Plan Review Details - Permit 06020393
Plan Review Stops For Permit 06020393
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-07 Cont ID  
Sent By lmartine Date 2006-04-07 Time 13:49 Rev Time 0.00
Received By lmartine Date 2006-04-07 Time 13:49 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-02 Cont ID  
Sent By lmartine Date 2006-03-02 Time 16:32 Rev Time 0.00
Received By lmartine Date 2006-03-02 Time 16:32 Sent To E
Notes
2006-03-02 00:00:00 
  
  
 BUILDING REVIEW COMMENTS
 -------- ------ --------
  
  
  
 1)
 EXPLAIN NEW INFORMATION FOR EXISTING
 ROOF TO BE RE-SHEATHED AND NEW OPENINGS
 INCLUDED WITH NO SUPPORTING DETAILS,
 WILL THERE BE A ROOF COVER APPLIED AND
 IF SO A SEPERATE ROOF PERMIT WILL BE
 REQUIRED.
  
 2)
 WHERE IS SECTION 'C' ON SHEET S-1.
  
 3)
 CONCRETE PAD PLACEMENT SHALL BE GIVEN
 SPECIFIC LOCATION NOT GENERAL.
  
 4)
 NATURAL AIR INTAKE CALCULATIONS MAYBE
 REQUIRED NOW THAT THE PLAN CALLS FOR A
 SOLID ROOF, IT WAS ORIGINALLY DESCRIBED
 AS AN OPEN AIR STRUCTURE.
  
 5)
 PRODUCE 2 COMPLETE SETS OF CONSTUCTION
 DRAWINGS FOR PERMIT ISSUE.
  
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-02-17 Cont ID  
Sent By lmartine Date 2006-02-17 Time 18:20 Rev Time 0.00
Received By lmartine Date 2006-02-17 Time 18:20 Sent To P
Notes
2006-02-17 00:00:00 
  
  
 BUILDING COMMENTS
 -------- --------
  
 PROVISO
 -------
  
  
  
 HAVE ENGINEER CORRECT STRUCTURAL NOTES
 ON SHEET S-2.
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-04-07 Cont ID  
Sent By dpalmer Date 2006-04-07 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2006-04-07 Time 16:02 Sent To  
Notes
2006-04-07 00:00:00COLUMN BEING REMOVED AS REDLINED ON
 PLANS PER 110.26,110.34
  
 SEE "S" SHEETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-06 Cont ID  
Sent By dpalmer Date 2006-03-06 Time 11:08 Rev Time 0.00
Received By dpalmer Date 2006-03-06 Time 11:08 Sent To B
Notes
2006-03-06 00:00:00***** NOTE/ FAIL*****
  
 1)NOTE: ELECTRICAL PLANS REDLINED AS
 COLUMN IS STILL SHOWN. SEE S-SHEETS AS
 THIS COLUMN IS BEING REMOVED.
  
 2)NOTE: PLEASE KNOW, PLANS TO REMAIN IN
 "F" STATUS UNTIL MECHANICAL AND BLDG
 REVIEWS ARE OK.
 PLEASE SEE BLDG SHEETS NOW INDICATE A
 ROOF OVER THE GENERATORS.
 PLEASE SEE MECHANICAL REVIEW AS AIR
 INTAKE CALCULATIONS FOR MAKE UP AIR
 WOULD BE NEEDED.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE
 CALL.\
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 18:17 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 16:50 Sent To Z
Notes
2006-02-08 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE DISRIBE PROJECT AS BEING
 INDICATED ON PLANS ON PERMIT
 APPLICATION. IF 2 GENERATORS ETC.
  
 2)NOTE: PLEASE SUBMIT MANUFACTURES
 SPEC/CUT SHEETS FOR ALL NEW EQUIPMENT
 BEING INSTALLED. GENERATOR,
 SYNCHRONIZATION EQUIPMENT, FUEL TANKS,
 ANY ATS EQUIPMENT ETC.
 PLEASE BE SURE ALL LISTINGS AS INDICATE
 FROM A NRTL.
  
 3)NOTE: PLEASE SEE THE PROPOSED
 GENERATORS ARE SUBSTANTIALLY LARGER THAN
 THE PREVIOUS ORIGIANL GENERATORS. PLEASE
 SEE PLANS SHOW THESE BEING LOCATED HALF
 IN AND HALF OUT OF GEN BLDG??
 IF THESE GEN'S ARE GOING TO BE "OUTSIDE"
 RAINTIGHT GEN'S, PLEASE BE SURE ALL MIN
 CLEARENCE REQUIREMENTS FOR PROPER
 VENTILATION IS PROVIDED. PLEASE SEE
 FOLLOWING COMMENT.
  
 4)NOTE: PLEASE SEE CLEARENCES FOR NEC
 CODE COMPLIANCE IS NOT MET PER TABLES
 110.34A.
 PLEASE ALSO SEE ENTRANCE, EGRESS
 ACCESSED IS ALSO NOT MET PER 110.33A1
 ETC.
  
 5)NOTE: PLEASE SEE NO INFORMATION IS
 PROVIDED FOR OCP AT GEN'S TO FEED NEW
 EQUIPMENT.
 PLEASE SEE 445.13 FOR SIZING ETC IFNO
 OCP IS PROVIDED AT GEN. ETC
  
 6)NOTE: PLEASE PROVIDE MORE INFORMATION
 ON TYOE OF CONDUCTORS ARE BEING
 INSTALLED FOR 5KV CONDUCTORS. PLEASE SEE
 TABLES 310.60
 PLEASE SEE THE # OF CONDUCTORS IN
 CONDUITS, AND SIZE , OCP AND AMBIENT
 TEMPS, AND VOLTAGE DROP MUST BE
 CONSIDERED. UNABLE TO DO THIS AT THIS
 TIME.
 ** PLEASE COMPLETE.
  
 7)NOTE: PLEASE CLARIFY IF THERE IS NEW
 OR EXISTING TRANSFER EQUIPMENT.
 PLEASE SEE THIS UNCLEAR ON ONE-LINE.
 215.5
  
 8)NOTE; PLEASE PROVIDE THE MIN LOADS FOR
 THE EXISTING LOADS WHICH WILL BE LOADED
 ON NEW GENERATORS.
 IT IS KNOWN THAT THESE WILL BE FEEDING
 EXISTING PUMPS ETC, HOWEVER THERE IS NO
 RECORD OF THE IMPOSED LOADS.
 PLEASE KNOW, THIS OFFICE HAD REVIEWED
 DOCUMENTATION IN WHICH THE GEN'S WERE
 GOING TO BE 3500KW.
 PLEASE VERIFY AND SHOW LOADS.
 215.5
  
 9)NOTE:PLEASE PROVIDE THE LOCATIONS OF
 OTHER EQUIPMENT. GEN SW GEAR BUS ETC.
  
 10)NOTE: PLEASE SEE THE GC IS APPLYING
 ONLY FOR THE INSTALLATION OF THE
 GENERATOR. PLEASE KNOW, A PERMIT MUST BE
 APPLIED FOR THE ELECTRICAL HOOK-UP AND
 INSTALLATION. THIS WILL BE A GEN- ELEC
 TYPE PERMIT. PLEASE ALSO KNOW A FUEL
 PERMIT WILL BE REQUIRED FOR SCOPE OF
 WORK FOR FUEL TANKS, PIPING ETC.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-04-05 Cont ID  
Sent By nmccray Date 2006-04-05 Time 11:11 Rev Time 0.00
Received By nmccray Date 2006-04-05 Time 11:11 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-03-03 Cont ID  
Sent By mwennerg Date 2006-03-03 Time 13:48 Rev Time 0.00
Received By mwennerg Date 2006-03-03 Time 13:48 Sent To  
Notes
2006-03-03 00:00:00******DENIED******
  
 1) PLEASE SUBMIT (2) COMPLETE SETS OF
 PLANS FOR REVIEW.
  
 2) DERM APPROVAL IS REQUIRED AND MUST BE
 REFLECTED ON DRAWINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By nmccray Date 2006-02-15 Time 10:04 Rev Time 0.00
Received By nmccray Date 2006-02-14 Time 10:28 Sent To I
Notes
2006-02-15 00:00:00DENIED:
  
 1) SHALL COMPLY WITH NFPA 110 STANDARD
 FOR EMERGENCY AND STANDBY POWER SYSTEMS
 2002 EDITION.
  
  
 2) PLEASE SUBMIT MANUFACTURES SPEC'S AND
 CUT SHEETS FOR ALL NEW EQUIPMENT BEING
 INSTALLED.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-02-21 Cont ID  
Sent By kstevens Date 2006-02-21 Time 17:34 Rev Time 0.00
Received By kstevens Date 2006-02-21 Time 17:34 Sent To  
Notes
2006-02-21 00:00:00FUEL SOURCE FOR GENERATORS IS DIESEL
 ONLY. NO NATURAL/LP GAS FOUND.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-02 Cont ID  
Sent By lmartine Date 2006-03-02 Time 17:14 Rev Time 0.00
Received By lmartine Date 2006-03-01 Time 17:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 16:20 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 16:20 Sent To B
Notes
2006-02-15 00:00:00TO "LMARTINEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 10:26 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 10:26 Sent To M
Notes
2006-02-15 00:00:00TO "PKRAUSS" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-09 Cont ID  
Sent By adarroug Date 2006-02-09 Time 12:07 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 12:07 Sent To M
Notes
2006-02-09 00:00:00TO "TGORDON" DESK--EXPIDITED PLAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-22 Cont ID  
Sent By lmartine Date 2006-02-22 Time 12:08 Rev Time 0.00
Received By lmartine Date 2006-02-08 Time 13:10 Sent To  
Notes
2006-02-08 00:00:00TO "MMCLEAN" DESK--EXPIDITED PLAN PER
 "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-05 Cont ID  
Sent By pkrauss Date 2006-04-04 Time 13:36 Rev Time 0.00
Received By pkrauss Date 2006-04-04 Time 13:36 Sent To P
Notes
2006-04-04 00:00:00PROVISO:
  
 1.PER 2004 FMC 1302.3 PIPE MATERIAL
 FOR FUEL OIL PIPING SHALL BE IN
 ACCORDANCE WITH TABLE 1302.3,
 NONMETALLIC PIPE - ASTM D2996.
 THE SUBMITTAL FOR THE SPECIFICATION OF
 THE FUEL OIL PIPING INDICATES ASTM
 D2310.THIS SHOULD READ ASTM D2996 AS
 THE STANDARD.ASTM D2310 IS A
 CLASSIFICATION UNDER ASTM D2996 &
 RTRP-11AF REFERENCES THE DESIGNATION
 CODE.THE MARKING OF THE PIPE SHALL
 COMPLY WITH ASTM D2996 SUB-SECTION 10.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By pkrauss Date 2006-02-15 Time 14:37 Rev Time 0.00
Received By pkrauss Date 2006-02-15 Time 14:13 Sent To I
Notes
2006-02-15 00:00:00DENIED:
 PLEASE PROVIDE A MINIMUM OF 4 COPIES TO
 THE DERM AT 3323 BELVEDERE ROAD BLDG
 #502, ATTENTION TO CHIP GREEN.CHIP
 GREEN MAY BE CONTACTED AT (561)233-2504.
  
 PLEASE RESUBMIT AFTER DERM APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status N Date 2006-02-09 Cont ID  
Sent By astelly Date 2006-02-09 Time 09:20 Rev Time 0.00
Received By astelly Date 2006-02-09 Time 09:20 Sent To  
Notes
2006-02-09 00:00:00GENERATOR IS WITHIN THE PROPERTY. NO DMP
 REVIEW REQUIRED.
  
 PLANS RETURNED TO INCOMING FOR FURTHER
 PROCESS.

Review Stop Z ZONING
Rev No 1 Status N Date 2006-02-09 Cont ID  
Sent By mmclean Date 2006-02-09 Time 10:56 Rev Time 0.00
Received By mmclean Date 2006-02-08 Time 15:48 Sent To  
Notes
2006-02-08 00:00:00PLANS ROUTED TO DPLANNER FOR ELECTRICAL
 REVIEW PER RBROWN.