| Notes |
| 2006-02-06 00:00:00 | REDLINED PLANS: | | | | | | ** CWP TO BE PART OF GE SYSTEM, 250.50 | | | | | | ** REMOVE THE EQUIPMENT GROUNDING | | | CONDUCTOR SHOWN IN PICTURES SUBMITTED. | | | PLEASE SEE 250.6, 250.24, THE EQUIPMENT | | | GROUNDING CONDUCTOR IS ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISCONNECT. |
|
|
|