Plan Review Details - Permit 06020313
Plan Review Stops For Permit 06020313
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-27 Cont ID  
Sent By alange Date 2006-10-27 Time 13:17 Rev Time 0.00
Received By alange Date 2006-10-27 Time 13:16 Sent To  
Notes
2006-10-27 13:17:25"S"PAGES OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-17 Cont ID  
Sent By alange Date 2006-05-17 Time 12:44 Rev Time 1.25
Received By alange Date 2006-05-17 Time 12:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-02 Cont ID  
Sent By btrobaug Date 2006-05-02 Time 16:11 Rev Time 1.00
Received By alange Date 2006-05-02 Time 08:28 Sent To  
Notes
2006-05-02 00:00:00DENIED
  
 3.SUBMIT SPECS FOR BBQ AND REQUIRED
 HOOD.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.SIGN OWNER AGENT ON
 CALCS.
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TO BE SUBMITTED AND APPROVED PRIOR TO
 INSTALLATION.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-27 Cont ID  
Sent By alange Date 2006-03-27 Time 09:02 Rev Time 2.50
Received By alange Date 2006-03-27 Time 09:02 Sent To  
Notes
2006-03-27 00:00:00DENIED
  
 1.713.13F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT SPECS FOR BBQ AND REQUIRED
 HOOD.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 LINTELS, STRAPS AND TIE-DOWNS.TWO
 COMPLETE SETS OF PRODUCT APPROVALS WITH
 STATE APPROVAL REQUIRED.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-24 Cont ID  
Sent By btrobaug Date 2006-10-24 Time 07:46 Rev Time 1.00
Received By btrobaug Date 2006-10-24 Time 06:52 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-02 Cont ID  
Sent By btrobaug Date 2006-04-24 Time 17:46 Rev Time 0.50
Received By btrobaug Date 2006-04-24 Time 17:16 Sent To B
Notes
2006-04-24 00:00:00 

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-22 Cont ID  
Sent By btrobaug Date 2006-02-22 Time 17:27 Rev Time 0.50
Received By btrobaug Date 2006-02-22 Time 17:05 Sent To B
Notes
2006-02-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF
 ELECTRICAL EQUIPMENT ON THE STRUCTURE
 BEING PERMITTED. IF THE SERVICE SHOWN ON
 SHEET A-3 IS FOR THIS STRUCTURE,
 INDICATE OVERHEAD OR UNDERGROUND, REMOVE
 OPTION.
  
 2} INDICATE COMPLIANCE WITH 225.32 AND
 250.32, DISCONNECTING AND GROUNDING @
 SEPERATE STRUCTURE, IF BEING FED FROM
 MAIN SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 11:59 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 11:59 Sent To Z
Notes
2006-10-18 11:59:44TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-10 Cont ID  
Sent By adarroug Date 2006-05-10 Time 16:43 Rev Time 0.00
Received By adarroug Date 2006-05-10 Time 16:43 Sent To Z
Notes
2006-05-10 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 15:11 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 15:11 Sent To E
Notes
2006-04-24 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 17:34 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 17:34 Sent To E
Notes
2006-02-13 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-27 Cont ID  
Sent By alange Date 2006-03-27 Time 09:08 Rev Time 0.00
Received By alange Date 2006-02-08 Time 15:14 Sent To  
Notes
2006-02-08 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-13 Cont ID  
Sent By mmclean Date 2006-02-13 Time 14:01 Rev Time 0.00
Received By mmclean Date 2006-02-13 Time 14:01 Sent To I
Notes
***NONE***