| Plan Review Stops For Permit 06011041 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2006-08-25 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-08-25 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-08-25 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2006-08-25 00:00:00 | EXT #0004( 5837 CORPORATE WAY)FOR THE | | | 60 KW DIESEL TANK GENERATOR WAS CREATED | | | .PERMIT MUST BE ATTACHED TO IT. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2006-08-22 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-08-22 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-08-22 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2006-08-22 00:00:00 | PROJECT UNDER REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-23 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-08-22 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-07-10 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-10 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-10 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2006-07-10 00:00:00 | DENIED | | | | | | 1.SEE ELECTRICAL REVIEW COMMENTS DONE | | | FOR BUILDING. | | | | | | 2.PROPERTY IS IN FLOOD ZONE "A" AND | | | TOP OF SLAB SHALL BE 7" ABOVE THE BASE | | | FLOOD ELEVATION NGVD,AN ELEVATION | | | CERTIFICATE IS REQUIRED FOR FINAL | | | INSPECTION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-03-29 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-03-29 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-03-29 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2006-03-29 00:00:00 | | | | | | | BUILDING PROVISO | | | -------- ------- | | | | | | | | | | | | COMPLY WITH ELECRICAL COMMENT'S #1 AND | | | #3 DATED MARCH 2ND. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | L.MARTINEZ | | | 561-805-6710 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-18 |
Time |
20:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-18 |
Time |
20:08 |
Sent To |
|
|
| Notes |
| 2006-08-18 00:00:00 | STAMPED ELECTRICAL PLANS, GEN SPECS, WP | | | HOUSING, AND ATS SPECS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-06-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-01 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-01 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2006-06-01 00:00:00 | ************UNSAT 2ND REVIEW ******** | | | | | | ** PLEASE SEE COMMENTS FROM PREVIOUS | | | REVIEW AND SOME NEW COMMENTS FROM THIS | | | REVIEW . | | | | | | | | | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS | | | OF PLANS. PLEASE REMOVE ANY OLD/VOIDED | | | SHEETS OR SETS AND ONLY SUBMIT ONE COPY | | | OF OLD/VOIDED SHEETS/SETS SEPARATELY IN | | | PACKAGE FOR REFERENCE. | | | | | | 2) NOTE: PLEASE SEE SOME OF THE NEW | | | PLANS SUBMITTED ARE SEALED "PHOTO-COPIES | | | OF SIGNED PLANS AND SHALL BE RETAINED BY | | | THIS OFFICE FOR SUBMITTIAL TO THE | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS | | | AS OTHER PROJECTS AND REVIEWS HAVE HAD | | | THE SAME COMMENT AND PLANS ARE STILL | | | BEING SUBMITTED WITH THE SAME SIMILAR | | | COMMENTS. PLEASE SEE FS 471.025 WHICH | | | REQUIRES PLANS TO CONTAIN A RAISED SEAL, | | | AND AN ORIGINAL SIGNATURE AND DATE BY | | | THE SAID ENGINEER. | | | PLEASE SEE SOME OTHER PLANS WERE | | | SUBMITTED AFTER ORIGINAL DATE WHICH NOW | | | CONTAINS ORIGINAL SIGNATURE. | | | | | | 3) NOTE:PLEASE ALSO SEE NEW "S" | | | SHEETS. PLEASE SEE FAC 61G15-23.001 | | | WHICH IN FEB 04 THE FBPE'S RULED THE | | | "WORDING" IN THE SEAL SHALL BE CHANGED | | | TO "LICENSE" FROM "CERTIFICATE". AN | | | EXTENSION WAS GIVEN TO THE DATE OF | | | 12/31/05 IN WHICH THE OLD SEALS MAY BE | | | USED. PLEASE KNOW, THE SEAL AS SUBMITTED | | | FOR THE "S" SHEETS ARE NO LONGER | | | ACCEPTABLE UNDER FAC/ FLORIDA STATUES. | | | PELAS OBTAIN NEW SEAL AND REVISE SHEETS | | | ACCORDINGLY. | | | | | | 4) NOTE: PLEASE SUBMIT THE SPECS AS | | | REQUESTED FOR THE ATS. UNABLE TO VERIFY | | | CODE COMPLIANCE FOR MANY ITEMS AS THE | | | ATS MUST MEET, | | | 230.70,230.76,230.79,225.31-225.39. | | | PLEASE SEE THE ATS IS REQUIRED TO BE | | | RATED AS "SERVICE ENTRANCE", ETC. | | | ONLY THE SPECS FOR THE GENERATOR WERE | | | LOCATED IN PLANS AND PAPERWORK | | | SUBMITTED. | | | PLEASE BE SURE TO CORRELATE WITH PLANS. | | | | | | | | | **PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-03-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-02 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-01 |
Time |
21:01 |
Sent To |
|
|
| Notes |
| 2006-03-02 00:00:00 | ********* UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | AS DETAIL FOR SLAB SHALL BE SIGNED, | | | DATED AND SEALED. FS 481.221, 471.023 | | | | | | 2)NOTE: PLEASE SEE CURRENT CODES NEED TO | | | BE REFERENCED ON PLANS. PLEASE SEE THAT | | | WE ARE CURRENLTY UNDER THE 2004 FBC, | | | 2003 NFPA-101, 2002 NFPA-110, 2002 | | | NFPA-70 | | | | | | 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | WITH RESPECT TO BFE. | | | PLEASE SEE NFPA-110 7.2.3* | | | PLEASE NOTE AND VERIFY THE LOCATION OF | | | GENERATOR. | | | | | | 4)NOTE: PLEASE SUBMIT ALL MANUFACTURE | | | SPECS/CUT SHEETS FOR GEN, ATS, SUB BASE | | | FUEL TANK, WP HOUSING. | | | THE ONLY SPEC SUBMITTED WAS FOR THE | | | GENERATOR WHICH INDICATES AND INDOOR | | | UNIT. ASSUBMITTED, GEN IS SHOWN AS | | | 54KW/KVA, WHERE-AS THE PERMIT | | | APPLICATION MENTIONS 60KW?? | | | PLEASE CORRELATE. | | | | | | 5)NOTE: PLEASE SEE EXISTING MCB IS SHOWN | | | ON ROOF??? | | | PLEASE VERIFY AS THIS IS NOT READILY | | | ACCESSIBLE AS REQUIRED PER 230.70,PLEASE | | | SEE MAINS ARE NOT GROUPED PER 230.72, | | | 225.34. | | | | | | 6)NOTE: PLEASE SEE VALUATION IS BASED ON | | | COMPLETE SCOPE PF WORK WHICH IS TO | | | INCLUDE ALL LABOR AND MATERIALS, EVEN OF | | | ANY EQUIPMENT IS OWNER SUPPLIED. VALUE | | | AS SHOWN IS WAY LOW AND MAY BE ADJUSTED | | | BY THIS OFFICE IF AN APPROPRIATE VALUE | | | IS NOT INCREASED. | | | THIS IS TO BE INCREASED WHEN | | | RESUBMITTING PLANS AFTER ALL REVIEWS ARE | | | COMPLETED. | | | | | | 7)NOTE: PLEASE SUBMIT THE INTENDED LOADS | | | FOR GENERATOR. GEN MUS BE SIZED FOR | | | LOADS SERVED. | | | 220, 215.5 | | | | | | ** PLEASE SEE COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2006-03-01 00:00:00 | IN ELEC FOR REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-06-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-06-20 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-06-20 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-03-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-03-16 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-03-16 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2006-03-16 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE PROVIDE MANUFACTURER SPEC | | | SHEETS FOR GENERATOR, FUEL TANK AND | | | ASSOCIATED EQUIPMENT. | | | | | | 2) APPROPRIATE PROTECTION DEVICES MAY BE | | | REQUIRED IF FUEL TANK AND EQUIPMENT ARE | | | SUBJECT TO MECHANICAL DAMAGE. | | | | | | 3) PLEASE INDICATE SIZE OF VENT PIPING | | | AND LOCATION OF EXHAUSTING IN REGARDS TO | | | BUILDING OPENINGS, PROPERTY LINES ETC. | | | | | | 4) WORK TO COMPLY WITH CURRENT | | | APPLICABLE BUILDING AND LIFE SAFETY | | | CODES IN ADDITION TO NFPA 110. NFPA 101 | | | AND NFPA 1, 2003 EDITIONS SHALL BE | | | REFERENCED. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-06 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-06 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2006-09-06 00:00:00 | DIESEL GENERATOR - NO NATURAL OR LP GAS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-08 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-08 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2006-08-18 00:00:00 | TO "COMM" BD#18 | | 2006-08-08 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-02 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-02 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2006-05-23 00:00:00 | TO "COMM" BD#22 | | 2006-05-02 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-03-29 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-03-29 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-01-28 |
Time |
17:21 |
Sent To |
|
|
| Notes |
| 2006-03-01 00:00:00 | TO "COMM" BD#7 | | 2006-01-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2006-07-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-07-10 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-07-10 |
Time |
08:33 |
Sent To |
B |
|
| Notes |
| 2006-07-10 00:00:00 | NO MECHANICAL OR FUEL PLANS SUBMITTED. | | | GENERATOR HAS A SUB-BASE DIESEL FUEL | | | TANK (SELF CONTAINED).GENERATOR HAS | | | PROPER CLEARANCES FROM BUILDINGS, & | | | PROPERTY LINES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-03-12 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-03-12 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-03-12 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2006-03-12 00:00:00 | PLANS DENIED | | | PLEASE PROVIDE EXHAUST AND EXHAUST | | | TERMINATION ON PLANS. | | | PLEASE PROVIDE EXHAUST VENTILATION FOR | | | THE GENERATOR ON THE PLANS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-03-16 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-03-16 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-03-16 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2006-08-23 00:00:00 | PROVISO: MUST HAVE A LANDSCAPE BUFFER | | | AROUND THE PROPOSED GENERATOR FOR | | | SCREENING SEC 94-444(B). |
|
|