| Plan Review Stops For Permit 06020077 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-02-13 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-02-13 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-02-07 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-02-07 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | DENIED | | | | | | 1) THE FLORIDA PRODUCT APPROVAL | | | COVERSHEET IS FOR BUILT UP ROOFS, NOT | | | FOR THE RUBEROID MODIFIED BITUMEN SYSTEM | | | LISTED IN THE NOA THAT WAS SUBMITTED. | | | SEE FL 617-R1. | | | | | | 2) THE ASSEMBLY THAT IS PROPOSED AND | | | LISTED ON PAGES 11 AND 12 OF THE NOA HAS | | | A MAXIMUM DESIGN PRESSURE OF -45 PSF | | | WHICH WILL NOT MEET REQUIRED UPLIFT | | | PRESSURS ON THE STRUCTURE. LIMITATION #9 | | | FROM THE NOA DOES NOT ALLOW FOR ENHANCED | | | FASTENING FOR THIS ASSEMBLY. | | | | | | 3) SPECIFY THE MEAN ROOF HEIGHT OF THE | | | STRUCTURE ON THE APPLICATION. THIS | | | REVIEW IS BASED ON A MEAN ROOF HEIGHT OF | | | LESS THAN 30 FEET. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
|