Plan Review Details - Permit 06010964
Plan Review Stops For Permit 06010964
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-26 Cont ID  
Sent By alange Date 2006-06-26 Time 15:40 Rev Time 1.50
Received By alange Date 2006-06-26 Time 15:40 Sent To  
Notes
2006-06-26 00:00:00 
 DENIED
  
 5.PRODUCT APPROVALS REQUIRED FOR
 FLAT ROOF.
  
 6.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 HAVE APPROVED SET AT JOB SITE PRIOR TO
 INSTALLATION.
  
 10.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.CHECK ALL CODE
 SECTIONS USED.SEE PAGE 6 CODE SECTIONS
 AND PAGE 21 FOR ASCE 7-98
  
 11.PROVISIONS FOR FLOOD HAZARD
 REDUCTION;ALL NEW CONSTRUCTION OR
 SUBSTANTIAL IMPROVEMENT OF ANY EXISTING
 RESIDENTIAL STRUCTURE SHALL HAVE THE
 LOWEST FLOOR, INCLUDING BASEMENT,
 ELEVATED TO SIX INCHES ABOVE THE BASE
 FLOOD ELEVATION OF 7 FT.
 SEE ATTACHED CITY OF WPB MUNI-CODE
 DEFINITION FOR SUBSTANTIAL IMPROVEMENT.
  
 NEW COMMENT:
 AFTER REVIEWING THE COPY OF THE SURVEY
 SUBMITTED DATING MAY 21, 2006, THE VALUE
 OF THE IMPROVMENTS ON THE PROPERTY ARE
 $272,180.BASE ON A PERMIT VALUE OF
 $250,000.A "SUBSTANTIAL IMPROVMENT
 STILL EXISTS.SHOW HOW THE EXISTING
 BUILDING WILL BE RAISED TO A MINIMUM OF
 6" ABOVE THE BASE FLOOD ELEVATION OF
 7FT.ROOM ADDITION SHALL BE AT OR ABOVE
 THIS ELEVATION AS WELL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-02 Cont ID  
Sent By alange Date 2006-05-02 Time 13:12 Rev Time 1.50
Received By alange Date 2006-05-02 Time 13:12 Sent To  
Notes
2006-05-02 00:00:00 
 DENIED
  
 5.PRODUCT APPROVALS REQUIRED FOR
 FLAT ROOF.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 HAVE APPROVED SET AT JOB SITE PRIOR TO
 INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.CHECK ALL CODE
 SECTIONS USED.
  
 11.PROVISIONS FOR FLOOD HAZARD
 REDUCTION;ALL NEW CONSTRUCTION OR
 SUBSTANTIAL IMPROVEMENT OF ANY EXISTING
 RESIDENTIAL STRUCTURE SHALL HAVE THE
 LOWEST FLOOR, INCLUDING BASEMENT,
 ELEVATED TO SIX INCHES ABOVE THE BASE
 FLOOD ELEVATION OF 7 FT.
 SEE ATTACHED CITY OF WPB MUNI-CODE
 DEFINITION FOR SUBSTANTIAL IMPROVEMENT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By alange Date 2006-03-03 Time 09:59 Rev Time 3.00
Received By alange Date 2006-03-03 Time 09:21 Sent To  
Notes
2006-03-03 00:00:00 
 DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT SPECS FOR OUTDOOR BBQ AND
 HOOD.
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 STRAPS AND TIE-DOWNS, OVERHEAD DOOR AND
 FLAT ROOF.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 11.PROVISIONS FOR FLOOD HAZARD
 REDUCTION;ALL NEW CONSTRUCTION OR
 SUBSTANTIAL IMPROVEMENT OF ANY EXISTING
 RESIDENTIAL STRUCTURE SHALL HAVE THE
 LOWEST FLOOR, INCLUDING BASEMENT,
 ELEVATED TO SIX INCHES ABOVE THE BASE
 FLOOD ELEVATION OF 7 FT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-21 Cont ID  
Sent By btrobaug Date 2006-04-21 Time 07:09 Rev Time 0.75
Received By btrobaug Date 2006-04-21 Time 06:01 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-03 Cont ID  
Sent By btrobaug Date 2006-02-03 Time 10:13 Rev Time 1.00
Received By btrobaug Date 2006-02-03 Time 07:13 Sent To M
Notes
2006-02-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SMALL APPLIANCE CALCULATION IS
 INCORRECT, SEE 220.16, 1500 VA PER
 CIRCUIT.
  
 2} PLEASE LOCATE THE AIR HANDLERS AND
 CONDENSING UNITS ON PLAN. SHOW
 DISCONNECTING MEANS PER 110.26 AND
 440.14, AND RECEPTACLE LOCATIONS PER
 210.63, LIGHTING PER 210.70(A)(3).
  
 3} THE LOAD CALCULATION FOR THE A/C
 SYSTEMS DOES NOT CORRESPOND WITH THE
 MECHANICAL SPECIFICATION. PLEASE
 CORRELATE AND RECALCULATE PER 220.30 OR
 220.31.
  
 4} PLEASE SEE 210.8(A)(7) FOR GFI
 REQUIREMENTS AT THE WET BAR.
  
 5} IF THE TUB UNIT IN THE MASTER BATH IS
 THE SPA REFERENCED IN THE LOAD CALCS,
 SHOW COMPLIANCE WITH 680.43. SWITCHES
 SHALL BE LOCATED AT LEAST 1.5 M (5 FT),
 MEASURED HORIZONTALLY, FROM THE INSIDE
 WALLS OF THE SPA OR HOT TUB IS PART OF
 THAT ARTICLE.
  
 6} A SMOKE DETECTOR IS REQUIRED ON THE
 THIRD LEVEL PER R313.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 09:48 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 09:48 Sent To M
Notes
2006-06-14 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 10:18 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 10:18 Sent To Z
Notes
2006-06-08 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-13 Cont ID  
Sent By adarroug Date 2006-04-13 Time 17:15 Rev Time 0.00
Received By adarroug Date 2006-04-13 Time 17:15 Sent To E
Notes
2006-04-13 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 17:50 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 17:50 Sent To E
Notes
2006-02-02 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-03 Cont ID  
Sent By alange Date 2006-03-03 Time 09:59 Rev Time 0.00
Received By alange Date 2006-01-27 Time 13:18 Sent To  
Notes
2006-01-27 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-06-15 Cont ID  
Sent By tgordon Date 2006-06-15 Time 08:34 Rev Time 0.30
Received By tgordon Date 2006-06-15 Time 08:34 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-04-25 Cont ID  
Sent By tgordon Date 2006-04-25 Time 10:22 Rev Time 0.30
Received By tgordon Date 2006-04-25 Time 10:22 Sent To P
Notes
2006-04-25 00:00:00*** DENIED ***
 1)NO MECHANICAL PLANS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT MECHANICAL PLANS
 FOR REVIEW, OR YOU MAY WISH TO VOID YOUR
 MECHANICAL PERMIT NUMBER 06011030 SO
 YOUR BUILDING PLANS MAY BY-PASS A
 MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-14 Cont ID  
Sent By tgordon Date 2006-02-14 Time 09:34 Rev Time 0.30
Received By tgordon Date 2006-02-14 Time 09:34 Sent To B
Notes
2006-02-14 00:00:00*** DENIED ***
 1) A/C SYSTEM #3 IS NOT ON ENERGY
 CALCULATIONS, PLEASE CORRECT.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 3) JOB ADDRESS NEEDS TO BE ON ALL MECH.
 PLAN SHEETS.
  
 4) MECH. PLANS NEED NAME AND SIGNATURE
 OF DESIGNER. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 5) NEED TO SHOW CLOTHES DRYER VENT
 LOCATION AND TERMINATION ON MECH. PLANS.
  
 6) DUCTS (FLEX) NOT SIZED IN MASTER
 BEDROOM.
  
 7) DOOR TO AHU #2 IS NOT ON BUILDING
 FLOOR PLAN PLEASE CORRECT.
  
 8) CLOSET FOR AHU #3 NOT SHOWING ON
 BUILDING FLOOR PLAN PLEASE CORRECT.
  
 9) 3RD FLOOR BBQ GRILL UNDER COVERED
 DECK NEEDS AN APPROVED HOOD, PER 2004
 FBC/M 505.3 .
  
 10) PLEASE NOTE THAT DUCT WORK IN A
 GARAGE NEEDS TO BE METAL WITH NO
 OPENINGS IN GARAGE, PER 2004 FBC/R
 309.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-15 Cont ID  
Sent By jleech Date 2006-06-15 Time 15:15 Rev Time 0.00
Received By jleech Date 2006-06-15 Time 15:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-04-29 Cont ID  
Sent By jleech Date 2006-04-29 Time 11:04 Rev Time 0.00
Received By jleech Date 2006-04-29 Time 11:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-14 Cont ID  
Sent By jleech Date 2006-02-14 Time 07:22 Rev Time 0.50
Received By jleech Date 2006-02-14 Time 07:22 Sent To M
Notes
2006-02-14 00:00:00DENIED;
 1.SIZE ROOF DRAINS, AND RAIN LEADERS.
 SHOW POINT OF DISCHARGE. (MUST BE 12"
 FROM BUILDING)
 2.RISER DIAGRAM, AUTOMATIC CLOTHES
 WASHER MUST DISCHARGE DOWN STREAM OF THE
 BATHROOM GROUP. FBC-2004 PLUMBING SEC.
 909.1. SEE CHAPTER 11 FOR SIZING OF ROOF
 DRAINS AND LEADERS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-12 Cont ID  
Sent By mmclean Date 2006-06-12 Time 14:15 Rev Time 0.00
Received By mmclean Date 2006-06-12 Time 14:15 Sent To I
Notes
2006-06-12 00:00:00NEW SHEETS -
 1. MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK
  
 NOTE: THE A/C UNIT WILL BE 1FT FROM SIDE
 PROPERTY LINE.
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-31 Cont ID  
Sent By mmclean Date 2006-01-31 Time 17:50 Rev Time 0.00
Received By mmclean Date 2006-01-31 Time 17:50 Sent To I
Notes
2006-01-31 00:00:00NOTE: MUST PULL A SEPERATE PEMIT FOR
 POOL/SPA/DECK.