Plan Review Details - Permit 06020057
Plan Review Stops For Permit 06020057
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-05-18 Cont ID  
Sent By dpalmer Date 2006-05-18 Time 12:22 Rev Time 0.00
Received By dpalmer Date 2006-05-18 Time 12:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-30 Cont ID  
Sent By mwennerg Date 2006-05-30 Time 11:09 Rev Time 0.00
Received By mwennerg Date 2006-05-30 Time 11:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By mwennerg Date 2006-02-07 Time 15:15 Rev Time 0.00
Received By mwennerg Date 2006-02-07 Time 15:15 Sent To  
Notes
2006-02-07 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT APPLICATION IS FOR
 FIRE STATION #6, WHICH IS ADDRESSED 3033
 CUMBERLAND DR. PLEASE MAKE CORRECTION.
  
 2) PLEASE INCLUDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR AND ASSOCIATED
 FUEL.
  
 3) WORK TO COMPLY WITH NFPA 110.
  
 4) PROTECTION FOR THE GENERATOR MAY BE
 REQUIRED TO PROTECT AGAINST MECHANICAL
 DAMAGE IF NECESSARY.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-02-18 Time   Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 15:57 Sent To  
Notes
2006-02-01 00:00:00WAITING FOR "COMM" BD W/GENERATOR
 PERMITS