Plan Review Details - Permit 06011131
Plan Review Stops For Permit 06011131
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-14 Cont ID  
Sent By amorse Date 2006-02-14 Time 14:39 Rev Time 0.50
Received By amorse Date 2006-02-14 Time 14:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-30 Cont ID  
Sent By amorse Date 2006-01-30 Time 08:17 Rev Time 0.50
Received By amorse Date 2006-01-30 Time 08:17 Sent To PC
Notes
2006-01-30 00:00:00 
  
 DENIED
  
 1) METAL ROOF PRODUCT APPROVAL HAS A
 MAXIMUM DESIGN PRESSURE OF -57.5 PSF
 THIS DOES NOT MEET THE REQUIRED PRESSURE
 FOR WEST PLAM BEACH IN THE FBC 2004
 THE ROOF SYSTEM CAN BE MADE TO COMPLY
 WITH THE INCREASED PRESSURES BUT THIS
 MUST BE CALCULATED BY A DESIGN
 PROFESSIONAL SUCH AS AN ARCHITECT OR
 ENGINEER.
  
 2) NO ROOF SYSTEM HAS BEEN CHOSEN FROM
 THE PRODUCT APPROVAL, ASSUMING THE ROOF
 IS NON-INSULATED AND APPLIED TO A
 PLYWOOD DECK THE CHOICES ARE ON PAGES
 33-38 OF THE NOA. ALL OF THESE CHOICES
 ALSO NEED ENHANCED FASTENING TO MEET THE
 INCREASED PRESSURES FOR 140 MPH EXP B
  
 3) PERMIT VALUATION IS LOW THE
 DETERMINATIONS WE USE ARE BASED ON THE
 MARSHALL & SWIFT GUIDE TO CONSTRUCTION
 COSTS THE PERMIT WILL BE ADJUSTED
 ACCORINGLY AND AN ADDITIONAL FEE CHARGED
  
  
  
 BLDG PLAN REVIEW