Plan Review Details - Permit 06011041
Plan Review Stops For Permit 06011041
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-08-25 Cont ID  
Sent By lursu Date 2006-08-25 Time 10:36 Rev Time 0.00
Received By lursu Date 2006-08-25 Time 10:36 Sent To  
Notes
2006-08-25 00:00:00EXT #0004( 5837 CORPORATE WAY)FOR THE
 60 KW DIESEL TANK GENERATOR WAS CREATED
 .PERMIT MUST BE ATTACHED TO IT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-08-22 Cont ID  
Sent By lursu Date 2006-08-22 Time 15:17 Rev Time 0.00
Received By lursu Date 2006-08-22 Time 15:17 Sent To  
Notes
2006-08-22 00:00:00PROJECT UNDER REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-23 Cont ID  
Sent By alange Date 2006-08-23 Time 08:37 Rev Time 0.00
Received By alange Date 2006-08-22 Time 11:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By alange Date 2006-07-10 Time 14:08 Rev Time 0.00
Received By alange Date 2006-07-10 Time 14:07 Sent To  
Notes
2006-07-10 00:00:00DENIED
  
 1.SEE ELECTRICAL REVIEW COMMENTS DONE
 FOR BUILDING.
  
 2.PROPERTY IS IN FLOOD ZONE "A" AND
 TOP OF SLAB SHALL BE 7" ABOVE THE BASE
 FLOOD ELEVATION NGVD,AN ELEVATION
 CERTIFICATE IS REQUIRED FOR FINAL
 INSPECTION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-29 Cont ID  
Sent By lmartine Date 2006-03-29 Time 13:12 Rev Time 0.00
Received By lmartine Date 2006-03-29 Time 13:12 Sent To  
Notes
2006-03-29 00:00:00 
  
 BUILDING PROVISO
 -------- -------
  
  
  
 COMPLY WITH ELECRICAL COMMENT'S #1 AND
 #3 DATED MARCH 2ND.
  
  
  
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-18 Cont ID  
Sent By dpalmer Date 2006-08-18 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2006-08-18 Time 20:08 Sent To  
Notes
2006-08-18 00:00:00STAMPED ELECTRICAL PLANS, GEN SPECS, WP
 HOUSING, AND ATS SPECS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-01 Cont ID  
Sent By dpalmer Date 2006-06-01 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2006-06-01 Time 13:02 Sent To  
Notes
2006-06-01 00:00:00************UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS FROM THIS
 REVIEW .
  
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS. PLEASE REMOVE ANY OLD/VOIDED
 SHEETS OR SETS AND ONLY SUBMIT ONE COPY
 OF OLD/VOIDED SHEETS/SETS SEPARATELY IN
 PACKAGE FOR REFERENCE.
  
 2) NOTE: PLEASE SEE SOME OF THE NEW
 PLANS SUBMITTED ARE SEALED "PHOTO-COPIES
 OF SIGNED PLANS AND SHALL BE RETAINED BY
 THIS OFFICE FOR SUBMITTIAL TO THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 AS OTHER PROJECTS AND REVIEWS HAVE HAD
 THE SAME COMMENT AND PLANS ARE STILL
 BEING SUBMITTED WITH THE SAME SIMILAR
 COMMENTS. PLEASE SEE FS 471.025 WHICH
 REQUIRES PLANS TO CONTAIN A RAISED SEAL,
 AND AN ORIGINAL SIGNATURE AND DATE BY
 THE SAID ENGINEER.
 PLEASE SEE SOME OTHER PLANS WERE
 SUBMITTED AFTER ORIGINAL DATE WHICH NOW
 CONTAINS ORIGINAL SIGNATURE.
  
 3) NOTE:PLEASE ALSO SEE NEW "S"
 SHEETS. PLEASE SEE FAC 61G15-23.001
 WHICH IN FEB 04 THE FBPE'S RULED THE
 "WORDING" IN THE SEAL SHALL BE CHANGED
 TO "LICENSE" FROM "CERTIFICATE". AN
 EXTENSION WAS GIVEN TO THE DATE OF
 12/31/05 IN WHICH THE OLD SEALS MAY BE
 USED. PLEASE KNOW, THE SEAL AS SUBMITTED
 FOR THE "S" SHEETS ARE NO LONGER
 ACCEPTABLE UNDER FAC/ FLORIDA STATUES.
 PELAS OBTAIN NEW SEAL AND REVISE SHEETS
 ACCORDINGLY.
  
 4) NOTE: PLEASE SUBMIT THE SPECS AS
 REQUESTED FOR THE ATS. UNABLE TO VERIFY
 CODE COMPLIANCE FOR MANY ITEMS AS THE
 ATS MUST MEET,
 230.70,230.76,230.79,225.31-225.39.
 PLEASE SEE THE ATS IS REQUIRED TO BE
 RATED AS "SERVICE ENTRANCE", ETC.
 ONLY THE SPECS FOR THE GENERATOR WERE
 LOCATED IN PLANS AND PAPERWORK
 SUBMITTED.
 PLEASE BE SURE TO CORRELATE WITH PLANS.
  
  
 **PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-02 Cont ID  
Sent By dpalmer Date 2006-03-02 Time 17:32 Rev Time 0.00
Received By dpalmer Date 2006-03-01 Time 21:01 Sent To  
Notes
2006-03-02 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS DETAIL FOR SLAB SHALL BE SIGNED,
 DATED AND SEALED. FS 481.221, 471.023
  
 2)NOTE: PLEASE SEE CURRENT CODES NEED TO
 BE REFERENCED ON PLANS. PLEASE SEE THAT
 WE ARE CURRENLTY UNDER THE 2004 FBC,
 2003 NFPA-101, 2002 NFPA-110, 2002
 NFPA-70
  
 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 WITH RESPECT TO BFE.
 PLEASE SEE NFPA-110 7.2.3*
 PLEASE NOTE AND VERIFY THE LOCATION OF
 GENERATOR.
  
 4)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR GEN, ATS, SUB BASE
 FUEL TANK, WP HOUSING.
 THE ONLY SPEC SUBMITTED WAS FOR THE
 GENERATOR WHICH INDICATES AND INDOOR
 UNIT. ASSUBMITTED, GEN IS SHOWN AS
 54KW/KVA, WHERE-AS THE PERMIT
 APPLICATION MENTIONS 60KW??
 PLEASE CORRELATE.
  
 5)NOTE: PLEASE SEE EXISTING MCB IS SHOWN
 ON ROOF???
 PLEASE VERIFY AS THIS IS NOT READILY
 ACCESSIBLE AS REQUIRED PER 230.70,PLEASE
 SEE MAINS ARE NOT GROUPED PER 230.72,
 225.34.
  
 6)NOTE: PLEASE SEE VALUATION IS BASED ON
 COMPLETE SCOPE PF WORK WHICH IS TO
 INCLUDE ALL LABOR AND MATERIALS, EVEN OF
 ANY EQUIPMENT IS OWNER SUPPLIED. VALUE
 AS SHOWN IS WAY LOW AND MAY BE ADJUSTED
 BY THIS OFFICE IF AN APPROPRIATE VALUE
 IS NOT INCREASED.
 THIS IS TO BE INCREASED WHEN
 RESUBMITTING PLANS AFTER ALL REVIEWS ARE
 COMPLETED.
  
 7)NOTE: PLEASE SUBMIT THE INTENDED LOADS
 FOR GENERATOR. GEN MUS BE SIZED FOR
 LOADS SERVED.
 220, 215.5
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-03-01 00:00:00IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-20 Cont ID  
Sent By mcarsill Date 2006-06-20 Time 15:42 Rev Time 0.00
Received By mcarsill Date 2006-06-20 Time 15:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-16 Cont ID  
Sent By mwennerg Date 2006-03-16 Time 13:34 Rev Time 0.00
Received By mwennerg Date 2006-03-16 Time 13:34 Sent To  
Notes
2006-03-16 00:00:00******DENIED******
  
 1) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR, FUEL TANK AND
 ASSOCIATED EQUIPMENT.
  
 2) APPROPRIATE PROTECTION DEVICES MAY BE
 REQUIRED IF FUEL TANK AND EQUIPMENT ARE
 SUBJECT TO MECHANICAL DAMAGE.
  
 3) PLEASE INDICATE SIZE OF VENT PIPING
 AND LOCATION OF EXHAUSTING IN REGARDS TO
 BUILDING OPENINGS, PROPERTY LINES ETC.
  
 4) WORK TO COMPLY WITH CURRENT
 APPLICABLE BUILDING AND LIFE SAFETY
 CODES IN ADDITION TO NFPA 110. NFPA 101
 AND NFPA 1, 2003 EDITIONS SHALL BE
 REFERENCED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By kstevens Date 2006-09-06 Time 15:56 Rev Time 0.00
Received By kstevens Date 2006-09-06 Time 15:56 Sent To  
Notes
2006-09-06 00:00:00DIESEL GENERATOR - NO NATURAL OR LP GAS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 11:58 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 11:58 Sent To  
Notes
2006-08-18 00:00:00TO "COMM" BD#18
2006-08-08 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 12:08 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 12:08 Sent To  
Notes
2006-05-23 00:00:00TO "COMM" BD#22
2006-05-02 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-29 Cont ID  
Sent By lmartine Date 2006-03-29 Time 13:33 Rev Time 0.00
Received By lmartine Date 2006-01-28 Time 17:21 Sent To  
Notes
2006-03-01 00:00:00TO "COMM" BD#7
2006-01-28 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-07-10 Cont ID  
Sent By pkrauss Date 2006-07-10 Time 08:33 Rev Time 0.00
Received By pkrauss Date 2006-07-10 Time 08:33 Sent To B
Notes
2006-07-10 00:00:00NO MECHANICAL OR FUEL PLANS SUBMITTED.
 GENERATOR HAS A SUB-BASE DIESEL FUEL
 TANK (SELF CONTAINED).GENERATOR HAS
 PROPER CLEARANCES FROM BUILDINGS, &
 PROPERTY LINES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-12 Cont ID  
Sent By hmoser Date 2006-03-12 Time 12:25 Rev Time 0.00
Received By hmoser Date 2006-03-12 Time 12:33 Sent To  
Notes
2006-03-12 00:00:00PLANS DENIED
 PLEASE PROVIDE EXHAUST AND EXHAUST
 TERMINATION ON PLANS.
 PLEASE PROVIDE EXHAUST VENTILATION FOR
 THE GENERATOR ON THE PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 1 Status P Date 2006-03-16 Cont ID  
Sent By mmclean Date 2006-03-16 Time 11:40 Rev Time 0.00
Received By mmclean Date 2006-03-16 Time 11:40 Sent To  
Notes
2006-08-23 00:00:00PROVISO: MUST HAVE A LANDSCAPE BUFFER
 AROUND THE PROPOSED GENERATOR FOR
 SCREENING SEC 94-444(B).