Plan Review Details - Permit 06020320
Plan Review Stops For Permit 06020320
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-02-10 Cont ID  
Sent By lursu Date 2006-02-10 Time 10:31 Rev Time 0.00
Received By lursu Date 2006-02-10 Time 10:28 Sent To  
Notes
2006-02-10 00:00:00CREATE EXTENSION #0002 FOR THE SUITE
 1006

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-13 Cont ID  
Sent By rmcdouga Date 2006-02-13 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2006-02-13 Time 11:20 Sent To  
Notes
2006-02-13 00:00:00DENIED
  
 1)NEW DOOR MUST COMPLY WITH FAIR HOUSING
 REQUIREMENTS. USEABLE DOORS MUST PROVIDE
 A NOMINAL 32" CLEAR OPENING OF AT LEAST
 31-5/8 INCHES CLEAR.
  
 2) SPECIFY THE MATERIAL THAT WILL BE
 USED TO FRAME THE INTERIOR WALLS.
 PARTITIONS MUST BE CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS. FBC 603
  
 3) A MECHANICAL PERMIT WIL BE REQUIRED
 TO PROVIDE FOR RETURN AIR FROM THE
 DEN/STUDY WHEN THE OPENING IS ENCLOSED
 BY A WALL AND DOOR.
  
 4) ELECTRICAL CODE REQUIRES SMOKE
 DETECTORS AND ARC FAULT PROTECTED
 CIRCUITS IN BEDROOMS.
  
 5) INTERIOR WALL AND FLOOR FINISHES
 SHALL COMPLY WITH CHAPTER 8 OF THE 2004
 FBC.
  
 6) THIS PROJECT IS LOCATED IN AN R2
 CONDO AND NOT AN R3 ONE OR TWO FAMILY
 RESIDENCE AND DOES NOT QUALIFY FOR THE
 OWNER BUILDER EXCEPTION, THEREFORE, A
 LICENSED CONTRACTOR IS REQUIRED TO PULL
 A PERMIT FOR THIS PROJECT. SEE ATTACHED
 COPY OF STATE STATUTE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-02 Cont ID  
Sent By rmcdouga Date 2006-03-02 Time 14:25 Rev Time 0.45
Received By rmcdouga Date 2006-03-02 Time 14:19 Sent To  
Notes
2006-03-02 00:00:00SEE NOTES ON PLANSJL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-23 Cont ID  
Sent By nmccray Date 2006-02-23 Time 14:24 Rev Time 0.00
Received By nmccray Date 2006-02-23 Time 14:08 Sent To  
Notes
2006-02-23 00:00:00DENIED:
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE 2003 EDITION.
  
 2) INTERIOR FINISH FOR WALL AND CEILING
 SHALL COMPLY WITH SECTION 10.2, AND
 SHALL BE CLASS A, CLASS B, OR CLASS C.
  
 3) SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 4)PLEASE VERIFY AND CONFIRM THAT THE
 CLOSET IS LESS THAN 12 SQ FT. IF NOT IT
 IS REQUIRED TO BE FIRE SPRINKLER
 PROTECTED.
  
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-01 Cont ID  
Sent By rmcdouga Date 2006-03-01 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2006-02-09 Time 16:20 Sent To  
Notes
2006-02-09 00:00:00TO "BOB"#6