Plan Review Details - Permit 06011022
Plan Review Stops For Permit 06011022
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-31 Cont ID  
Sent By tgordon Date 2006-01-31 Time 14:55 Rev Time 0.00
Received By tgordon Date 2006-01-27 Time 13:54 Sent To  
Notes
2006-01-27 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-01-31 Cont ID  
Sent By tgordon Date 2006-01-31 Time 14:25 Rev Time 0.25
Received By tgordon Date 2006-01-31 Time 14:25 Sent To  
Notes
2006-01-31 00:00:00*** PROVISO ***
 1) 26X16 NEW FIRE DAMPER TO BE INSTALLED
 AT TENANT SEPARATION WALL.
 2) EACH OFFICE MUST HAVE A RETURN AIR
 GRILL TO COMPLY WITH 2004 FBC/M 601.4 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  