| 2006-02-19 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBEXISTING BUILDING |
| | FBC R RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | WINDOW PERMIT APPLICATION, ONLY CHECKED |
| | ITEMS APPLY |
| | |
| | _XX_1.A NOTICE OF COMMENCEMENT MUST |
| | BE FILED WITH THE CLERK OF COURTS BEFORE |
| | A PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | ____2.PROVIDE BUILDING HEIGHT. |
| | DESIGN PRESSURES FOR BUILDINGS OVER |
| | 60FEET ARE REQUIRED TO BE DESIGNED USING |
| | ASCE7, FBC1609.1.1. DOCUMENTS PREPARED |
| | BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| | RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| | FAC61G15-23.002. |
| | |
| | ____3.PROVIDE A COPY OF THE CONDO |
| | ASSOCIATION APPROVAL. |
| | |
| | ____4.IMPACT PROTECTION REQUIRED, |
| | FBC EB507.3, FBC1609.1.4. |
| | |
| | _XX_5.FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG.THIS WAS NOT |
| | PROVIDED FOR THE WINDOW. |
| | |
| | _XX_6.THE EMERGENCY EGRESS |
| | REQUIREMENTS OF FBC R310.1 HAVE NOT BEEN |
| | MET.BEDROOMS 1 AND 2.THE WINDOW |
| | SPECIFIED FOR BEDROOM 3, 52X75, EXCEEDS |
| | THE MAXIMUM SIZE OF THE WINDOW YOU HAVE |
| | SPECIFIED, 50 ? X50 5/8 MAX.OTHER |
| | WINDOWS ALSO EXCEED MAXIMUM SIZE. |
| | |
| | _XX_7.PROVIDE LEGIBLE DOCUMENTS, TWO |
| | COPIES.ONLY ONE ILLEGIBLE COPY |
| | SUBMITTED. |
| | |
| | _XX_8.COMPLETE THE ATTACHED |
| | INSTALLATION SCHEDULE OR PROVIDE |
| | REQUIRED INFORMATION IN A SIMILAR |
| | FORMAT. (SHUTTERS) |
| | |
| | |