Plan Review Details - Permit 06020332
Plan Review Stops For Permit 06020332
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-04 Cont ID  
Sent By jwitmer Date 2006-10-04 Time 16:43 Rev Time 1.77
Received By jwitmer Date 2006-10-04 Time 16:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-24 Cont ID  
Sent By jwitmer Date 2006-05-24 Time 13:34 Rev Time 0.00
Received By hmoser Date 2006-10-04 Time 16:14 Sent To PC
Notes
2006-05-24 00:00:00RENOVATIONS AS A LEVEL 1 NO REMOVAL OF
 SYSTEM OR ADDITION TOO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-18 Cont ID  
Sent By jwitmer Date 2006-05-18 Time 07:27 Rev Time 0.77
Received By jwitmer Date 2006-05-18 Time 07:10 Sent To  
Notes
2006-05-18 00:00:00PERMIT: 06020332
 ADD: 213 CLEMATIS ST
 CONT: THOMAAS WILLIAMS CONSTRUCTION
 TEL: (954)802-0723
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) THE PERMIT APPLICATION AND WORK
 DESCRIBED ON PLANS DOES NOT MATCH, THIS
 REVIEW WILL BE COMPLETED WITH THE
 DESCRIPTION OF WORK DESCRIBED ON PLANS.
  
 2) THE DESCRIPTION OF WORK DESCRIBED ON
 THE PLANS IS A LEVEL 2 OF THE EXISTING
 BUILDINGS 2004 FBC. SEC 304.1 LEVEL 2
 ALTERATIONS INCLUDE THE RECONFIGURATION
 OF SPACE, THE ADDITION OR ELIMINATION OF
 ANY DOORS OR WINDOWS, THE
 RECONFIGURATION OR EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT. ALTERATIONS
 LEVEL 2, CHAPTER 6 OF THE EXISTING
 BUILDING FBC SHALL APPLY.
  
 3) PLEASE PROVIDE A CROSS SECTION BOTH
 NORTH / SOUTH AS WELL AS EAST / WEST OF
 THE SO CALLED MEZZANINE LEVEL FOR
 CLARIFICATION. PLEASE PROVIDE ELEVATIONS
  
 FLOOR TO CEILING MEASUREMENTS TO BE
 INCLUDED.
  
 3A) MEZZANINE VS SECOND STORY SEE
 DEFINITION OF MEZZANINE MUST COMMUNICATE
 WITH THE ROOM IT IS IN. IT APPEARS THERE
 IS A WALL DIVIDING THE FRONT OF THE
 BUILDING WITH THE REAR PORTION MAKING IT
  
 A SECOND STORY AND NOT A MEZZANINE.
 SEESEE 2004 FBC SECTION 502 DEFINITIONS:
  
 MEZZANINE. AN INTERMEDIATE LEVEL OR
 LEVELS BETWEEN THE FLOOR AND CEILING OF
 ANY STORY WITH AN AGGREGATE FLOOR AREA
 OF NOT MORE THAN ONE-THIRD OF THE AREA
 OF THE ROOM OR SPACE IN WHICH THE LEVEL
 OR LEVELS ARE LOCATED (SEE SECTION 505
 ).
  
 HEIGHT, STORY. THE VERTICAL DISTANCE
 FROM TOP TO TOP OF TWO SUCCESSIVE
 FINISHED FLOOR SURFACES; AND, FOR THE
 TOP MOST STORY, FROM THE TOP OF THE
 FLOOR FINISH TO THE TOP OF THE CEILING
 JOISTS OR, WHERE THERE IS NOT A CEILING,
 TO THE TOP OF THE ROOF RAFTERS.
  
 1208.2 MINIMUM CEILING HEIGHTS.
 OCCUPIABLE SPACES, HABITABLE SPACES AND
 CORRIDORS SHALL HAVE A CEILING HEIGHT OF
 NOT LESS THAN 7 FEET 6 INCHES (2286 MM).
 BATHROOMS, TOILET ROOMS, KITCHENS,
 STORAGE ROOMS AND LAUNDRY ROOMS SHALL BE
 PERMITTED TO HAVE A CEILING HEIGHT OF
 NOT LESS THAN 7 FEET (2134 MM).
  
 3B)2004 FBC EXISTING BUILDINGS 605.4
 EGRESS DOORWAYS.
 EGRESS DOORWAYS IN ANY WORK AREA SHALL
 COMPLY WITH SECTIONS 605.4.1 THROUGH
 605.4.5 .
  
 3C) 2004 FBC EXISTING BUILDING 605.4.2
 DOOR SWING.
 IN THE WORK AREA AND IN THE EGRESS PATH
 FROM ANY WORK AREA TO THE EXIT
 DISCHARGE, ALL EGRESS DOORS SERVING AN
 OCCUPANT LOAD GREATER THAN 50 SHALL
 SWING IN THE DIRECTION OF EXIT TRAVEL.
  
  
 3D) 2004 EXISTING BUILDING FBC 603.2.3
 SUPPLEMENTAL STAIRWAY ENCLOSURE
 REQUIREMENTS.
 WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS
 THAT ARE PART OF THE MEANS OF EGRESS
 SERVING THE WORK AREA SHALL, AT A
 MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT
 CONSTRUCTION ON THE HIGHEST WORK AREA
 FLOOR AND ALL FLOORS BELOW.
 PROVIDE A SECTION THROUGH STAIRWAY
 INDICATING SHAFT CONSTRUCTIONAND THE
 LOCATION OF THE WOMENS HANDICAPPED
 RESTROOM DOORWAY .
  
 3E) 2004 EXISTING BUILDING 603.4
 INTERIOR FINISH.
 THE INTERIOR FINISH OF WALLS AND
 CEILINGS IN EXITS AND CORRIDORS IN ANY
 WORK AREA SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
 3F) 2004 EXISTING BUILDING 607.4
 EXISTING STRUCTURAL MEMBERS.
 EXISTING STRUCTURAL COMPONENTS
 SUPPORTING ADDITIONAL EQUIPMENT OR
 SUBJECTED TO ADDITIONAL LOADS BASED ON
 FLORIDA BUILDING CODE, BUILDING, TABLES
 1607.1 AND 1607.6 AS A RESULT OF A
 RECONFIGURATION OF SPACES SHALL COMPLY
 WITH SECTIONS 607.4.1 THROUGH 607.4.3.
  
 607.4.1 GRAVITY LOADS.
 EXISTING STRUCTURAL ELEMENTS SUPPORTING
 ANY ADDITIONAL GRAVITY LOADS AS A RESULT
 OF ADDITIONAL EQUIPMENT OR SPACE
 RECONFIGURATION SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING .
  
 3G) PLANS DO NOT IDENTIFY DOORWAYS WITH
 ALPHA OR NUMERIC CHARACTERS, FIRST FLOOR
 DOORWAY IT APPEARS TO BE A FREEZER DOOR.
 2004 FBC 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF AN
 AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, PASSAGEWAY OR LANDING, WHEN
 FULLY OPEN. DOORS SHALL NOT OPEN
 IMMEDIATELY ONTO A STAIR WITHOUT A
 LANDING. THE LANDING SHALL HAVE A WIDTH
 AT LEAST EQUAL TO THE WIDTH OF THE DOOR.
  
 3H) DOORWAY JUST RIGHT OF THE FIRST
 FLOOR FREEZER, ELEC SHEETS INDICATE ICE
 MACHINES;
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3I) BOTH EXISTING RESTROOM DOORS SCALE
 TO BE 2'-0" DOORS , 2004 EXISTING
 BUILDING CODE 605.4 EGRESS DOORWAYS IN
 ANY WORK AREA SHALL COMPLY WITH SECTIONS
 605.4.1 THROUGH 605.4.5.
 2004 FBC 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING
 SHALL BE SUFFICIENT FOR THE OCCUPANT
 LOAD THEREOF AND SHALL PROVIDE A CLEAR
 WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH
 THE DOOR OPEN 90 DEGREES (1.57 RAD).
 2004 FBC11-4.1.6(2) DUTY TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO
 ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 % OF
 THE COST OF THE ALTERA- TION TO THE
 PRIMARY FUNCTION AREA.(A)(I) AN
 ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 4) COVER SHEET NOTE ESIXTING
 CONSTRUCTION BUILDING TYPE ?
 UNKNOWN?NOTE 4C IS REQUIRED BEFORE A
 PERMIT WILL BE ISSUED. SOME EXPLORATION
 ON THE CONTRACTORS PART MAY BE
 NECCESSARY TO DETERMINE MINIMUM BUILDING
 TYPE.
 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 5) COMPLIED.
  
 6)COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-22 Cont ID  
Sent By jwitmer Date 2006-02-22 Time 07:11 Rev Time 3.33
Received By jwitmer Date 2006-02-22 Time 07:11 Sent To  
Notes
2006-02-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06020332
 ADD: 213 CLEMATIS ST
 CONT: THOMAAS WILLIAMS CONSTRUCTION
 TEL: (954)802-0723
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) THE PERMIT APPLICATION AND WORK
 DESCRIBED ON PLANS DOES NOT MATCH, THIS
 REVIEW WILL BE COMPLETED WITH THE
 DESCRIPTION OF WORK DESCRIBED ON PLANS.
  
 2) THE DESCRIPTION OF WORK DESCRIBED ON
 THE PLANS IS A LEVEL 2 OF THE EXISTING
 BUILDINGS 2004 FBC. SEC 304.1 LEVEL 2
 ALTERATIONS INCLUDE THE RECONFIGURATION
 OF SPACE, THE ADDITION OR ELIMINATION OF
 ANY DOORS OR WINDOWS, THE
 RECONFIGURATION OR EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT. ALTERATIONS
 LEVEL 2, CHAPTER 6 OF THE EXISTING
 BUILDING FBC SHALL APPLY.
  
 3) PLEASE PROVIDE A CROSS SECTION BOTH
 NORTH / SOUTH AS WELL AS EAST / WEST OF
 THE SO CALLED MEZZANINE LEVEL FOR
 CLARIFICATION. PLEASE PROVIDE ELEVATIONS
  
 FLOOR TO CEILING MEASUREMENTS TO BE
 INCLUDED.
  
 3A) MEZZANINE VS SECOND STORY SEE
 DEFINITION OF MEZZANINE MUST COMMUNICATE
 WITH THE ROOM IT IS IN. IT APPEARS THERE
 IS A WALL DIVIDING THE FRONT OF THE
 BUILDING WITH THE REAR PORTION MAKING IT
  
 A SECOND STORY AND NOT A MEZZANINE.
 SEESEE 2004 FBC SECTION 502 DEFINITIONS:
  
 MEZZANINE. AN INTERMEDIATE LEVEL OR
 LEVELS BETWEEN THE FLOOR AND CEILING OF
 ANY STORY WITH AN AGGREGATE FLOOR AREA
 OF NOT MORE THAN ONE-THIRD OF THE AREA
 OF THE ROOM OR SPACE IN WHICH THE LEVEL
 OR LEVELS ARE LOCATED (SEE SECTION 505
 ).
  
 HEIGHT, STORY. THE VERTICAL DISTANCE
 FROM TOP TO TOP OF TWO SUCCESSIVE
 FINISHED FLOOR SURFACES; AND, FOR THE
 TOP MOST STORY, FROM THE TOP OF THE
 FLOOR FINISH TO THE TOP OF THE CEILING
 JOISTS OR, WHERE THERE IS NOT A CEILING,
 TO THE TOP OF THE ROOF RAFTERS.
  
 1208.2 MINIMUM CEILING HEIGHTS.
 OCCUPIABLE SPACES, HABITABLE SPACES AND
 CORRIDORS SHALL HAVE A CEILING HEIGHT OF
 NOT LESS THAN 7 FEET 6 INCHES (2286 MM).
 BATHROOMS, TOILET ROOMS, KITCHENS,
 STORAGE ROOMS AND LAUNDRY ROOMS SHALL BE
 PERMITTED TO HAVE A CEILING HEIGHT OF
 NOT LESS THAN 7 FEET (2134 MM).
  
 3B)2004 FBC EXISTING BUILDINGS 605.4
 EGRESS DOORWAYS.
 EGRESS DOORWAYS IN ANY WORK AREA SHALL
 COMPLY WITH SECTIONS 605.4.1 THROUGH
 605.4.5 .
  
 3C) 2004 FBC EXISTING BUILDING 605.4.2
 DOOR SWING.
 IN THE WORK AREA AND IN THE EGRESS PATH
 FROM ANY WORK AREA TO THE EXIT
 DISCHARGE, ALL EGRESS DOORS SERVING AN
 OCCUPANT LOAD GREATER THAN 50 SHALL
 SWING IN THE DIRECTION OF EXIT TRAVEL.
  
  
 3D) 2004 EXISTING BUILDING FBC 603.2.3
 SUPPLEMENTAL STAIRWAY ENCLOSURE
 REQUIREMENTS.
 WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS
 THAT ARE PART OF THE MEANS OF EGRESS
 SERVING THE WORK AREA SHALL, AT A
 MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT
 CONSTRUCTION ON THE HIGHEST WORK AREA
 FLOOR AND ALL FLOORS BELOW.
 PROVIDE A SECTION THROUGH STAIRWAY
 INDICATING SHAFT CONSTRUCTIONAND THE
 LOCATION OF THE WOMENS HANDICAPPED
 RESTROOM DOORWAY .
  
 3E) 2004 EXISTING BUILDING 603.4
 INTERIOR FINISH.
 THE INTERIOR FINISH OF WALLS AND
 CEILINGS IN EXITS AND CORRIDORS IN ANY
 WORK AREA SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
 3F) 2004 EXISTING BUILDING 607.4
 EXISTING STRUCTURAL MEMBERS.
 EXISTING STRUCTURAL COMPONENTS
 SUPPORTING ADDITIONAL EQUIPMENT OR
 SUBJECTED TO ADDITIONAL LOADS BASED ON
 FLORIDA BUILDING CODE, BUILDING, TABLES
 1607.1 AND 1607.6 AS A RESULT OF A
 RECONFIGURATION OF SPACES SHALL COMPLY
 WITH SECTIONS 607.4.1 THROUGH 607.4.3.
  
 607.4.1 GRAVITY LOADS.
 EXISTING STRUCTURAL ELEMENTS SUPPORTING
 ANY ADDITIONAL GRAVITY LOADS AS A RESULT
 OF ADDITIONAL EQUIPMENT OR SPACE
 RECONFIGURATION SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING .
  
 3G) PLANS DO NOT IDENTIFY DOORWAYS WITH
 ALPHA OR NUMERIC CHARACTERS, FIRST FLOOR
 DOORWAY IT APPEARS TO BE A FREEZER DOOR.
 2004 FBC 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF AN
 AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, PASSAGEWAY OR LANDING, WHEN
 FULLY OPEN. DOORS SHALL NOT OPEN
 IMMEDIATELY ONTO A STAIR WITHOUT A
 LANDING. THE LANDING SHALL HAVE A WIDTH
 AT LEAST EQUAL TO THE WIDTH OF THE DOOR.
  
 3H) DOORWAY JUST RIGHT OF THE FIRST
 FLOOR FREEZER, ELEC SHEETS INDICATE ICE
 MACHINES;
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3I) BOTH EXISTING RESTROOM DOORS SCALE
 TO BE 2'-0" DOORS , 2004 EXISTING
 BUILDING CODE 605.4 EGRESS DOORWAYS IN
 ANY WORK AREA SHALL COMPLY WITH SECTIONS
 605.4.1 THROUGH 605.4.5.
 2004 FBC 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING
 SHALL BE SUFFICIENT FOR THE OCCUPANT
 LOAD THEREOF AND SHALL PROVIDE A CLEAR
 WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH
 THE DOOR OPEN 90 DEGREES (1.57 RAD).
 2004 FBC11-4.1.6(2) DUTY TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO
 ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 % OF
 THE COST OF THE ALTERA- TION TO THE
 PRIMARY FUNCTION AREA.(A)(I) AN
 ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 4) COVER SHEET NOTE ESIXTING
 CONSTRUCTION BUILDING TYPE ?
 UNKNOWN?NOTE 4C IS REQUIRED BEFORE A
 PERMIT WILL BE ISSUED. SOME EXPLORATION
 ON THE CONTRACTORS PART MAY BE
 NECCESSARY TO DETERMINE MINIMUM BUILDING
 TYPE.
 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 5) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE 713.13(2) IF WORK HAS NOT BEEN
 STARTED AFTER RECORDING OF NOC IT
 BECOMES VOID REQUIRING RE-RECORDING.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-10-16 Cont ID  
Sent By dpalmer Date 2006-10-16 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2006-10-16 Time 20:42 Sent To PC
Notes
2006-10-16 20:47:47REVISED , REMOVED LIGHTING CONTROL, AS THIS IS
 CONSIDERED A SEPARATE BLDG BY DEFINITION UNDER THE FBC
 AND UNDER 5K SQ FT.
 CHAPTER 13 FOR CONTROLS NOT APPLICABLE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-29 Cont ID  
Sent By dpalmer Date 2006-09-29 Time 09:26 Rev Time 0.00
Received By dpalmer Date 2006-09-29 Time 09:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-22 Cont ID  
Sent By dpalmer Date 2006-08-22 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2006-08-22 Time 17:51 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-28 Cont ID  
Sent By dpalmer Date 2006-04-28 Time 13:18 Rev Time 0.00
Received By dpalmer Date 2006-04-28 Time 11:01 Sent To  
Notes
2006-04-28 00:00:00************ PROVISO **************
  
 1) NOTE: PLEASE SUBMIT A COMPLETE
 FIXTURE SCHEDULE WHICH CORRELATES WITH
 THE FIXTURES ON PLANS.
 RESPONSE MENTIONS TO BE DONE BY ID,
 HOWEVER THESE WERE NOT SUBMITTED.
 PLEASE KNOW, THIS SHALL BE SUBMITTED ON
 THE ELECTRICAL PLANS. THESE FIXTURES ARE
 TO CORRELATE WITH THE PLANS AND TO BE
 DONE BY THE ELECTRICAL ENGINEER OF
 RECORD.
 THIS SHALL INCLUDE ALL FIXTURES, EM LTS,
 EXT LTS, ETC.
 ** PLEASE KNOW, WE ARE UNABLE TO VERIFY
 CODE COMPLIANCE WITH THE FBC CHAPTER 13
 AT THIS TIME.
  
 ************* NOTE *************
  
 PLEASE SUBMIT THIS BEFORE THE "ROUGH"
 ELECTRICAL INSPECTION IS CALLED IN.
 PLEASE INCLUDE WITH ANY OTHER REVISIONS.
 PLEASE KNOW, IF PLANS COME BACK WITH ANY
 OTHER COMMENTS FROM TRADES, PLEASE
 REVISE AT THAT TIME TO AVOID SUBMITTING
 REVSIONS AT A LATER DATE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 17:51 Sent To PC
Notes
2006-02-22 00:00:00********UNSAT *********
  
 1)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FS
 471.025 WHICH REQUIRES THE PLANS TO BE
 SIGNED , DATED AND SEALED BY THE
 ENGINEER OF RECORD. PLEASE ALSO SEE FS
 481.221 FOR ARCHITECT'S.
 PLEASE SEE ONE SET OF PLANS ARE
 PHOTO-COPIES OF SIGNED, AND SEALED
 PLANS.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE BE SURE PLANS REFERENCE
 AND INDICATE THE CURRENT CODES AS
 FOLLOWS ON ELECTRICAL, ARCHITECTURAL AND
 FIRE SHEETS.
 2003 NFPA-101,2002 NFPA-72, NFPA-70 2002
 PLEASE ALSO VERIFY WITH OTHER NOTES
 PERTIAING TO KITCHEN AND ANY POSSIBE
 HOODS PER NFPA-96 2001.
  
 3)NOTE: PLEASE SEE SCOPE OF WORK
 INDICATED ON PERMIT APPLICATION DOES NOT
 CORRELATE WITH THE SUBMITTED PLANS.
 PLEASE SEE PLANS INDICATE KITCHEN WORK
 ETC, YET APPLICATION MENTIONS BAR ONLY??
 SEE COMMENTS FROM OTHER TRADES, AS PLANS
 ALSO INDICATE REMOVAL OF KITCHEN
 EQUIPMENT??
  
 4)NOTE: PLEASE SEE NOT ON PLANS MENTIONS
 ALL RECEPTS WITH IN"6" INCHES (") OF
 SINKS SHALL BE GFI?
 PLEASE SEE 2002 NEC 210.8B3 ETC FOR
 RECEPTS WITH IN 6' (FEET) AND ALL
 15A/20A 125V RECEPTS WITHIN A KITCHEN
 SHALL BE GFI/GFI PROTECTED.
  
 5)NOTE: PLEASE VERIFY LIGHTING CONTACTOR
 BEING REMOVED AND REQUIREMENTS OF FBC
 CHAPTER 13, 13-415.1.ABC.1.1, IT DOES
 NOT SEEM IT IS PERMITTED TO REMOVE THE
 AUTOMATIC MEANS OF LIGHTING SHUT OFF
 UNLESS MEETING THE REQUIREMENTS AND
 PROVIDING NEW MEANS.??
  
 6)NOTE: PLEASE CLARIFY NEW OR EXSITING
 WINDOW RECEPTS ABOVE WINDOWS, 210.62,
 220.12.
  
 7)NOTE: PLEASE CLARIFY/SHOW NEW OR
 EXISTING SIGN CIRCUIT. 600.5
  
 8)NOTE: PLEASE SHOW ALL CONTINUOUS AND
 LARGEST MOTOR LOADS AT 125%.
 215.3,230.42 ETC.
 PLEASE SHOW LOAD CALCULATIONS PER NEC.
  
 9)NOTE: PLEAS VERIFY OCP FOR FACP IS
 SHOWN AS 2POLE 20?
 215.5
  
 10)NOTE: COULD NOT LOCATE A FIXTURE
 SCHEDULE TO CORRELATE WITH THE FIXTURES
 AS NOTED ON PLANS?
 PLEASE SUBMIT.
  
 ** PLEASE SEE OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS FROM SETS OF PLANS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-18 Cont ID  
Sent By nmccray Date 2006-05-18 Time 09:56 Rev Time 0.00
Received By nmccray Date 2006-05-02 Time 10:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By mcarsill Date 2006-02-15 Time 17:08 Rev Time 0.00
Received By mcarsill Date 2006-02-15 Time 17:08 Sent To  
Notes
2006-02-15 00:00:001. DEMOLITION, CONSTRUCTION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. EXITS ARE TO REMAIN CLEAR.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 4. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM ADDITION.
  
 5. SEPERATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT, AND SUPPRESSION SYSTEM.
  
 6. ON PAGE AO PLANS INDICATE SPACE IS
 NOT FIRE SPRINKLER PROTECTED BUT ON PAGE
 A2.0 IT INDICATES THAT FIRE SPRINKLERS
 EXIST. PLEASE ADVISE.
  
 7. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 8. ANY STORAGE OR ELECTRIC PLANNED FOR
 UNDERNEATH OF ELEVATED PLATFORM.
  
 9. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 10. PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF 100 OR
 MORE PERSONS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-11 Cont ID  
Sent By adarroug Date 2006-10-11 Time 10:28 Rev Time 0.00
Received By adarroug Date 2006-10-11 Time 10:28 Sent To E
Notes
2006-10-11 10:28:59TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 18:05 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 18:05 Sent To  
Notes
2006-09-27 00:00:00TO "BOB"#17
2006-09-23 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 17:11 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 17:11 Sent To E
Notes
2006-08-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 11:30 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 11:30 Sent To  
Notes
2006-04-27 00:00:00TO BOB 13
2006-04-21 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-02-22 Time   Rev Time 0.00
Received By adarroug Date 2006-02-08 Time 13:20 Sent To  
Notes
2006-02-08 00:00:00TO "BOB"#2

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-04 Cont ID  
Sent By hmoser Date 2006-10-04 Time 16:14 Rev Time 0.00
Received By hmoser Date 2006-10-04 Time 16:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-03 Cont ID  
Sent By tgordon Date 2006-05-03 Time 08:39 Rev Time 0.20
Received By tgordon Date 2006-05-03 Time 08:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By hmoser Date 2006-02-15 Time 14:46 Rev Time 0.00
Received By hmoser Date 2006-02-15 Time 14:46 Sent To  
Notes
2006-02-15 00:00:00PLAN DENIED
 PLEASE REFER TO CHAPTER 1 ADMINISTRATION
 2004 ADITION,SECTION 106.1 AND CHAPTOR
 471 FLORIDA STATUTES.TWO OR MORE SETS OF
 PLANS WITH OFFICIAL SEAL SIGNATURE AND
 DATE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-04 Cont ID  
Sent By jleech Date 2006-05-04 Time 10:19 Rev Time 0.00
Received By jleech Date 2006-05-04 Time 10:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-22 Cont ID  
Sent By jleech Date 2006-02-22 Time 14:14 Rev Time 4.00
Received By jleech Date 2006-02-22 Time 14:14 Sent To  
Notes
2006-02-22 00:00:00DENIED;
 1)DRINKING FOUNTAIN REQUIRED. SEE
 FBC-2004 PLUMBING TABLE 403.1 (A-2) AND
 410.1.
 2)SANITARY DRAIN FROM BAR AREA AND
 MEZZANINE MUST GO TO SANITARY NOT TO
 GREASE TANK. GREASE TANK SHALL BE CAPED
 OF AT BOTH END, PUMPED AND SANITIZED.
 3)5' TURNING RADIUS DOES NOT EXIST IN
 MENS HANDICAP BATHROOM SHOW WHERE THE
 20% RULE WILL BE USED. ONE URINAL MUST
 BE HANDICAP. SHOW DETAIL ON PLANS, PER.
 FBC-2004 CHAPTER 11 SEC. 11-4.18.1 THRU
 11-4.18.4.
 4)ICE MACHINE DETAIL PAGE P-4 SEPARATE
 DRAIN LINES ARE REQUIRED FOR CUBER AND
 ICE BIN.
 5)EQUIPMENT SCHEDULE MISSING. ( NEEDED
 TO COMPLETE PLUMBING PLAN REVIEW.
 6)ONE SET OF PLANS NOT SEALED.
 7)IF COOKING COOKING EQUIPMENT WAS GAS
 ALL GAS PIPING MUST BE REMOVED BY A GAS
 CONTRACTOR, DEMO PERMIT REQUIRED. ADD
 NOTE ON DEMO PLAN.
 8)PLUMBING FIXTURES, FLOOR DRAINS, AND
 FLOOR SINKS IN KITCHEN AREA MUST BE
 REMOVED SO NO DEAD ENDS EXIST. (NOT
 SHOWN ON DRAWINGS) SHOW ALL DEMO WORK.
 9)PLANS TO BE REVIEWED AND APPROVED BY
 THE HEALTH DEPARTMENT BEFORE RESUB TO
 WPB. CONTACT NAN MC DERMIT
 901 EVERNIA ST
 WPB
 355-3018
 10.WATER RISER. REMOVE AIR CHAMBER
 SYMBALS. LOWER THE WATER HAMMER
 ARRESTORS DOWN. ARRESTORS ARE TO BE
 INSTALLEDCLOSE TO FIXTURES PER
 MANUFACTORS INSTALLATION INSTRUCTIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-14 Cont ID  
Sent By mflis Date 2006-02-14 Time 08:47 Rev Time 0.00
Received By mflis Date 2006-02-14 Time 08:47 Sent To  
Notes
***NONE***