| 2006-03-11 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE DRAINAGE PLANS AS REQUIRED BY |
| | SEC. R401.3 OF 2004 RESIDENTIAL CODE. |
| | |
| | 2- PROVIDE STRUCTURAL BUCK DETAIL USING |
| | 2X BUCK AS REQUIRED BY ENTRY DOOR |
| | PRODUCT APPROVAL SUBMITTED. SEE SECTION |
| | R613.6.2 2004 RESIDENTIAL CODE FOR |
| | PROPER BUCK INSTALLATION. |
| | |
| | 3- OWES $306.73 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | |
| | 4- PROVIDE SPECS/DETAILS FOR |
| | INSTALLATION OF DECORATIVE STORM |
| | SHUTTERS. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 5- DRAWINGS S-1, S-2 AND S-3 ARE MISSING |
| | THE ENGINEER'S INFORMATION AS REQUIRED |
| | BY CHAPTER 471 FLORIDA STATUTES. |
| | |
| | 6- A) PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR FRENCH DOORS WITH TRANSOM |
| | ABOVE SINGLE UNIT AS SHOWN ON PLANS OR |
| | PROVIDE COMPLETE INFORMATION FOR |
| | STRUCTURAL MULLION AS REQUIRED BY SEC. |
| | R613.7 2004 RESIDENTIAL CODE. |
| | B) SPECIFY SIZE OF FIXED WINDOW. |
| | |
| | 7- ARCHITECT TO PROVIDE ALLINFORMATION |
| | ON TITLE BLOCK AS REQUIRED BY CHAPTER |
| | 481 FLORIDA STATUTES AND 61G1-16.004 OF |
| | ADMINISTRATIVE CODE. SEE ATTACHED COPY. |
| | |
| | 8- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL AS REQUIRED BY RULE 9B-72 FOR: |
| | A) FRENCH DOORS WITH TRANSOM ABOVE. |
| | OR FRENCH DOORS ALONE. SEE ITEM #7 ABOVE |
| | B) STRUCTURAL MULLIONS. SEE ITEM #7. |
| | C) FIXED WINDOWS. SEE ITEM #7 ABOVE. |
| | D) ALL TRUSS CONNECTORS. SEE PLANS. |
| | E) SINGLE HUNG WINDOWS. DADE COUNTY |
| | NOA TO MATCH NOA SUBMITTED FOR FLORIDA |
| | APPROVAL. VISIT WWW.FLORIDABUILDING.ORG |
| | TO DOWNLOAD CORRESPONDING NOA. |
| | F) ROOF SHINGLES. PROVIDE SAME NOA |
| | SUBMITTED FOR FLORIDA PRODUCT APPROVAL. |
| | G) PRECAST LINTELS. |
| | H) ALUMINUM VENTS. |
| | I) ALUMINUM SIDING. |
| | |
| | 9- DESIGNER OF RECORD TO REVIEW AND |
| | APPROVE IN WRITTING ALL PRODUCT |
| | APPROVALS PRIOR TO SUBMITTAL TO THIS |
| | OFFICE AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 10- DRAWING 1: UPDATE BUILDING CODE |
| | DATA. SEE 2004 RESIDENTIAL CODE. |
| | |
| | 11- DRAWING A-1: A) SPECIFY SAFETY GLASS |
| | FOR WINDOW IN BATHROOM. SEE PLANS. SEC. |
| | R308.4 2004 RESIDENTIAL CODE. |
| | B) UPDATE CODE REFERENCE FOR ATTIC |
| | ACCESS. SEE 2004 RESIDENTIAL CODE. |
| | C) UPDATE CODE REFERENCES SPECIFIED |
| | ON GENERAL NOTES AND SCHEDULE NOTES. SEE |
| | 2004 RESIDENTIAL CODE. |
| | |
| | 12- DRAWING A-2: A) SPECIFY SIZE OF |
| | MANUFACTURED ALUMINUM LOUVER AT FRONT |
| | AND BACK. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | B) WIND PRESSURES LETTER SHOWN ON |
| | ELEVATIONS DON'T MATCH LETTER SHOWN IN |
| | DESIGN PRESSURES CHART. REVISE AS REQ'D. |
| | |
| | 13- DRAWING A-3: A) WHERE IS DETAIL A-5" |
| | SPECIFIED ON PLANS? |
| | B) SECTION "A": 1) WHERE IS DETAIL |
| | SHT 5? |
| | 2) WHERE IS DETAIL SHT 5 FOR WOOD |
| | COLUMN SURROUND? |
| | 3) WHERE IS THE CONCRETE SIDEWALK?. |
| | SEE SITE PLAN. |
| | |
| | 14- DRAWING A-4: A) WALL SECTION "A". |
| | UPDATE CODE REFERENCE SPECIFIED FOR |
| | FIREBLOCKING AND SPECIFY FIREBLOCKING |
| | MATERIAL. SEE 2004 RESIDENTIAL CODE. |
| | B) WALL SECTION "B". FOUNDATION PLAN |
| | DOESN'T MATCH PLANS. REVISE AS REQUIRED. |
| | C) PORCH BEAM IS NOT AN ARCHED BEAM. |
| | REVISE AS REQUIRED. SEE PLANS. |
| | |
| | 15- DRAWING S-1: A) PROVIDE COMPLETE |
| | DETAILS AND SPECS FOR WOOD DECK AND WOOD |
| | STEPS AT REAR AREA. SPECIFY ALL |
| | FASTENERS. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | B) SPECIFY ROOF TRUSS CONNECTORS. |
| | C) WHERE ARE DETAILS C AND E? |
| | KEY DETAILS TO MATCH DRAWINGS. |
| | |
| | 16- DRAWING S-2: A) TYP. 1 STORY |
| | SECTION: SPECIFY SIZE AND LOCATION OF |
| | ATTIC VENTS. ALSO, CONSIDER ALUMINUM |
| | VENTS FOR TOTAL VENTING AREA REQUIRED. |
| | SEC. R806 2004 RESIDENTIAL CODE. |
| | B) DETAIL D: 1) HOW IS 2"X6" SILL |
| | PLATE ATTACHED TO CONCRETE BEAM? |
| | 2) HOW IS 2" X 6" "L" BRACE NAILED TO |
| | BOTTOM SILL? |
| | 3) USP TA18 IS SHOWN AS BEING |
| | ATTACHED TO CONCRETE BEAM. SEE USP |
| | CATALOGUE FOR PROPER INSTALLATION AND |
| | FASTENERS. REVISE AS REQUIRED. |
| | 4) DETAIL A: SHOW COMPLETE DETAILS |
| | AND SPECS FOR CONCRETE STEPS AT ENTRY |
| | PORCH. |
| | |
| | 17- DRAWING S-3: A) GENERAL NOTES: |
| | UPDATE ALL REFERENCE STANDARDS AND |
| | SPECIFIC EDITION TO BE USED. SEE 2004 |
| | RESIDENTIAL CODE AND 2004 FBC CHAPTER |
| | 35. |
| | B) UPDATE CODE SECTIONS REFERENCED |
| | FOR WIND LOADS, EMERGENCY EGRESS AND |
| | GLASS IMPACT PROTECTION NOTES. |
| | C) VENTILATION AND EGRESS ARE TWO |
| | DIFFERENT CODE ISSUES.REVISE AS REQ'D. |
| | D) TRUSS ANCHOR SCHEDULE: NUMBER OF |
| | NAILS AND UPLIFT LOADS TO MATCH CURRENT |
| | USP CATALOGUE. OTHERWISE, PROVIDE |
| | COMPLETE ENGINEERING ANALYSIS FOR NUMBER |
| | AND UPLIFT LOADS THAT DIFFER THOSE |
| | PUBLISHED BY MANUFACTURER. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | E) DELETE NOTES CORRESPONDING TO |
| | STRUCTURE ADDITIONS. THEY DON'T APPLY TO |
| | THIS PROJECT. |
| | |
| | 18- A) SURVEY TO HAVE SURVEYOR'S |
| | ORIGINAL SIGNATURE, NOT COPY, AS |
| | REQUIRED BY CHAPTER 472 FLORIDA |
| | STATUTES. |
| | B) PROPERTY IS LOCATED ON FLOOD ZONE |
| | C, NOT B. REVISE AS REQUIRED. COMMUNITY |
| | PANEL 120229 0015 B, MARCH 1ST 1979. |
| | |
| | 19- STORM SHUTTERS: |
| | A) PROVIDE KEY PLAN. |
| | B) PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. PROVIDE |
| | ALL INFORMATION. |
| | |
| | 20- ENERGY CALCULATIONS: |
| | A) USE 2004 FORM, NOT 2001. |
| | B) A/C AREA DOESN'T MATCH A/C AREA |
| | SHOWN IN PLANS. REVISE AS REQUIRED. |
| | C) OWNER/AGENT TO SIGN BOTTOM OF FORM |
| | D) IF CALCULATIONS ARE NOT DONE FOR |
| | WORST CASE SCENARIO, THEN. THEY MUST |
| | MATCH ACTUAL HOUSE ORIENTATION. SEE |
| | SURVEY FOR HOUSE ORIENTATION AND REVISE |
| | CALCULATIONS AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |