Plan Review Details - Permit 06020129
Plan Review Stops For Permit 06020129
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-06 Cont ID  
Sent By jwitmer Date 2006-04-06 Time 08:30 Rev Time 1.55
Received By jwitmer Date 2006-04-06 Time 08:30 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-16 Cont ID  
Sent By jwitmer Date 2006-03-16 Time 09:36 Rev Time 2.22
Received By jwitmer Date 2006-03-16 Time 09:36 Sent To PC
Notes
2006-03-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06020129
 ADD: 1801 PALM BCH LAKES# 230C
 CONT:PLAN REVIEW
 GENERAL GROWTH C/O ASHLEY
 STEWART
 TEL: (201)319-9093
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) SHEET T1.0 CODE INFORMATION
 1A)COMPLIED.
 1B)COMPLIED.
 1C)COMPLIED.
 1D) ALL CODE REFRENCES AND TABLES ARE
 NOT 2004 FBC.
 THE NEW T1.0 SHEET INDICATESTHE NEW
 TABLE 601 FOR BUILDING CLASSIFICATION,
 BUT THE WRONG BUILDING TYPE. PLANS
 INDICATE A TYPE IV BUILDING WHICH UNDER
 THE 2004 CODE IS HEAVY TIMBER.
  
  
 2) A1.0 & A2.0 THE REAR EGRESS DOES NOT
 MEET THE MANEUVERING CLEARENCES OF A
 DOOR 12" REQUIRED PUSH SIDE OF LATCH
 WHEN A DOOR CLOSER AND LATCH ARE
 PRESENT.11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3)COMPLIED.
  
 NEW COMMENTS DUE TO THE REDESIGN OF THE
 FLOOR PLAN.
  
 4) THE EGRESS PATH FROM THE FRONT OF THE
 STORE TO THE STORAGE AREA, THE DOORWAY
 THAT ENTERS THE STOREROOM DOES NOT MEET
 THE MANEUVERING CLEARENCES. 11-4.13.6
 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 5) DRESSING ROOMS VERSES DOOR SWING.
 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF AN
 AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, PASSAGEWAY OR LANDING, WHEN
 FULLY OPEN. DOORS SHALL NOT OPEN
 IMMEDIATELY ONTO A STAIR WITHOUT A
 LANDING. THE LANDING SHALL HAVE A WIDTH
 AT LEAST EQUAL TO THE WIDTH OF THE DOOR.
 THE SECOND ISSUE IS THAT IT APPEARS THAT
 THE HANDICAPPED DRESSING ROOM IS THE
 ROOM BEHIND THE COMMON DRESSING ROOM
 MAKING IT HARDER FOR TURNING AND ALSO
 ACCESSIBLITY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-16 Cont ID  
Sent By jwitmer Date 2006-02-16 Time 08:12 Rev Time 1.11
Received By jwitmer Date 2006-02-16 Time 08:12 Sent To  
Notes
2006-02-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06020129
 ADD: 1801 PALM BCH LAKES# 230C
 CONT:PLAN REVIEW
 GENERAL GROWTH C/O ASHLEY
 STEWART
 TEL: (201)319-9093
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) SHEET T1.0 CODE INFORMATION
 1A) WRONG CODES STATED 2004 FLORIDA
 BUILDING CODE
 1B) ACCESSIBILITY: FBC 2004 CHAPTER 11
 1C) FBC EXISTING BUILDING CODE 2004
 INDICATE IF RENOVATION FALLS UNDER :
 LEVEL 1
 LEVEL 2
 LEVEL 3
 1D) ALL CODE REFRENCES AND TABLES ARE
  
 NOT 2004 FBC.
  
 2) A1.0 & A2.0 THE REAR EGRESS DOES NOT
 MEET THE MANEUVERING CLEARENCES OF A
 DOOR 12" REQUIRED PUSH SIDE OF LATCH
 WHEN A DOOR CLOSER AND LATCH ARE
 PRESENT.11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3)PLANS ARE CURRENTLY IN UNDER PLAN
 REVIEW, WHEN FILED FOR PERMIT THE DESIGN
 PROFESSIONAL SHALL SIGN/ SEAL AND "DATE"
 PLANS, THE DATE IS MISSING.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-02-16 Cont ID  
Sent By jwitmer Date 2006-02-16 Time 08:33 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2006-02-16 00:00:00PLANS APPROVED BY J. LEAHY 2/11/06 SEE
 SIGNATURE SHEET E1.0JW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-02-09 Cont ID  
Sent By mwennerg Date 2006-02-09 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2006-02-09 Time 14:26 Sent To  
Notes
2006-02-09 00:00:00******PROVISO******
  
 1) EXIT SIGNS ARE NOT SHOWN AT FRONT OR
 REAR DOORS.
  
 2) UNIT NUMBER TO BE INSTALLED IN
 APPROVED LOCATION ON STOREFRONT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 15:55 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 15:55 Sent To B
Notes
2006-04-05 00:00:00TO "JWITMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-06 Cont ID  
Sent By adarroug Date 2006-03-06 Time 16:10 Rev Time 0.00
Received By adarroug Date 2006-03-06 Time 16:10 Sent To  
Notes
2006-03-06 00:00:00TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-16 Cont ID  
Sent By jwitmer Date 2006-02-16 Time 08:34 Rev Time 0.00
Received By jwitmer Date 2006-02-06 Time 13:29 Sent To  
Notes
2006-02-06 00:00:00TO "BOB"#1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-02-09 Cont ID  
Sent By hmoser Date 2006-02-09 Time 09:22 Rev Time 0.00
Received By hmoser Date 2006-02-09 Time 09:22 Sent To  
Notes
2006-02-09 00:00:00PASS PRIVISO
 1- PLEASE REFER TO SECTION 606.2.1
 SYSTEM DUCT DETECTORS.AND SECTION
 606.4.1 SUPERVISON. 2004 FBC(M)
 2- PLEASE REFER TO SECTION 602.2.1
 MATERALS EXPOSED WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE.
 3- PLEASE REFER TO SECTION 307.2.3
 AUXILIARY AND SECONDARY DRAIN SYSTEMS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-08 Cont ID  
Sent By jleech Date 2006-03-08 Time 13:37 Rev Time 0.00
Received By jleech Date 2006-03-08 Time 13:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-02-08 Cont ID  
Sent By jleech Date 2006-02-08 Time 16:42 Rev Time 0.50
Received By jleech Date 2006-02-08 Time 16:42 Sent To  
Notes
***NONE***