Plan Review Details - Permit 06020087
Plan Review Stops For Permit 06020087
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-26 Cont ID  
Sent By alange Date 2006-04-26 Time 08:25 Rev Time 2.00
Received By alange Date 2006-04-26 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-10 Cont ID  
Sent By alange Date 2006-04-10 Time 08:43 Rev Time 1.00
Received By alange Date 2006-04-10 Time 08:42 Sent To  
Notes
2006-04-10 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 4.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 5.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR ALL WINDOWS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-28 Cont ID  
Sent By alange Date 2006-03-28 Time 09:05 Rev Time 1.50
Received By alange Date 2006-03-28 Time 09:05 Sent To  
Notes
2006-03-28 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 4.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 5.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR ALL WINDOWS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By alange Date 2006-03-09 Time 07:47 Rev Time 3.00
Received By alange Date 2006-03-09 Time 07:47 Sent To  
Notes
2006-03-09 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.CONSTRUCTION TYPE IS INCORRECT.
 SELECT THE CORRECT CUNSTRUCTION TYPE FOR
 THE 2004 FBC.
  
 4.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 5.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR LINTELS AND ALL WINDOWS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 12:31 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 12:31 Sent To PC
Notes
2006-07-07 00:00:00REV, AS-BUILTS

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-18 Cont ID  
Sent By dpalmer Date 2006-03-18 Time 17:15 Rev Time 0.00
Received By dpalmer Date 2006-03-18 Time 16:45 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2006-02-09 Time 19:44 Sent To M
Notes
2006-02-09 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE THE MAINS DISCONNECT
 "A" MAY NOT BE USED AS A RACEWAY FOR
 SEC'S TO MAIN "B". PLEASE SEE 230.7
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS
 SHALL NOT BE INSTALLED IN THE SAME
 SERVICE RACEWAY OR SERVICE CABLE.
 ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS
 MUST BE SEPARATED FROM SERVICE
 CONDUCTORS.
  
 2))NOTE: PLEASE SEE THE "GAS POOL
 HEATER" IS BEING SHOWN WITH AN
 ELECTRICAL LOAD AND CALCULATIONS
 INDICATING THIS HEATER AND AN ELECTRICAL
 TYPE HEATER/HEAT PUMP?
 PLEASE CLARIFY WHICH.
  
 3)NOTE: PLEASE SHOW SERVICE ON PLANS, AS
 PLANS ONLY INDICATE A METER ON THE
 OUTSIDE OF THE HOUSE. MAIN(S)?
 215.5
  
 4)NOTE: PLEASE SEE 210.8A7 WHICH
 REQUIRES ALL RECEPTS WITHIN 6' OF A WET
 BAR TO BE GFI.
 PLEASE SEE REDLINED PLANS.
  
 5 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE SEE THIS IS SHOWN AS PART OF THE
 GEN LT LOADS FOR LTS AND RECEPTS. THIS
 SHOULD BE ADDED TO GEN LIGHTING LOAD.
  
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONLY ONE COPY OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REVIEW.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLEASE ALSO CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THAT OF THE
 FIXTURES ON PANEL SCHEDULE.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 16:46 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 16:46 Sent To E
Notes
2006-07-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-19 Cont ID  
Sent By adarroug Date 2006-04-19 Time 12:40 Rev Time 0.00
Received By adarroug Date 2006-04-19 Time 12:40 Sent To B
Notes
2006-04-19 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-04 Cont ID  
Sent By adarroug Date 2006-04-04 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-04-04 Time 14:14 Sent To B
Notes
2006-04-04 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 14:12 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 14:03 Sent To E
Notes
2006-03-17 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-09 Cont ID  
Sent By alange Date 2006-03-09 Time 07:52 Rev Time 0.00
Received By alange Date 2006-02-03 Time 15:26 Sent To  
Notes
2006-02-03 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-20 Cont ID  
Sent By tgordon Date 2006-03-20 Time 12:03 Rev Time 0.30
Received By tgordon Date 2006-03-20 Time 12:03 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-10 Cont ID  
Sent By tgordon Date 2006-02-10 Time 11:38 Rev Time 0.30
Received By tgordon Date 2006-02-10 Time 11:38 Sent To P
Notes
2006-02-10 00:00:00*** DENIED ***
 1)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-02-10 Cont ID  
Sent By jleech Date 2006-02-10 Time 13:20 Rev Time 0.05
Received By jleech Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-09 Cont ID  
Sent By mmclean Date 2006-02-09 Time 13:02 Rev Time 0.00
Received By mmclean Date 2006-02-09 Time 13:02 Sent To E
Notes
2006-02-09 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA.