Plan Review Details - Permit 06011056
Plan Review Stops For Permit 06011056
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By mjacobs Date 2006-02-08 Time 09:41 Rev Time 0.00
Received By mjacobs Date 2006-02-08 Time 07:10 Sent To  
Notes
2006-02-07 00:00:001) 108.3 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING, AL-
 TERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION FOR
 BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN
 FEES, OVERHEAD AND PROFIT, EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES
 MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT,MEANS,ETC.)
 WITH REGIONAL ADJUSTMENTS FOR LOCATION
 AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 2) (2004 FBC) 11-4.13.6 MANEUVERING
 CLEARANCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIGURE 11-25. THE FLOOR OR
 GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
  
 3) SHOW IN DETAIL HOW THE SINK WILL MEET
 THE ADA REQUIREMENTS. MAKING THE
 STATEMENT IS NOT SUFFICENT INFORMATION.
 ALL DIMENTIONS AND DRAWINGS SHOWING HOW
 THE SINK WILL MEET THE REQUIREMENTS IS
 REQUIRED ON THE DRAWINGS.
  
 4)(2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-30 Cont ID  
Sent By jleahy Date 2006-01-30 Time 16:38 Rev Time 0.30
Received By jleahy Date 2006-01-30 Time 16:38 Sent To  
Notes
2006-01-30 00:00:00NO ELECTRIC INCLUDED WITH PLANSJL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-30 Cont ID  
Sent By nmccray Date 2006-01-30 Time 15:06 Rev Time 0.00
Received By nmccray Date 2006-01-30 Time 15:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 16:55 Sent To  
Notes
2006-01-28 00:00:00TO "BOB"#16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-04 Cont ID  
Sent By pschmitz Date 2006-02-04 Time 05:55 Rev Time 0.00
Received By pschmitz Date 2006-02-04 Time 05:55 Sent To  
Notes
2006-02-04 00:00:00 
  
  
 PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC 2004 BUILDING CH 11
 DENIED
 1)CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICAL. CONSTRUCTION
 DOUCMENTS SHALL BE OF SUFFICENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT ITWILL CONFORM TOTHE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS
 AS DETERMINED BY THE BUILDING OFFICAL (
 SEE ALSO SECTION 106.3.5)
  
 2) SHT A-2 BREAK ROOM, REFERENCE TO SHT
 A-1 DETAIL 2,
 SHT A-1 NOT WITH SUBMITTED PLANS.
 NOTE: COMPLY WITH ADA REQUIRMENTS IS NOT
 ACCEPTABLE.PROVIDE ELEVATION DETAIL
 11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 3) SHT A-2,SEC 106.3.5.1.3 (4.)
 COMMERICAL BUILDINGS,
 PLUMBING SANITARY DRAINAGE.
 ( DWV ISOMETRIC REQUIRED )
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  
  
  