Plan Review Details - Permit 06020258
Plan Review Stops For Permit 06020258
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-20 Cont ID  
Sent By rbrown Date 2007-02-20 Time 19:36 Rev Time 0.00
Received By rbrown Date 2007-02-20 Time 19:36 Sent To  
Notes
2007-02-20 19:39:53LETTER FROM GENERAC SIGNED AND SEALED BY RICHARD W.
 LINCOLN, P.E., WISCONSIN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-22 Cont ID  
Sent By lmartine Date 2006-12-22 Time 12:52 Rev Time 0.00
Received By lmartine Date 2006-12-22 Time 12:52 Sent To  
Notes
2006-12-22 13:14:59LETTER FROM GENERAC DATED 12/6/06 IS NOT ACCEPTABLE.
  
 LETTER SHALL BE SIGNED AND SEALED BY A PROFESSIONAL
 ENGINEER PROPERLY REGISTERED IN THE STATE OF FLORIDA.
  
 ALSO NOT NOTED AT PERMIT ISSUE, A FLOOD ZONE ELEVATION
 CERTIFICATE WILL BE REQUIRED BEFORE C. O., MIN.
 ELEVATION SHALL BE RECORDED AT 7.5' OR HIGHER.
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-10 Cont ID  
Sent By alange Date 2006-03-10 Time 15:50 Rev Time 0.50
Received By alange Date 2006-03-10 Time 15:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-04 Cont ID  
Sent By btrobaug Date 2007-05-04 Time 10:57 Rev Time 0.50
Received By btrobaug Date 2007-05-04 Time 10:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-23 Cont ID  
Sent By btrobaug Date 2007-04-23 Time 14:32 Rev Time 1.00
Received By btrobaug Date 2007-04-23 Time 09:07 Sent To PC
Notes
2007-04-23 09:21:17 
  
 REVISION DENIED/INCOMPLETE INFORMATION.
  
 THE RISER NOW HAS TWO ATS SERVING TWO 200 AMP PANELS.
 BECAUSE OF THE SYSTEM CHANGE THE FOLLOWING IS
 REQUIRED.
  
 1} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. THE RISER NOW HAS
 TWO ATS SERVING TWO 200 AMP PANELS.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL(S). 106.3.5.4 FBC AS
 AMENDED.
  
 3} THE PERMITTED GENERATOR WAS A 40 KW. THE REVISION
 INDICATES A 45KW. IF A GENERATOR OTHER THAN THE ONE ON
 THE PERMITTED SET OF PLANS IS TO BE INSTALLED, SUBMIT
 SPECIFICATIONS FOR SAME,
  
 4} PROVIDE SPECIFICATIONS FOR THE ADDED TRANSFER
 SWITCH.
  
 5} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 6} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING,
 AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-20 Cont ID  
Sent By btrobaug Date 2006-12-20 Time 18:00 Rev Time 0.25
Received By btrobaug Date 2006-12-20 Time 17:49 Sent To B
Notes
2006-12-20 18:00:33 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE DOCUMENT SUBMITTED BY RICHARD LINCOLN REGARDING
 MINIMUM CLEARANCES FROM STRUCTURES IS NOT ACCEPTABLE.
 THE MANUFACTURER MUST INDICATE THE MINIMUM OPERATING
 CLEARANCE FOR VENTILATION AND FROM COMBUSTUBLES FOR THE
 UNIT AS TESTED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-01 Cont ID  
Sent By btrobaug Date 2006-03-01 Time 11:40 Rev Time 0.50
Received By btrobaug Date 2006-03-01 Time 11:30 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-12-20 Cont ID  
Sent By pschmitz Date 2006-12-20 Time 15:21 Rev Time 0.00
Received By pschmitz Date 2006-12-20 Time 14:46 Sent To  
Notes
2006-12-20 15:19:25 
 PAUL SCHMITZ
  
 561-805-6692
 [email protected]
 FBC 2004 PLUMBING CODE PLAN
 REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 DENIED
  
  
  
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
  
  
  
  
  
 1) NOTE: THE LETTER SUBMITTED FROM THE MANUFACTURE
 DATED 12/6/06 DOES NOT SPECIFY THE MINIMUM CLEARANCE
 ALLOAWANCE FOR THIS SPECIFIC SITE ADDRESS. THE MINIMUM
 CLEARANCES WILL NOT BE DETEREMINED BY THE AUTHORITY
 HAVING JURISDICTION.
 PLEASE SUBMIT A "SITE SPECIFIC" LETTER FROM A FLORIDA
 REGISTERED ENGINEER ACCEPTING AND STATING THE MINIMUM
 CLEARANCE AS LOCATED ON JOBSITE.
 IT IS THE DETERMINATION AND UNDERSTANDING FROM THIS
 REVIEWER THAT CITY OF WEST PALM BEACH WILL NOT BE
 RESPONSIBLE FOR THE "SUFFICIENT ROOM" ALLOWANCES.
 THIS SHALL BE EITHER STATED AND/OR DETERMINED BY THE
 MANUFACTURE OR BY THE ENGINEER AS STATED ABOVE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 ALSO AFFECT THIS REVIEW OF THE SUBMITTED LETTER.
 QUESTIONS

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-03 Cont ID  
Sent By mperson Date 2006-03-03 Time 16:27 Rev Time 0.00
Received By mperson Date 2006-03-03 Time 16:27 Sent To B
Notes
2006-03-03 00:00:00GAS PERMIT SUBMITTED UNDER #06020260

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 14:59 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 14:59 Sent To E
Notes
2007-05-01 14:59:30TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 13:41 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 13:41 Sent To E
Notes
2007-04-16 13:41:48TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 16:31 Sent To P
Notes
2007-02-01 16:31:48TO "PSCHMITZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-19 Cont ID  
Sent By rbrown Date 2006-12-19 Time 18:42 Rev Time 0.00
Received By rbrown Date 2006-12-19 Time 18:42 Sent To  
Notes
2006-12-19 18:43:38SUBMITTAL ROUTED TO PAUL SCHMITZ DESK.LETTER FROM
 MANUFACTURER'S ENGINEER FOR REQUIRED CLEARANCES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 08:33 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 08:33 Sent To E
Notes
2006-02-13 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-10 Cont ID  
Sent By alange Date 2006-03-10 Time 15:50 Rev Time 0.00
Received By alange Date 2006-02-08 Time 11:30 Sent To  
Notes
2006-02-08 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-03-02 Cont ID  
Sent By tgordon Date 2006-03-02 Time 09:50 Rev Time 0.15
Received By tgordon Date 2006-03-02 Time 09:49 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-03-03 Cont ID  
Sent By mperson Date 2006-03-03 Time 16:26 Rev Time 0.00
Received By mperson Date 2006-03-03 Time 16:26 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-10 Cont ID  
Sent By mmclean Date 2006-02-10 Time 18:02 Rev Time 0.00
Received By mmclean Date 2006-02-10 Time 18:02 Sent To I
Notes
***NONE***