Plan Review Details - Permit 06020067
Plan Review Stops For Permit 06020067
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-27 Cont ID  
Sent By shill Date 2006-03-27 Time 15:32 Rev Time 0.00
Received By shill Date 2006-03-27 Time 15:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-16 Cont ID  
Sent By shill Date 2006-03-16 Time 13:28 Rev Time 0.00
Received By shill Date 2006-03-16 Time 13:28 Sent To  
Notes
2006-03-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SHEET LS2.0, PLEASE DECLARE
 BUILDING TYPE IA OR IB, FBC TABLE 601.
  
 NOT ADDRESSED.AS DISCUSSED WITH THE
 ARCHITECT, THIS MAY BE DONE IN THE FORM
 OF A LETTER.
  
 3.)ADDRESSED.
  
 4.)DOCUMENTS PREPARED BY AN INTERIOR
 DESIGNER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED, AND DATED
 ORIGINALS, FAC61G1-16.003.AN INTERIOR
 DESIGN BUSINESS LICENSE IS REQUIRED FOR
 CORPORATE INTERIORS INC.EACH SHEET IS
 TO CONTAIN ALL INFORMATION REQUIRED BY
 FAC61G1-16.004.
  
 THE TITLE BLOCK IS NOW IN COMPLIANCE BUT
 THE SEAL IS TO LEAVE AN IMPRESSION
 FAC61G16-23.001.AN INK SEAL WAS
 PROVIDED FOR THE INTERIOR DESIGNER.
  
 5.) (NEW COMMENT.)SEE MECHANICAL
 COMMENTS IN REGARDS TO PENETRATIONS
 THROUGH THE 2 HOUR WALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By shill Date 2006-02-27 Time 08:11 Rev Time 0.00
Received By shill Date 2006-02-26 Time 14:18 Sent To  
Notes
2006-02-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SHEET LS2.0, PLEASE DECLARE
 BUILDING TYPE IA OR IB, FBC TABLE 601.
  
 3.)CORRIDOR 813 SHOWS A DISTANCE OF
 53FT, CORRIDOR 871 SHOWS 60FT, BOTH
 WHICH EXCEED THE 50FT MAX FOR A DEAD END
 CORRIDOR FBC1016.3.
  
 4.)DOCUMENTS PREPARED BY AN INTERIOR
 DESIGNER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED, AND DATED
 ORIGINALS, FAC61G1-16.003.AN INTERIOR
 DESIGN BUSINESS LICENSE IS REQUIRED FOR
 CORPORATE INTERIORS INC.EACH SHEET IS
 TO CONTAIN ALL INFORMATION REQUIRED BY
 FAC61G1-16.004.
  
 5.)INTERIOR FINISHES ARE TO COMPLY
 WITH FBC803.5, NFPA75-5.3.1.2.1.NOTE
 DESIGN CRITERIA ON THE PLAN.
  
 6.)SHEET 8.08A, PREPARED BY THE
 INTERIOR DESIGNER, SHOWS WOOD BLOCKING.
 SEE FBC717.5, FBC603 AND REVISE TO SHOW
 COMPLIANCE.
  
 7.)THE BREAK ROOM SINKS ARE TO COMPLY
 WITH FBC11-4.24.THE SINK IS TO BE
 ACCESSIBLE AND IS REQUIRED TO HAVE THE
 KNEE CLEARANCE FBC11-4.24.3.CABINET
 DOORS ARE SHOWN ON THE PLAN.
  
 8.)CORRIDOR 832 IS OPEN TO RECORDS
 STORAGE 864.FBC1002, THE CORRIDOR
 SHOULD BE ENCLOSED.
  
 9.)SHOW FIRE PROTECTION FOR COMPUTER
 ROOM 860, WALLS AND OPENINGS, NFPA75
 5.1.3.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-14 Cont ID  
Sent By dpalmer Date 2006-03-14 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2006-03-14 Time 08:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-24 Cont ID  
Sent By jleahy Date 2006-02-24 Time 20:10 Rev Time 0.00
Received By dpalmer Date 2006-02-24 Time 19:08 Sent To B
Notes
2006-02-24 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE REFERENCE ALL CURRENT
 CODE IN EFFECT FOR PLANS AND DESIGN.
 PLEASE SEE LOCATIONS ON PLANS WHICH
 REFLECT THE 2001 FBC ETC.
 ** PLEASE REFERENCE THE FOLLOWING:
 2003 NFPA-101, 2002 NFPA-72, 2002
 NFPA-70, AND 2004 FBC.
  
 2)NOTE: PLEASE SEE NEC 645 AND NFPA-75
 FOR ALL THE REQUIREMENTS WHICH WILL NEED
 TO BE ADJUSTED ON PLANS.
 PLEASE SEE 645.5,645.7,645.10 ETC
 PLEASE ADJUST LOADS FOR EQUIPMENT.645.5
 ** PLEASE SEE OTHER REVIEWS AND PLEASE
 BE SURE TO ADJUST MECH, AND BLDG PLANS
 ACCORDINGLY.
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC
  
 4)NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE CONNECTION FOR TRANSFORMER,
 PER 250.30 AND 250.58
  
 5)NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN NEW 400A MIAN
 AND MDP-1.
 250.110,250.122
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT PER 110.9,
 215.5
 ** IT IS NOTED THESE ARE SHOWN FOR
 PANELS,HOWEVER PLEASE PROVIDE FOR NEW
 MAIN DISCONNECT.
  
 7)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM LTS WHICH REQUIRES THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 ** PLEASE KNOW, IF THESE THE LIGHTING IN
 THE ARE OF FLOOR GOES OUT, NO MEANS OF
 EGRESS LIGHTING WOULD BE PROVIDED AS THE
 EM WOULD NOT COME ON UNLESS BLDG
 ELECTRICAL UTILITY SERVICES FAILS. THIS
 WOULD LEAVE ANY ONE AREA /FLOOR IN TOTAL
 DARKNESS. PLEASE EITHER ADD ADDTIONAL
 BATTERY BACK UP FIXTURES TO AREA FOR
 EGRESS, PLACE FIXTURES SHOWN ON LOCAL
 CIRCUITS.
 700.12,NFPA-101,7.8,7.9.2.2
  
 8)NOTE: PLEASE SEE 2004 FBC CHAPTER 13
 FOR COMMERCIAL BLDGS AND THE ENERGY CODE
 FOR PLANS AND DESIGS. IT IS NOTED, SOME
 MD/ ARE NOTED, HOWEVER PLEASE PROVIDE AL
 INFORMATION AS FOLLOWS AND COMPLETE
 PLANS FOR LAYOUTS, SCHEDULING,VOLTAGE
 DROPS, OVER-RIDES, SPACE
 CONTROLS,CALCULATIONS ETC.
 PLEASE SEE :
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2,
 13-413.1.ABC.1.1 & .1.2, 13-415.1.ABC.1,
  
 &.1.1
 PLEASE SEE ALL DESIGNS SHALL MEET 2004
 FBC.
 PLEASE ALSO SEE COMPLETION DOC'S
 REQUIRED 13-413.1.ABC.2.1.&.2
 ** PLEASE KNOW, SPEC SHEETS ON DEVICES,
 AND SYSTEM BEING INSTALLED WILL BE
 REQUIRED TO BE SUBMITTED, PLEASE PROVIDE
 A MIN OF TWO COPIES.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-03-24 Cont ID  
Sent By mwennerg Date 2006-03-24 Time 09:43 Rev Time 0.00
Received By mwennerg Date 2006-03-24 Time 09:43 Sent To  
Notes
2006-03-24 00:00:00SHEETS STAMPED 3/24/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-03-14 Cont ID  
Sent By mwennerg Date 2006-03-14 Time 15:58 Rev Time 0.00
Received By mwennerg Date 2006-03-14 Time 15:58 Sent To  
Notes
2006-03-14 00:00:00******PROVISO******
  
 1) PLEASE SEE COMMENT FROM MECHANICAL
 PLAN REVIEW REF: FIRE DAMPERS.
  
 2) PLANS RED LINES REGARDING CORRECTED
 CODE SECTION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-14 Cont ID  
Sent By nmccray Date 2006-02-14 Time 09:39 Rev Time 0.00
Received By nmccray Date 2006-02-13 Time 11:59 Sent To  
Notes
2006-02-14 00:00:00DENIED:
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE 2003 EDITION AND NFPA 1
 UNIFORM FIRE CODE 2003 EDITION.
  
 2) CORRIDOR # 813 APPEARS TO EXCEED 50
 FEET TRAVEL DISTANCE FOR DEAD-END
 CORRIDORS CHAPTER 38.2.5.2.1, NFPA 101.
  
 3) FIRE ALARM NOTE # 17 HVAC DUCT SMOKE
 DETECTORS SHALL BE CONNECTED TO THE FIRE
 ALARM CONTROL PANEL AND SHALL INITIATE A
 GENERAL FIRE ALARM SIGNAL, NOT A
 SUPERVISORY SIGNAL.
  
 4) DELAYED-EGRESS LOCKS SHALL COMPLY
 WITH NFPA 101 CHAPTER 7.2.1.6.1, AND
 ACCESS-CONTROLLED EGRESS DOORS SHALL
 COMPLY WITH NFPA 101 CHAPTER 7.2.1.6.2.
  
 5) SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE ALARM
 SYSTEM REMODEL.
  
 6) SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 7) INTERIOR WALL AND CEILING FINISH
 MATERIAL COMPLYING WITH NFPA 101 SECTION
 10.2 SHALL CLASS A OR CLASS B IN EXITS
 AND IN EXIT ACCESS CORRIDORS.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 15:58 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 15:58 Sent To M
Notes
2006-11-04 15:58:58TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-03-28 Time 16:09 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 16:09 Sent To P
Notes
2006-03-28 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 20:08 Sent To  
Notes
2006-03-21 00:00:00SENT TO BOB BOARD # 7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 14:37 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 14:37 Sent To  
Notes
2006-03-09 00:00:00TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-27 Cont ID  
Sent By shill Date 2006-02-27 Time 08:19 Rev Time 0.00
Received By shill Date 2006-02-02 Time 18:05 Sent To  
Notes
2006-02-02 00:00:00*EXPIDITED PLAN* OK TO ROUTE TO "BOB"
 PER RBROWN.
  
 TO "BOB"#18

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-11-15 Cont ID  
Sent By tgordon Date 2006-11-15 Time 10:31 Rev Time 0.45
Received By tgordon Date 2006-11-15 Time 10:31 Sent To  
Notes
2006-11-15 10:38:22REVISION TO MECH. PLANS PAGE M0.2, M2.1, AND M2.2 .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-22 Cont ID  
Sent By tgordon Date 2006-03-22 Time 12:32 Rev Time 0.20
Received By tgordon Date 2006-03-22 Time 12:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-14 Cont ID  
Sent By tgordon Date 2006-03-14 Time 12:25 Rev Time 0.45
Received By tgordon Date 2006-03-14 Time 12:25 Sent To  
Notes
2006-03-14 00:00:00*** DENIED ***
 1) AS STATED IN LAST REVIEW 02-13-06 #3.
 FIRE DAMPERS ARE REQUIRED WHERE DUCTS
 ARE PENETRATEING THE FIRE RATED WALLS TO
 COURT ROOMS (847 & 838) PER 2004 FBC
 716.5.1 . PLEASE SEE TRANSFER RETURN AIR
 DUCT FROM COURTROOM 847 TO ROOM 873;
 RETURN AIR DUCT FROM COURTROOM 847 TO
 ROOM 845; TRANSFER RETURN AIR DUCT FROM
 COURTROOM 838 TO ROOM 872; AND RETURN
 AIR DUCT FROM COURTROOM 838 TO ROOM 836.
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-13 Cont ID  
Sent By tgordon Date 2006-02-13 Time 10:43 Rev Time 3.00
Received By tgordon Date 2006-02-13 Time 10:43 Sent To  
Notes
2006-02-13 00:00:00*** DENIED ***
 1) PLEASE PROVIDE ENERGY CALCULATIONS,
 PER 2004 FBC CHAPTER 13.
  
 2) PLEASE SHOW ON MECH. PLANS HOW AIR
 CONDITIONING IS PROVIDED FOR ROOM 860
 (THE COMPUTER ROOM).
  
 3) FIRE DAMPERS ARE REQUIRED WHERE DUCTS
 ARE PENETRATEING THE FIRE RATED WALLS TO
 COURT ROOMS (847 & 838), PER 2004 FBC
 716.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-03-30 Cont ID  
Sent By jleech Date 2006-03-30 Time 08:06 Rev Time 0.00
Received By jleech Date 2006-03-30 Time 08:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-03-22 Cont ID  
Sent By jleech Date 2006-03-22 Time 09:47 Rev Time 0.00
Received By jleech Date 2006-03-22 Time 09:47 Sent To  
Notes
2006-03-22 00:00:00DENIED;
 1. WATER LINES STILL NOT SHOWN TO MOP
 SINK, PAGE P3.2.
 2.WATER HEATER PAN DRAIN CANNOT
 DISCHARGE INTO STORM WATER RISER. SEE
 FBC-2004 PLUMBING SEC.504.7.2 PAN DRAIN
 TERMINATION, MUST DISCHARGE OVER AN
 INDIRECT RECEPTOR OR EXTERIOR OF
 BUILDING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-13 Cont ID  
Sent By jleech Date 2006-03-13 Time 08:53 Rev Time 0.00
Received By jleech Date 2006-03-13 Time 08:53 Sent To  
Notes
2006-03-13 00:00:00DENIED;
 1.WATER HEATER PAN DRAIN IS NOT SHOWN ON
 PAGE P-2.1 AS NOTED ON WATER HEATER
 DETAIL. MECHANICAL ROOM IS SHOWN ON PAGE
 P-2.2. AND NO SANITARYDRAINAGE IS
 SHOWN. A FLOOR DRAIN SHOULD NOT BE USED
 IN A MECHANICAL ROOM BECAUSE THE TRAP
 WOULD BE SUBJECT TO A PNEUMATIC PRESSURE
 DIFFERENTIAL OF MORE THAN ONE INCH OF
 WATER COLUMN. FBC-2004 PLUMBING SEC.
 901.2.
 2.PAGE P-5.1 SANITARY AND WATER RISER
 DIAGRAMS SHOW A MOP SINK. PAGE P-2.1,
 SANITARY FLAT DRAWING, SANITARY PIPING
 NOT SHOWN. PAGE P-3.2 WATER PIPING NOT
 SHOWN TO MOP SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-11 Cont ID  
Sent By pschmitz Date 2006-02-11 Time 06:17 Rev Time 0.00
Received By pschmitz Date 2006-02-11 Time 06:17 Sent To  
Notes
2006-02-11 00:00:00 
 PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC 2004 BUILDING CH 11
 DENIED
 1)SHT 8.10 DETAIL (E)
 BREAK ROOMS #863,815,827.
 BASE CABINET DOORS UNDER SINKS.
 SINKS
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
  
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
  
 2)PRIVATE TOILET ROOM #818
 SECTION 11-4.1.3
 11) TOILET FACILITIES. IF TOILET ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH
 SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF
 SPECIFIC SPACES (I.E., A PRIVATE TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE
 OFFICE) SHALL BE ADAPTABLE. IF BATHING
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE BATHROOM SHALL COMPLY WITH
 SECTION 11-4.23. ACCESSIBLE TOILET ROOMS
 AND BATHING FACILITIES SHALL BE ON AN
 ACCESSIBLE ROUTE.
 11-4.22.2 DOORS.
 (1) ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SECTION 11-4.13. DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
  
 3) SHT P-01 WATER HEATER DETAIL
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 607.3.1 PRESSURE-REDUCING VALVE.
 FOR WATER SERVICE SYSTEM SIZES UP TO AND
 INCLUDING 2 INCHES (51 MM), A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED
 WHERE, BECAUSE OF THERMAL EXPANSION, THE
 PRESSURE ON THE DOWNSTREAM SIDE OF A
 PRESSURE-REDUCING VALVE EXCEEDS THE
 PRESSURE-REDUCING VALVE SETTING.
  
 4)SHT-5.1 DOMESTIC WATER ISOMETRIC
 AIR CHAMBERS NOT APPROVED
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED
 TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  