Plan Review Details - Permit 06020337
Plan Review Stops For Permit 06020337
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-14 Cont ID  
Sent By btrobaug Date 2006-02-14 Time 14:57 Rev Time 0.33
Received By btrobaug Date 2006-02-14 Time 14:57 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-10 Cont ID  
Sent By btrobaug Date 2006-02-10 Time 07:36 Rev Time 0.50
Received By btrobaug Date 2006-02-10 Time 07:23 Sent To P
Notes
2006-02-10 00:00:00 
 PLEASE SUBMIT A RISER DIAGRAM INDICATING
 CONDUCTOR,CONDUIT AND GROUNDING
 ELECTRODE SYSTEM SIZES.
 ALSO CHECK THE AVAILABLE FAULT CURRENT
 AT THE TRANSFORMER TO CONFIRM THE
 EQUIPMENT CONFORMS TO 110.9 AND 10.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/561) 805-6731
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-10 Cont ID  
Sent By btrobaug Date 2006-02-10 Time 07:23 Rev Time 0.00
Received By btrobaug Date 2006-02-08 Time 13:50 Sent To E
Notes
2006-02-08 00:00:00TO "E" BOX