0.00
Received By mwennerg Date 2006-03-22 Time 15:12 Sent To  
Notes
2006-03-22 00:00:00******DENIED******
  
 1) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED. SHT A-5.1.
  
 2) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3) COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION. SHT A5.1.
  
 4) PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AN OCCUPANT LOAD GREATER
 THAN 100. PLEASE INDICATE ON DOOR
 SCHEDULE.
  
 5) AN ADDRESS IS REQUIRED ON THE
 BUILDING AND SHALL BE A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING WITH THE
 BACKGROUND.
  
 6) SEPARATE SHOP DRAWING AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS OR REMODEL.
  
 7) THE FIRE DEPARTMENT CONNECTION SHALL
 BE LOCATED NOT FURTHER THAN 150' FROM A
 FIRE HYDRANT. THE DISTANCE EXCEEDS THIS
 REQUIREMENT ON SHT FP-1. PLEASE INDICATE
 IF THERE IS A CLOSER FIRE HYDRANT.
  
 8) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 9) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 10) DUCT SMOKE DETECTORS, IN ADDITION TO
 FAN SHUT DOWN, SHALL INITIATE A FIRE
 ALARM WHEN ACTIVATED IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 11) INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS SHALL COMPLY WITH
 NFPA 101, SECTION 36.3.3.1, AND SHALL BE
 CLASS A OR B. SHT A-0.1.
  
 12) EXIT ACCESS SHALL MEET THE
 REQUIREMENT OF NFPA 101, SECTION
 36.2.5.11.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 15:31 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 15:31 Sent To E
Notes
2006-10-12 15:31:44TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 14:51 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 14:51 Sent To B
Notes
2006-10-03 00:00:00TO "COMM" BD#1
2006-09-20 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 14:18 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 14:18 Sent To M
Notes
2006-09-19 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 10:15 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 10:14 Sent To B
Notes
2006-09-08 00:00:00TO "HPISKURA" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-08-25 Cont ID  
Sent By adarroug Date 2006-08-25 Time 09:10 Rev Time 0.00
Received By adarroug Date 2006-08-25 Time 09:10 Sent To B
Notes
2006-08-25 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 17:03 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 17:03 Sent To B
Notes
2006-08-23 00:00:00TO "COMM" BD#4
2006-08-22 00:00:008/22/06--WAITING FOR "COMM" BD-NEEDS
 ZONING AND FIRE PER "ALANGE"
  
2006-08-12 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 14:02 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 14:02 Sent To E
Notes
2006-08-11 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 11:54 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 11:54 Sent To M
Notes
2006-08-11 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-17 Time 09:01 Rev Time 0.00
Received By adarroug Date 2006-07-17 Time 09:01 Sent To  
Notes
2006-07-31 00:00:00TO "COMM" BD#14
2006-07-17 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 14:04 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 14:04 Sent To Z
Notes
2006-05-06 00:00:00SUBMITTAL PUT W/APPLICATION--WAITING FOR
 "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 08:32 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 08:31 Sent To  
Notes
2006-05-17 00:00:00TO "COMM" BD#63--EXPEDITED PERMIT---
2006-05-01 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-15 Cont ID  
Sent By adarroug Date 2006-04-15 Time 15:32 Rev Time 0.00
Received By adarroug Date 2006-04-15 Time 15:32 Sent To  
Notes
2006-04-15 00:00:00TO "COMM" BD#16 W/ APPLICATION-SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-18 Cont ID  
Sent By alange Date 2006-04-18 Time 10:47 Rev Time 0.00
Received By alange Date 2006-02-10 Time 09:34 Sent To  
Notes
2006-03-13 00:00:00TO "COMM" BD#16
2006-03-03 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-09-20 Cont ID  
Sent By tgordon Date 2006-09-20 Time 11:20 Rev Time 0.45
Received By tgordon Date 2006-09-20 Time 11:20 Sent To  
Notes
2006-09-20 00:00:00REVISION TO MECH. PLANS PAGES M2.2,
 M7.1, AND M7.2 .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-15 Cont ID  
Sent By tgordon Date 2006-08-15 Time 16:16 Rev Time 1.30
Received By tgordon Date 2006-08-15 Time 16:16 Sent To  
Notes
2006-08-15 00:00:00REVISION TO MECH. PLANS AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 15:50 Rev Time 0.45
Received By tgordon Date 2006-08-11 Time 15:50 Sent To  
Notes
2006-08-11 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) NEED TO SUBMIT NEW ENERGY
 CALCULATIONS AS THE A/C SYSTEMS WENT
 FROM 20 UNITS = 200 TOTAL BTU'S, TO 22
 UNITS = 232 TOTAL BTU'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-03-21 Cont ID  
Sent By hmoser Date 2006-03-21 Time 07:21 Rev Time 0.00
Received By hmoser Date 2006-03-21 Time 07:21 Sent To  
Notes
2006-03-21 00:00:00PASS PROVISO
 1) PLEASE REFER TO SECTION 307
 CONDENASTE DOSPOSAL.FBC(M)2004
 2) PLEASE REFER TO SECTION 307.2.3
 FBC(M)2004 AUXILIARY AND SECONDARY DRAIN
 SYSTEM.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-08-10 Cont ID  
Sent By jleech Date 2006-08-10 Time 07:43 Rev Time 0.00
Received By jleech Date 2006-08-10 Time 07:43 Sent To  
Notes
2006-08-10 00:00:00REVISED PLUMBING PLANS OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-27 Cont ID  
Sent By pschmitz Date 2006-05-27 Time 08:36 Rev Time 0.00
Received By pschmitz Date 2006-05-27 Time 07:35 Sent To  
Notes
2006-05-27 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 PROVISO
  
 SHT P-3.1 WATER HEATER DETAIL SEC 607.3
 PROVIDE THERMAL EXPANSION.
  
 CLEAN OUTS REQUIRED AT THE JUNCTION OF
 ALL BUILDING DRAINS AND BUILDING SEWER.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-06 Cont ID  
Sent By jleech Date 2006-04-06 Time 10:12 Rev Time 0.00
Received By jleech Date 2006-04-06 Time 10:11 Sent To  
Notes
2006-04-06 00:00:00DENIED;
 1.BREAK SINK; PAGE A-3.1 MUST COMPLY
 WITH FBC-2004 CHAPTER 11 SEC11-4.24.3
 KNEE CLEARANCE 30", WIDE 27", AND 19"
 DEEP FOR FRONTAL APPROACH. 11-4.24.4
 MAXIMUM DEPTH OF SINK IS 6 1/2" ADD
 NOTE. 11-4.24.6 INSULATE PIPES UNDER
 SINK, AND NOTE. 11-4.24.7 FAUCET TO BE
 LEVER, PUSH OR ELECTROIC, SHOW ON PLANS.
 2.PLEASE SHOW TURING RADIUS IN BOTH
 BATHROOMS AND IN H/C STALLS.
 3.URINAL: PAGE A-3.1 SEC.11-4.18.2 MAX.
 17" HIGH TO RIM TO FLOOR. 11-4.18.4
 FLUSH CONTROL NO HIGHER THAN 44". SHOW
 ON DRAWING.
 4.SANITARY RISER DIAGRAM W/C NOT VENTED
 ONLY 12 FIXTURE UNITS PERMITED ON A 3"
 WET VENT FBC-2004 PLUMBING TABLE
 909.3.SAME BRANCH DRAIN, RELIEF VENT
 PART OF THE CIRCUIT VENT SHOULD BE
 BETWEEN THE W/C AND F/D, SEC. 911.4.1.
 (ONE SET OF PLANS RED LINED)
 5.MOP SINK AND FLOOR DRAINS IN KITCHEN
 AREA ARE REQUIRED TO GO TO GREASY WASTE.
 6.UNDER COUNTER GREASE INTERCEPTERS IN
 FOOD PREP AREA ARE NOT PERMITED, (HEALTH
 DEPARMENT) PLEASE CONTACT THE UTILITY
 DEPARTMENT FOR GREASE TRAP SIZING TO
 COMPLY WITH WASTE ORD. 3434. LYNN MASSON
 PHONE NUMBER (561) 822-2271.
 7.TABLE 403.1, REQUIRES 3 DRINKING
 FOUINTAINS ON ONE SHOWN ON RISER
 DIAGRAMS. SEE SEC.410.1 ONLY ONE CAN BE
 BOTTLED WATER.
 8.CLEANOUTS REQUIRED AT THE JUNCTION OF
 THE BUILDING DRAIN AND BUILDING SEWER,
 AND BOTH SIDES OF LIFT STATION,
 SEC708.3.5.
 9.PROVIDE A DETAIL OF THE SEWAGE PUMP OR
 EJECTOT TO BE USED AND LOCATION OF VENT.
 SUMP PUMPS ARE NOT MADE FOR DISCHARGE OF
 SOLID WASTE FROM TOILETS.
 10. CAFE EQUIPMENT NOT LISTED PLEASE
 SHOW IN DETAIL INCLUDE LOCATION OF HAND
 SINKS THAT ARE REQUIRED.
 11.INDIRECT WASTE RECEPTORS SHALL COMPLY
 WITH 802.3 WITH REMOVABLE STRAINERS
 SEC802.3. (FLOOR SINKS)
 12.PAGE P-3.1 WATER HEATER DETAIL SHOW
 THERMAL EXPANSION CONTROL PER. 607.3
 ALSO SHOW LOCATION ON FLOOR PLAN.
 13.CAFE AREA TO BE REVIEWED AND APPROVED
 BY THE DEPARTMENT OF HOTEL AND
 RESTAUANTS. MUST BE APPROVED BEFORE NEXT
 PLUMBING REVIEW. (CONTACT CENTER
 (850)487-1395.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2006-10-25 Cont ID  
Sent By jroach Date 2006-10-25 Time 10:43 Rev Time 0.00
Received By jroach Date 2006-10-25 Time 10:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-09-07 Cont ID  
Sent By jroach Date 2006-09-07 Time 18:22 Rev Time 0.00
Received By jroach Date 2006-09-07 Time 18:22 Sent To  
Notes
2006-09-07 00:00:009/7/06 ***FAILED***
  
 SURVEY SHALL BE PROVIDED VERIFYING THAT
 THE PROPOSED REVISION TO THE PARKING LOT
 STRIPING DOES NOT RESULT IN A LOSS OF
 PARKING OR ANY OTHER NEW NONCONFORMITY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-23 Cont ID  
Sent By jroach Date 2006-05-23 Time 16:13 Rev Time 0.00
Received By jroach Date 2006-05-23 Time 16:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-28 Cont ID  
Sent By jroach Date 2006-03-28 Time 18:50 Rev Time 0.00
Received By jroach Date 2006-03-28 Time 18:50 Sent To  
Notes
2006-03-28 00:00:003/28/2006 ***FAILED***
  
 1) SECTION 94-441(C)(2) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS REQUIRES THAT
 RENOVATIONS, REPAIRS, ALTERATION OR
 REDEVELOPMENT WHICH EXCEEDS 50 PERCENT
 OF THE VALUE OF THE STRUCTURE SHALL
 BRING THE SITE UP TO ALL LANDSCAPING AND
 SCREENING REQUIREMENTS OF ARTICLE XIV.
  
 PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER AT (561) 822-1435 TO DISCUSS
 POSSIBLE SOLUTIONS TO THIS REQUIREMENT.