Plan Review Details - Permit 06011125
Plan Review Stops For Permit 06011125
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-25 Cont ID  
Sent By amorse Date 2006-04-25 Time 10:08 Rev Time  
Received By amorse Date 2006-04-25 Time 10:08 Sent To PC
Notes
2006-04-25 00:00:00 
  
 BUILDING REVISION ONLY WILL REQUIRE ELEC
 PLANS FOR ELEC CHANGES

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-20 Cont ID  
Sent By amorse Date 2006-03-20 Time 08:24 Rev Time  
Received By amorse Date 2006-03-20 Time 08:24 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-05-22 Cont ID  
Sent By btrobaug Date 2006-05-22 Time 12:14 Rev Time 0.75
Received By btrobaug Date 2006-05-22 Time 06:31 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-04-18 Cont ID  
Sent By dpalmer Date 2006-04-18 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2006-04-18 Time 12:23 Sent To  
Notes
2006-04-18 00:00:00********** UNSAT *******
  
  
 1) NOTE: PLEASE SEE REV'S SUBMITED
 4/13/06 HAS ATTACHED PROPOSED CHANGES
 FOR SCOPE PF WORK WHICH INLCUDE MANY
 ELECTRICAL CHNAGES, HOWEVER NO
 ELECTRICAL PLANS FOR THESE REVISIONS
 WERE SUBMITTED FOR REVIEW.
  
  
 2) NOTE: PLEASE ALSO KNOW AS TO DATE,
 ELECTRICAL PLANS FOR LV WORK WHICH IS BE
 UNDER A SEPARATE PERMIT AND PLANS, HAVE
 NOT BEEN SUBMITTED.
 THIS WAS REDLINED ON PREVIOUS PLANS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-28 Cont ID  
Sent By dpalmer Date 2006-03-28 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2006-03-28 Time 07:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-02 Cont ID  
Sent By dpalmer Date 2006-03-02 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2006-03-02 Time 20:43 Sent To  
Notes
2006-03-02 00:00:00**** UNSAT ***
  
 1)NOTE: PLEASE SEE MISSING CERTICATE OF
 AUTHORIZATION NUMBER FOR MECHNICAL
 ENGINEERING FIRM WHICH IS REQUIRED ON
 TITLE BLOCK PER FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002, FLORIDA STATUES
 481.219. THIS COMMENT IS NOT FOR
 ELECTRICAL ENGINEER.
  
 2)NOTE: PLEASE VERIFY LOADS FOR TRACK
 LIGHTING PER 220.12B , PLEASE SHOW
 TOTALS ETC.
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT
 125%( LIGHTING). 215.3,230.42.
  
 3)NOTE: PLEASE CORRELATE LOAD
 CALCUALTIONS SUBMITTED WITH RISER
 DIAGRAM. PLEASE SEE LOADS INDICATE
 SERVICE AS 1000A'S, WHEN RISER SHOWS
 1200A'S?
 215.5
  
 4)NOTE: PLEASE SEE KEYNOTE #8 WHICH
 MENTIONS EM LTS TO BE CONNECTED TO EM
 CIRCUIT. PLEASE SEE 700.12E WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST NOTE FOR FIXTURES BEING
 ADDED.
  
 5)NOTE: PLEASE SEE FBC 2004 CHAPTER 13 ,
 13-415.1.ABC.1.2,
 PLEASE ALSO SEE 13-415.1.ABC.1.1 WHICH
 WILL REQUIRED THE LIGHTING INSIDE ROOMS
 TO BE PART OF THE LIGHTING CONTROL
 SYSTEM.
  
 6)NOTE: PLEASE SEE NOTE ON LV PLANS
 MENTIONS WIRING BY OTHERS. PLEASE KNOW,
 IF LV IS NOT INCLUDED ONTHIS PERMIT,
 THEN SEPARATE PERMIT AND PLANS WILL BE
 REQUIRED BEFORE INSTALLATION.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-25 Cont ID  
Sent By mwennerg Date 2006-04-21 Time 14:21 Rev Time 0.00
Received By mwennerg Date 2006-04-21 Time 14:21 Sent To  
Notes
2006-04-21 00:00:00******OK******
  
 1) PLEASE NOTE THAT THE DISTANCE BETWEEN
 THE TWO REQUIRED EXITS SHALL COMPLY WITH
 NFPA 101, SECTION 7.5.1.3.3 WHICH STATES
 THAT "NOT LESS THAN 1/3 THE LENGTH OF
 THE MAXIMUM OVERALL DIAGONAL DIMENSION
 OF THE BUILDING OR AREA TO BE SERVED".
 IT APPEARS THAT THIS DISTANCE WAS
 CALCULATED ON LESS THAN THE ENTIRE AREA.
  
 2) THAT DISTANCE SEPARATION IS STILL
 REQUIRED WHERE MORE THAN (2) EXITS ARE
 PROVIDED IN ACCORDANCE WITH NFPA 101,
 SECTION 7.5.1.3.6.
  
 PLANS SCALED SHOWING COMPLIANCE.
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-03-20 Cont ID  
Sent By nmccray Date 2006-03-20 Time 09:57 Rev Time 0.00
Received By nmccray Date 2006-03-20 Time 09:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 08:53 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 08:53 Sent To E
Notes
2006-05-18 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-15 Cont ID  
Sent By adarroug Date 2006-04-15 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-04-15 Time 13:15 Sent To  
Notes
2006-04-15 00:00:00TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 18:21 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 18:20 Sent To  
Notes
2006-03-24 00:00:00TO BOB #2.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-20 Cont ID  
Sent By amorse Date 2006-03-20 Time 08:25 Rev Time 0.00
Received By amorse Date 2006-01-31 Time 14:35 Sent To  
Notes
2006-03-13 00:00:00EXPIDITED-SENT TO "BOB"#16
2006-03-02 00:00:00TO "COMM" BD#34
2006-01-31 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-27 Cont ID  
Sent By tgordon Date 2006-03-27 Time 11:14 Rev Time 0.20
Received By tgordon Date 2006-03-27 Time 11:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-14 Cont ID  
Sent By tgordon Date 2006-03-14 Time 08:59 Rev Time 0.30
Received By tgordon Date 2006-03-14 Time 08:59 Sent To  
Notes
2006-03-14 00:00:00*** DENIED ***
 1) MECHANICAL ENGINEERING FIRM'S LICENSE
 NUMBER MUST APPEAR IN TITLE BLOCK, PER
 FAC 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-03-14 Cont ID  
Sent By jleech Date 2006-03-14 Time 08:08 Rev Time 0.00
Received By jleech Date 2006-03-14 Time 08:08 Sent To  
Notes
2006-03-14 00:00:00NO PLUMBING SHOWN ON PLANS.