Plan Review Details - Permit 06020473
Plan Review Stops For Permit 06020473
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-14 Cont ID  
Sent By alange Date 2006-03-14 Time 09:06 Rev Time 0.33
Received By alange Date 2006-03-14 Time 09:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-01 Cont ID  
Sent By btrobaug Date 2006-03-01 Time 13:54 Rev Time 0.33
Received By btrobaug Date 2006-03-01 Time 13:26 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By mperson Date 2006-03-06 Time 15:14 Rev Time 0.15
Received By mperson Date 2006-03-06 Time 15:14 Sent To B
Notes
2006-03-06 00:00:00NOTES:GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL RES-GEN INSPECTION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 15:27 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 15:27 Sent To M
Notes
2006-04-03 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 16:19 Sent To Z
Notes
2006-03-17 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-25 Cont ID  
Sent By adarroug Date 2006-02-25 Time 11:55 Rev Time 0.00
Received By adarroug Date 2006-02-25 Time 11:55 Sent To E
Notes
2006-02-25 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-14 Cont ID  
Sent By alange Date 2006-03-14 Time 09:07 Rev Time 0.00
Received By alange Date 2006-02-13 Time 17:21 Sent To  
Notes
2006-02-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-04 Cont ID  
Sent By tgordon Date 2006-04-04 Time 08:09 Rev Time 0.15
Received By tgordon Date 2006-04-04 Time 08:09 Sent To  
Notes
2006-04-04 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-02 Cont ID  
Sent By tgordon Date 2006-03-02 Time 11:36 Rev Time 0.15
Received By tgordon Date 2006-03-02 Time 11:36 Sent To P
Notes
2006-03-02 00:00:00*** DENIED ***
 1) NEED TO PROVIED TWO COPYS OF THE
 CURRENT SURVEY SHOW THE PROPOSED
 LOCATION OF THE GENERATOR.
  
 2) PLEASE BE AWARE THAT GENERATOR EXHUST
 MUST BE TEN FEET AWAY FROM ANY BUILDING
 OPENINGS (WINDOWS, DOORS, ROOF & EAVE
 VENTS), AND TEN FEET AWAY FROM ADJECENT
 BUILDING OPENS. PER 2004 FBC/M 401.5.1,
 AND MAKE NOTE ON SURVEY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By mperson Date 2006-03-06 Time 15:14 Rev Time 0.00
Received By mperson Date 2006-03-06 Time 15:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-04-02 Cont ID  
Sent By mmclean Date 2006-04-02 Time 17:22 Rev Time 0.00
Received By mmclean Date 2006-04-02 Time 17:22 Sent To I
Notes
2006-04-02 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO A
 SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-24 Cont ID  
Sent By mmclean Date 2006-02-24 Time 11:26 Rev Time 0.00
Received By mmclean Date 2006-02-24 Time 11:26 Sent To I
Notes
2006-02-24 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF CURRENT
 SURVEY WITH THE LOCATION OF THE PROPOSED
 GENERATOR.
 2. MUST PROVIDE THE DIMENSION OF
 GENERATOR AND SETBACK FROM THE PROPERTY
 LINE & STRUCTURE.
  
 NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720