Plan Review Details - Permit 06020333
Plan Review Stops For Permit 06020333
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2006-06-28 Cont ID  
Sent By lursu Date 2006-06-28 Time 08:53 Rev Time 0.00
Received By lursu Date 2006-06-28 Time 08:53 Sent To  
Notes
2006-06-28 00:00:00BASED ON THE NEW LIST PROVIDED BY THE
 CIY PLACE GUEST SERVICE SUPERVISOR THE
 UNIT 162 FOR JOURNEYS IS UNDER
 CONSTRUCTION AND IS UNIT 162.THE EXT
 #0014 MODIFIED TO BE USED FOR UNIT 162.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-06-27 Cont ID  
Sent By lursu Date 2006-06-27 Time 08:17 Rev Time 0.00
Received By lursu Date 2006-06-26 Time 13:11 Sent To  
Notes
2006-06-26 00:00:00EXT #0014 WAS CREATED INITIALLY FOR UNIT
 165 TO MATCH THE SITE ADDRESS LIST FOR
 THE CITY PLACE BUT ON THE APPLICATION
 THE UNIT IS C9.
 ON THE APPLICATION THE ADDRESS MUST BE
 CORRECTED AS: 550 S ROSEMARY AVE # 165
 WITH PCN = 74 43 43 21 13 003 0010.
 ON THE PERMIT UNDER COMMENTS UNIT 165 IS
 DESCRIBED AS THE JOB LOCATION BUT ON THE
 SITE PLANS AND SITE PLAN REVIEW THE UNIT
 IS 162.BOTH SITE PLANS AND APPLICATION
 MUST BE REVISED.

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By lursu Date 2006-06-28 Time 08:56 Rev Time 0.00
Received By lursu Date   Time   Sent To  
Notes
2006-06-28 00:00:00UNIT 162 IS CORRECT FOR THE TENANT
 JOURNEYS SHOE
2006-06-23 00:00:00PLANS AND RESUB SHEET SHOWS SUITE #162,
 YET NO EXTENSION FOR #162 IN COMP.
 NEEDS ADDRESSING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-28 Cont ID  
Sent By lmartine Date 2006-08-28 Time 16:17 Rev Time 0.00
Received By lmartine Date 2006-08-28 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 13:30 Rev Time 0.00
Received By shill Date 2006-08-11 Time 13:30 Sent To  
Notes
2006-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)CITY PLACE STAMP REQUIRED (APPROVAL
 FROM CITY PLACE).PLANS OTHERWISE
 APPEAR CODE COMPLIANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-06 Cont ID  
Sent By shill Date 2006-07-06 Time 10:21 Rev Time 0.00
Received By shill Date 2006-07-06 Time 10:21 Sent To  
Notes
2006-07-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)SEE ELECTRIC REVIEW'S COMMENTS,
 FIRST AND SECOND REVIEWS, IN REGARDS TO
 INFORMATION REQUIRED TO BE ON THE TITLE
 BLOCK.A CERTIFICATE OF AUTHORIZATION
 IS REQUIRED FOR THE COMPANY "RESOURCE
 DESIGN" TO PRACTICE ARCHITECTURE IN
 FLORIDA, AND THIS NUMBER IS TO PRINTED
 ON EACH SHEET.FAC61G1-16.003, 004.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By shill Date 2006-05-04 Time 14:49 Rev Time 0.00
Received By shill Date 2006-05-04 Time 14:49 Sent To  
Notes
2006-05-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE ARCHITECT'S SIGNATURE IS A
 PHOTOCOPY.ORIGINAL REQUIRED.
  
 2.)PROVIDE THE DIMENSION BETWEEN THE
 EXISTING TOILET DOORS AND THE SHELVES.
 FBC1005.2, THE DOORS CANNOT REDUCE THE
 REQUIRED WIDTH TO LESS THAN ONE-HALF.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-08-25 Cont ID  
Sent By dpalmer Date 2006-08-25 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2006-08-25 Time 19:42 Sent To  
Notes
2006-08-25 00:00:00ELEC STAMPED.
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 07:12 Sent To  
Notes
2006-08-11 00:00:00IN ELEC FOR REVIEW
 ******** UNSAT 3RD REVIEW ***********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
 PLEASE ALSO SEE ANYNEW COMMENTS. NOTE
 BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW.
  
  
  
 1) NOTE: OK.
  
 2 )NOTE: OK.
  
  
 3) NOTE: NO, PLEASE SEE FBC CHAPTER 13,
 AS NOTED BELOW. PLEASE SEE NO LIGHTING
 CONTROLS REQUIRED AS OVER-RIDES ARE
 SHOWN. PLEASE SEE SAME ARTICLES AS
 REFERENCED PREVIOULY. ALL INDIVIDUAL
 SPACES WITH FLR TO CEILING PARTITIONS
 SHALL CONTAIN SEPARATE MEANS OF
 SWITCHING TO OVER-RIDE SYSTEM/TIME
 CLOCK. (BATHRMS ETC) PLEASE SEE IF USING
 A TIMER TYPE DEVICE PLANS SHALL INDICATE
 THIS AND ALSO INDICATE THE MAX OF 4HRS
 AS PERMITTED. PLEASE SEE OF USING AN
 OCCUPANCY SENSOR (MOTION,HEAT, SOUND)
 TPE DEVICES, THEN A MAX OF 30MINS ON
 OVER-RIDE SHALL BE STATED AND DEVICES
 CHOSEN SHOULD CORRELATE WITH THE DEVICES
 AS NOTED AND ON PLANS.
 PLEASE SEE OTHER AREAS SHALL CONTAIN THE
 OVER RIDES AT THE POINT OF ENTRANCE INTO
 SPACE WHERE THE OCCUPANT CAN SEE
 LIGHTING IN WHICH IS BEING
 CONTROLLED.(OVERIDEN).
 PLEASE SEE TABLES AND LIGHTING POWER
 DENSITES AS SPECIFIED IN TABLES, SEE
 CALCULATIONS ETC.
 PLEASE SEE OTHER ENERGY CALCULATIONS
 SUBMITTED ARENOT SIGNED, DATED OR
 SEALED BY THE DESIGN PROFESSIONAL AS
 REQUIRED.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1,.1.2, .1.3 FOR LIGHTING
 CONTROLS, SCHEDULING, ETC.
 PLEASE SEE 13-415.1.ABC.3,
 13.415-.1.AB.1,13-415.2.ABC.1
 PLEASE SEE NO CALCULATIONS COULD BE
 FOUND AND RESPONSE DOES NOT SEEM ANSWER
 THIS.??
 PLEASE SEE THAT THE AUTOMATED SYSTEM IS
 SHOWN, THE OVER RIDE DEVICES AND
 LOCATIONS , ALONG WITH THE TIME OF THE
 OVER RIDES DEVICES DEPENDING ON TYPE
 USED.
 PLEASE PROVIDE CALCULATIONS AS NEEDED.
  
  
 4) NOTE: NO, PLEASE SEE A FEE OF
 $1,980.00 WAS ASSESSED FOR FOUR TIMES
 FEE BASED ON THE 30% PORTION OF THE BASE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW .
 THIS FEE MUST BE PAID BEFORE PLANS CAN
 BE RESUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW, THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.
  
  
 ** NOTE 5 FOR CONTRACTOR.
 5) NOTE: NO, NEW RECORD NOC MUST BE
 SUBMTTED BEFORE PERMIT CAN BE PICKED UP.
  
 PLEASE SEE FS 713.13(2) AS THE
 NOTICE OF COMMENCEMENT SUBMITTED IN FEB
 06 HAS NOW EXPIRED. AS STATED IN THE
 FLORIDA STATUES, "IF WORK HAS NOT
 COMMENCED WITH IN 90 DAYS OF RECORDING
 NOC, THE NOC SHALL BECOME "VOID" AND
 WILL BE REQUIRED TO BE RE-RECORDED.
 PLEASE ALSO KNOW, THE "OWNER" SHALL SIGN
 NOC. PLEASE KNOW, THE OWNER AS NOTED BY
 THE CITY'S ATTORNEY'S OFFICE IS "CITY
 PLACE PARTNERS".
  
 6) NOTE: PLEASE SEE THAT ALL PLANS
 SUBMITTED FOR PERMITTING MUST CONTAIN
 THE "CITY PLACE" STAMP ON ALL SHEETS
 REVIEWED BY THE CITY PLACE
 ADMINISTRATIVE OFFICE.
 PLEASE SEE THIS IS IN AN AGREEMENT
 BETWEEN THE CITY'S LAW DEPARTMENT,
 CONSTRUCTION SERVICES DEPT ANDCITY
 PLACE ADMINISTRATION. PLEASE SEE A "CITY
 PLACE" HOLD IS CURRENTLY PLACED ON ALL
 OF THE CITY PLACE PROPERTIES.
 PLEASE OBTAIN STAMP ON ALL SHEET BEFORE
 RSUBMITTING.
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. THIS WILL TAKE
 PLACE ONCE ALL REVIEWS ARE DONE AND
 PLANS ARE PICKED UP BEFORE RSUBMITTING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 REMOVED SHEETS.
  
 ** PLEASE KNOW, A RESPONSE LETTER FROM
 THE DESIGN PROFESSIONALS IN RESPONSE TO
 COMMENTS WILL HELP IN EXPEDITING THE
 REVIEW PROCESS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 19:59 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 19:30 Sent To  
Notes
2006-06-23 00:00:00*********** UNSAT 2ND REVIEW ***********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
  
  
  
 1) NOTE: PLEASE SEE MISSING LICENSING
 INFORMATION REQUIRED ON TITLE BLOCK FOR
 ARCHITECT'S FIRM. FLORIDA ADMINISTRATIVE
 CODE61G1-16.004, FLORIDA STATUES
 481.219.
  
 2 )NOTE:PLEASE SEE ENGINEER'S TITLE
 BLOCK NOW ALSO CONTAINS A CERTIFICATE OF
 AUTHORIZATION WITHOUT THE NAME OF THE
 COMPANY FOR SAID #.
 PLEASE INCLUDE THE NAME OF THE FIRM, OR
 REMOVE THE CA #, AS THE INDIVIDUAL PE
 MAY BE THE ONLY ONE ON TITLE BLOCK.
  
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1,.1.2, .1.3 FOR LIGHTING
 CONTROLS, SCHEDULING, ETC.
 PLEASE SEE 13-415.1.ABC.3,
 13.415-.1.AB.1,13-415.2.ABC.1
 PLEASE SEE NO CALCULATIONS COULD BE
 FOUND AND RESPONSE DOES NOT SEEM ANSWER
 THIS.??
 PLEASE SEE THAT THE AUTOMATED SYSTEM IS
 SHOWN, THE OVER RIDE DEVICES AND
 LOCATIONS , ALONG WITH THE TIME OF THE
 OVER RIDES DEVICES DEPENDING ON TYPE
 USED.
 PLEASE PROVIDE CALCULATIONS AS NEEDED.
  
 ** NEW NOTES**
  
 4) NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW, THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.
  
  
 ** NOTE 5 FOR CONTRACTOR.
 5) NOTE: PLEASE SEE FS 713.13(2) AS THE
 NOTICE OF COMMENCEMENT SUBMITTED IN FEB
 06 HAS NOW EXPIRED. AS STATED IN THE
 FLORIDA STATUES, "IF WORK HAS NOT
 COMMENCED WITH IN 90 DAYS OF RECORDING
 NOC, THE NOC SHALL BECOME "VOID" AND
 WILL BE REQUIRED TO BE RE-RECORDED.
 PLEASE ALSO KNOW, THE "OWNER" SHALL SIGN
 NOC. PLEASE KNOW, THE OWNER AS NOTED BY
 THE CITY'S ATTORNEY'S OFFICE IS "CITY
 PLACE PARTNERS".
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. THIS WILL TAKE
 PLACE ONCE ALL REVIEWS ARE DONE AND
 PLANS ARE PICKED UP BEFORE RSUBMITTING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 REMOVED SHEETS.
  
 ** PLEASE KNOW, A RESPONSE LETTER FROM
 THE DESIGN PROFESSIONALS IN RESPONSE TO
 COMMENTS WILL HELP IN EXPEDITING THE
 REVIEW PROCESS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-07 Cont ID  
Sent By dpalmer Date 2006-03-07 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2006-03-06 Time 20:39 Sent To  
Notes
2006-03-07 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE BE SURE PLANS REFERENCE
 ALL CURRENT CODES AS FOLLOWS.
 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002
 NFPA-72.
 PLANS INDICATE THE 2004 FLORIDA
 ELECTRICAL CODE?
  
 2)NOTE: PLEASE SEE "A" SHEETS WHICH
 CONTAIN A RAISED SEALED OVER
 "PHOTO-COPIED" SIGNATURE OF ARCHITECT.
 PLEASE SEE FLORIDA STATUES, 481.221
 WHICH REQUIRES THE SIGNATURE TO BE
 "ORIGINAL"/"WET" SIGNATURE.
 THIS IS REQUIRED FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 3)NOTE: PLEASE SEE MISSING LICENSING
 INFORMATION REQUIRED ON TITLE BLOCK FOR
 ARCHITECT'S FIRM. FLORIDA ADMINISTRATIVE
 CODE61G1-16.004, FLORIDA STATUES
 481.219.
 PLEASE ALSO SEE MISSING THE PRINTED AR #
 THIS IS REQUIRED FOR ALL TRADES AND ON
 ALL SHEETS CONTAINING THE TITLE BLOCK
 FOR SAID ARCHITECTURAL FIRM/ ARCHITECT,
 WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 4)NOTE:PLEASE SEE ENGINEER'S TITLE
 BLOCK AS THIS IS MISSING THE "PRINTED
 LICENSE" NUMBER AS REQUIED PER FAC
 61G15-23.002.
 PLEASE SEE SEE FS 471.025 WHICH REQUIRES
 THE LEGAL SIGNATURE FOR ENGINEER. PLEASE
 SEE PLANS APPEAR TO HAVE "INITIALS"?? IF
 INDEED THIS IS THE "LEGAL SIGNATURE",
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED NOTORIZED LTR ATTESTING TO THE
 LEGAL SIGNATURE AS SHOWN.
 PLEASE KNOW THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCE
 AS NEEDED.
  
 5)NOTE: PLEASE OBTAIN THE CORRECT
 "SUITE" INFORMATION AS PERMIT
 APPLICATION MENTIONS "C-9" AND THIS IS
 NOT AN ACCURATE SUITE #.
 PLEASE ADJUST ALL TITLE BLOCKS ON PLANS
 ONCE SUITE NUMBER IS KNOWN.
 FAC 61G15-23.002, FAC 61G1-16.004
  
 6)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 &.2 FOR LIGHTING
 CONTROLS, SCHEDULING, ETC.
 PLEASE PROVIDE ALL INFORMATION AS
 SETFORTH FOR ENERGY CONSERVATION AS
 REQUIRED.
 PLEASE PROVIDE CALCULATIONS AS NEEDED.
  
 7)NOTE: PLEASE SHOW/VERIFY NEW OR
 EXISTING "SHOW WINDOW" RECEPTS AS
 REQUIRED PER 210.62. PLEAS ADJUST LOAD
 CALCUALTIONS PER 220.12A
  
 8)NOTE: PLEASE INDICATE THE TRACK
 LIGHTING LOADS PER 220.12B
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. THIS WILL TAKE
 PLACE ONCE ALL REVIEWS ARE DONE AND
 PLANS ARE PICKED UP BEFORE RSUBMITTING.
 PLEASE SUBMIT ONE SET OF ANY OLD/VOIDED
 REMOVED SHEETS.
  
 ** PLEASE KNOW, A RESPONSE LETTER FROM
 THE DESIGN PROFESSIONALS IN RESPONSE TO
 COMMENTS WILL HELP IN EXPEDITING THE
 REVIEW PROCESS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-12 Cont ID  
Sent By mcarsill Date 2006-07-12 Time 10:02 Rev Time 0.00
Received By mcarsill Date 2006-07-12 Time 10:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-04-11 Cont ID  
Sent By mwennerg Date 2006-04-11 Time 10:19 Rev Time 0.00
Received By mwennerg Date 2006-04-11 Time 10:19 Sent To  
Notes
2006-04-11 00:00:00UNIT ADDRESS SHALL BE DISPLAYED IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 18:06 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 18:06 Sent To  
Notes
2006-08-25 00:00:00TO "COMM" BD#50
2006-08-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 15:21 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 15:21 Sent To  
Notes
2006-08-09 00:00:00TO "COMM" BD#27
2006-07-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 11:04 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 11:04 Sent To  
Notes
2006-06-22 00:00:00TO "COMM" BD#34
2006-06-09 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-06 Time 16:43 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 16:52 Sent To  
Notes
2006-03-06 00:00:00TO "COMM" BD#58
2006-02-09 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-28 Cont ID  
Sent By pkrauss Date 2006-08-28 Time 15:31 Rev Time 0.00
Received By pkrauss Date 2006-08-28 Time 14:53 Sent To  
Notes
2006-08-25 00:00:00NEEDS REVIEW, NEW REVISED SHEETS DATED
 AFTER THE "P" REVIEW OF MECHNICAL ON
 7/18/06.
 SEE REVISED PLANS ARE DATED 7/19/06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-18 Cont ID  
Sent By pkrauss Date 2006-07-18 Time 15:18 Rev Time 0.00
Received By pkrauss Date 2006-07-18 Time 15:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-05 Cont ID  
Sent By hmoser Date 2006-04-05 Time 10:13 Rev Time 0.00
Received By hmoser Date 2006-04-05 Time 09:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-08-28 Cont ID  
Sent By lmartine Date 2006-08-28 Time 16:19 Rev Time 0.00
Received By lmartine Date 2006-08-28 Time 16:19 Sent To  
Notes
2006-08-28 00:00:00SEE BUILDING APPROVAL 8/28/06LM

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-08-12 Cont ID  
Sent By pschmitz Date 2006-08-12 Time 10:41 Rev Time 0.00
Received By pschmitz Date 2006-08-12 Time 09:52 Sent To  
Notes
2006-08-12 00:00:00 
  
 OK TO PRINT PERMIT WHEN COMMENTS FROM
 BUIDING AND ELECTRIC ARE APPROVED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-08 Cont ID  
Sent By pschmitz Date 2006-07-08 Time 10:25 Rev Time 0.00
Received By pschmitz Date 2006-07-08 Time 10:25 Sent To  
Notes
2006-07-08 00:00:00PROVISO:
 SHT P1 PLUMBING NOTE (4) CLEAN AND
 REFURBISH FIXTURES, NO CHANGE IN PIPING.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-05-06 Cont ID  
Sent By pschmitz Date 2006-05-06 Time 11:36 Rev Time 0.00
Received By pschmitz Date 2006-05-06 Time 11:36 Sent To  
Notes
2006-05-06 00:00:00[email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 PRVISO:
 SEE ADDITIONAL COMMENTS FROM OTHER PLAN
 REVIEWERS
  
 EXISTING H/C REST ROOMS, CLEAN FIXTURES
 ONLY.
  
 QUESTIONS 561-805-6692PAUL SCHMITZ
  
  
  