Plan Review Details - Permit 06020406
Plan Review Stops For Permit 06020406
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-03 Cont ID  
Sent By shill Date 2006-05-03 Time 15:30 Rev Time 0.00
Received By shill Date 2006-05-03 Time 15:30 Sent To  
Notes
2006-05-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)CERTIFICATE OF AUTHORIZATION NUMBER
 FOR THE PROFESSIONAL ASSOCIATION IS
 REQUIRED, FAC61G15-23.002.
  
 2.)EACH SHEET IS TO BE SEALED OR AN
 INDEX SHEET IS REQUIRED,
 FAC61G15-23.002.YOU HAVE INCLUDED AN
 INCOMPLETE TABLE OF CONTENTS.ADDRESS.
  
 3.)THE LETTER DATED FEBRUARY 1, 2006
 FROM DAVIS ENGINEERS PA TO WEST PALM
 BEACH REFERS TO 20TH FBC RATHER THAN
 2004 FBC (TYPO).
  
 4.)PROVIDE A SITE PLAN WHICH SHOWS
 COMPLIANCE WITH FBC TABLE 602,
 FBC3103.3..A SITE PLAN WAS PROVIDED
 BUT DOES NOT INCLUDE DIMENSIONS TO THE
 PROPERTY LINE OR TO THE FUTURE SALES
 OFFICE TRAILER.
  
 5.)THE LETTER DATED FEB 1,2006
 PROVIDES A WIND DESIGN CRITERIA OF 90MPH
 WITH REMOVAL OF THE FABRIC AT 75MPH.
 THE CITY OF WEST PALM BEACH IS IN THE
 140MPH ZONE.THE ENTIRE STRUCTURE IS TO
 BE STRUCTURALLY COMPLIANT FOR THIS WIND
 ZONE, FBC1609, FBC3102.7.
  
 6.)PROVIDE WIND DESIGN INFORMATION
 FBC1603.1.4.NOTE THAT THIS PARCEL HAS
 ALREADY BEEN DETERMINED TO BE EXPOSURE C
 BY OTHER DESIGN PROFESSIONALS.
  
 7.)DECLARE AN OCCUPANCY, FBC CHAPTER
 3.
  
 8.)THE LETTER STATES THAT THE SOIL
 CONDITIONS ARE SIMILAR TO THE DORAL
 PROJECT.THE LETTER FROM THE SOILS
 ENGINEER STATES THAT THERE IS A LIMEROCK
 SUBSTRATE.THIS AREA DOES NOT HAVE A
 LIMEROCK SUBSTRATE.A SOILS REPORT IS
 AVAILABLE FOR THIS SITE.CONSULT WITH
 THE SOILS ENGINEER FOR THIS PROJECT TO
 JUSTIFY YOUR DESIGN RATHER THAN
 ENGINEERING FROM ANOTHER PROJECT.
  
 7.)ANY SUPPORTING DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FAC61G15-23.002.
  
 8.)FLAME RESISTANCE IS TO BE IN
 ACCORDANCE WITH NFPA 701.THE
 CERTIFICATE PROVIDED IS DATED 2002,
 STATES THAT IT IS FILED WITH CALIFORNIA,
 AND DOES NOT REFER TO NFPA 701.IT ALSO
 STATES THAT IT COVERS MATERIALS REFERRED
 TO ON THE REVERSE SIDE, BUT THAT SIDE IS
 BLANK.PLEASE ADDRESS.
  
 9.)PROVIDE THE EXIT DOOR DIMENSION,
 FBC10.
  
 10.)SHOW THE SIDEWALK WIDTH AND THE
 SLOPE (ACCESSIBLE ROUTE),
 FBC11-4.1.2(2).NOTE THAT THE SITE PLAN
 STATES THAT THERE IS A SLOPE IN THE
 GRADE.
  
 11.)PROVIDE THE ELEVATION ON BOTH
 SIDES OF THE DOOR, FBC11-4.1.2.
  
 12.)PROVIDE DETAILS FOR THE BATHROOM;
 TURNING RADIUS, DIMENSIONS FOR THE SINK
 AND TOILETS, GRAB BARS, ETC.THE FLOOR
 PLAN DOES NOT MATCH THE ELEVATION.
  
 13.)THE FLOOR PLAN DIFFERS FROM THE
 SITE PLAN IN THE BATHROOM LOCATION. IF
 THE BATHROOM IS LOCATED TEN FEET AWAY AS
 SHOWN, PROVIDE INFORMATION IN REGARDS TO
 THE ACCESSIBLE ROUTE.A RAMP IS SHOWN
 ON AN ELEVATION, WHAT IS THIS FOR?
  
 14.)INFORMATIONAL ONLY; NEW COMMENTS
 ARE LIKELY UPON RESUBMITTAL DUE TO THE
 LACK OF COMPLETE INFORMATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By dpalmer Date 2006-03-06 Time 19:08 Rev Time 0.00
Received By dpalmer Date 2006-03-06 Time 18:52 Sent To  
Notes
2006-03-06 00:00:00************UNSAT ************
  
 1)NOTE: PLEASE SEE NOT ENOUGH
 INFORMATION WAS SUBMITTED FOR ELECTRICAL
 PLANS.
  
 2)NOTE:PLEASE SEE NO RISER, PANEL
 SCHEDULES, LOAD CALCUALTIONS ETC.
 215.5
  
 3)NOTE: PLEASE SUBMIT SPECS FOR
 GENERATOR UNIT AND HOW THIS WILL CONNECT
 INTO ELECTRICAL SYSTEM.
  
 4)NOTE: PLEASE PROVIDE LAYOUT FOR SALES
 OFFICE FURNITURE.
  
 5)NOTE: PLEASE VERIFY ALL CIRCUITING FOR
 EM/ EXT LTS PER 700.12E.
 PLEASE SEE NO PERMANENT LIGHTING OR
 EMERGENCY LTS ARE SHOWN??
 PLEASE PROVIDE MIN LIGHTING PER LS 101
 7.8, 7.9.2.2
  
 6)NOTE: PLEASE SEE PLANS SUBMITTED
 CONTAINING TITLE BLOCKS FOR ENGINEER ,
 SHALL BE SIGNED, DATED AND SEAL AS
 REQUIRED PER FS 471.025
 PLEASE SEE REVIEW COMMENTS FROM OTHER
 TRADES WHICH MAY REQUIRE PLANS.
  
 7)NOTE: PLEASE SUBMIT ELECTRICAL
 PLANS/DETAIL FOR REVIEW UNDER THE 2002
 NEC, LS 101 ETC
  
 8)NOTE: PLEASE SEE MISSING LICENS
 INFORMATION REQUIRED ON TITLE BLOCKS FOR
 ENGINEERING FIRM. PER FLORIDA
 ADMININSTRATIVE CODE 61G15-23.002,
 FLORIDA STATUES, 471.023
  
 9)NOTE: PLEASE SEE VALUATION SHALL
 INCLUDE ALL LABOR AND MATERIALS FOR
 COMPLETE SCOPE OF WORK FOR TIME IN-USE,
 108.3 FBC ADMINISTRATIVE CODE AS AMENDED
 BY THE CITY OF WEST PALM BEACH.
  
 10)NOTE: PLEASE SEE COMMENS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW ONCE ALL REVIEWS ARE COMPLETED.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-11 Cont ID  
Sent By mwennerg Date 2006-04-11 Time 09:33 Rev Time 0.00
Received By mwennerg Date 2006-04-11 Time 09:33 Sent To  
Notes
2006-04-11 00:00:00******DENIED******
  
 1) PLEASE SUBMIT MANUFACTURER SPEC
 SHEETS FOR GENERATOR.
  
 2) PLEASE PROVIDE MORE INFORMATION
 REGARDING EXIT LIGHT, EMERGENCY LIGHTING
 AND FIRE EXTINGUISHER LOCATIONS.
  
 3) IN ADDITION TO APPLICABLE BUILDING
 CODES, LIFE SAFETY TO COMPLY WITH NFPA
 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-03 Cont ID  
Sent By shill Date 2006-05-03 Time 17:39 Rev Time 0.00
Received By shill Date 2006-02-09 Time 16:56 Sent To  
Notes
2006-03-06 00:00:00TO "COMM" BD#14
2006-02-09 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-20 Cont ID  
Sent By hmoser Date 2006-03-20 Time 10:40 Rev Time 0.00
Received By hmoser Date 2006-03-20 Time 10:40 Sent To  
Notes
2006-03-20 00:00:00MECHANICAL PERMIT NOT ERQUIRED. 3/20/06
 HM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-17 Cont ID  
Sent By jleech Date 2006-04-17 Time 13:44 Rev Time 0.00
Received By jleech Date 2006-04-17 Time 13:44 Sent To  
Notes
2006-04-17 00:00:00DENIED;
  
 1.BATHROOMS DO NOT APPEAR TO MEET THE
 FBC-2004 CHAPTER 11 ACCESSIBITY CODE.
 PLEASE SHOW DETAIL WITH TURNING RADIUS
 AND CLEAR FLOOR SPACE.
 2.FBC-2004 PLUMBING TABLE 403.1 MINIMUM
 PLUMBING FIXTURES REQUIRES A DRINKING
 FOUINTAIN NONE SHOWN.
 3.SHOW WATER AND SEWER CONNECTIONS.
 BACKFLOW PROTECTION REQUIRED ON WATER
 SERVICE.
 4.INFORMATION NEEDED FROM GENERATOR;
 MANUFACTURE SPEC SHEETS,SIZE AND TYPE OF
 FUEL IT WILL USE.
 5.SITE PLAN AND FIRE LEGEND DRAWINGS ARE
 NOT THE SAME. GENERATOR AND BATHROOM
 LOCATIONS ARE DIFFERENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-03-29 Cont ID  
Sent By ajones Date 2006-03-29 Time 08:58 Rev Time 0.00
Received By ajones Date 2006-03-29 Time 08:57 Sent To  
Notes
***NONE***