Plan Review Details - Permit 06020407
Plan Review Stops For Permit 06020407
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-03-30 Cont ID  
Sent By nmccray Date 2006-03-30 Time 10:50 Rev Time 0.00
Received By nmccray Date 2006-03-30 Time 10:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By nmccray Date 2006-02-27 Time 15:33 Rev Time 0.00
Received By nmccray Date 2006-02-27 Time 15:33 Sent To  
Notes
2006-02-27 00:00:00DENIED:
  
 1) FIRE ALARM SYSTEM SHALL CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 2) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFICATED FOR CENTRAL STATION SERVICE
 AND HAVE DOCUMENTS ATTESTING TO THIS
 CERTIFICATION PRIOR TO FINAL FIRE
 INSPECTION.
  
 3) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN THE CITY OF WEST
 PALM BEACH.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-30 Cont ID  
Sent By nmccray Date 2006-03-30 Time 10:49 Rev Time 0.00
Received By nmccray Date 2006-02-10 Time 09:42 Sent To  
Notes
2006-02-10 00:00:00TO "F" BOX