| Plan Review Stops For Permit 06010964 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-06-26 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-06-26 |
Time |
15:40 |
Rev Time |
1.50 |
| Received By |
alange |
Date |
2006-06-26 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2006-06-26 00:00:00 | | | | DENIED | | | | | | 5.PRODUCT APPROVALS REQUIRED FOR | | | FLAT ROOF. | | | | | | 6.ALL PRODUCT APPROVALS SUBMITTED | | | SHALL HAVE THE FOLLOWING STATE APPROVAL | | | ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS | | | FOR REVIEW PER 2004 FBC R-802.10.1 | | | HAVE APPROVED SET AT JOB SITE PRIOR TO | | | INSTALLATION. | | | | | | 10.ALL PLANS SUBMITTED AFTER OCTOBER, | | | 1, 2005 SHALL BE DESIGNED TO THE 2004 | | | FLORIDA BUILDING CODE.CHECK ALL CODE | | | SECTIONS USED.SEE PAGE 6 CODE SECTIONS | | | AND PAGE 21 FOR ASCE 7-98 | | | | | | 11.PROVISIONS FOR FLOOD HAZARD | | | REDUCTION;ALL NEW CONSTRUCTION OR | | | SUBSTANTIAL IMPROVEMENT OF ANY EXISTING | | | RESIDENTIAL STRUCTURE SHALL HAVE THE | | | LOWEST FLOOR, INCLUDING BASEMENT, | | | ELEVATED TO SIX INCHES ABOVE THE BASE | | | FLOOD ELEVATION OF 7 FT. | | | SEE ATTACHED CITY OF WPB MUNI-CODE | | | DEFINITION FOR SUBSTANTIAL IMPROVEMENT. | | | | | | NEW COMMENT: | | | AFTER REVIEWING THE COPY OF THE SURVEY | | | SUBMITTED DATING MAY 21, 2006, THE VALUE | | | OF THE IMPROVMENTS ON THE PROPERTY ARE | | | $272,180.BASE ON A PERMIT VALUE OF | | | $250,000.A "SUBSTANTIAL IMPROVMENT | | | STILL EXISTS.SHOW HOW THE EXISTING | | | BUILDING WILL BE RAISED TO A MINIMUM OF | | | 6" ABOVE THE BASE FLOOD ELEVATION OF | | | 7FT.ROOM ADDITION SHALL BE AT OR ABOVE | | | THIS ELEVATION AS WELL. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-05-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-05-02 |
Time |
13:12 |
Rev Time |
1.50 |
| Received By |
alange |
Date |
2006-05-02 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2006-05-02 00:00:00 | | | | DENIED | | | | | | 5.PRODUCT APPROVALS REQUIRED FOR | | | FLAT ROOF. | | | | | | 6.ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE APPROVAL ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS | | | FOR REVIEW PER 2004 FBC R-802.10.1 | | | HAVE APPROVED SET AT JOB SITE PRIOR TO | | | INSTALLATION. | | | | | | 9.A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF | | | LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | SHOW HOW PLANS WILL COMPLY WITH THE | | | SECTION(S) SELECTED.2004 FBC EXISTING | | | BUILDING 301.5 | | | | | | 10.ALL PLANS SUBMITTED AFTER OCTOBER, | | | 1, 2004 SHALL BE DESIGNED TO THE 2004 | | | FLORIDA BUILDING CODE.CHECK ALL CODE | | | SECTIONS USED. | | | | | | 11.PROVISIONS FOR FLOOD HAZARD | | | REDUCTION;ALL NEW CONSTRUCTION OR | | | SUBSTANTIAL IMPROVEMENT OF ANY EXISTING | | | RESIDENTIAL STRUCTURE SHALL HAVE THE | | | LOWEST FLOOR, INCLUDING BASEMENT, | | | ELEVATED TO SIX INCHES ABOVE THE BASE | | | FLOOD ELEVATION OF 7 FT. | | | SEE ATTACHED CITY OF WPB MUNI-CODE | | | DEFINITION FOR SUBSTANTIAL IMPROVEMENT. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-03-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-03-03 |
Time |
09:59 |
Rev Time |
3.00 |
| Received By |
alange |
Date |
2006-03-03 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2006-03-03 00:00:00 | | | | DENIED | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.SUBMIT SPECS FOR OUTDOOR BBQ AND | | | HOOD. | | | | | | 4.SIGN OWNER/AGENT ON ENERGY CALCS. | | | | | | 5.PRODUCT APPROVALS REQUIRED FOR | | | STRAPS AND TIE-DOWNS, OVERHEAD DOOR AND | | | FLAT ROOF. | | | | | | 6.ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE APPROVAL ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 7.THOSE PRODUCT APPROVALS WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL.WPB | | | AMENDMENT TO FBC 106.3.3. | | | | | | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS | | | FOR REVIEW PER 2004 FBC R-802.10.1 | | | | | | 9.A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF | | | LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | SHOW HOW PLANS WILL COMPLY WITH THE | | | SECTION(S) SELECTED.2004 FBC EXISTING | | | BUILDING 301.5 | | | | | | 10.ALL PLANS SUBMITTED AFTER OCTOBER, | | | 1, 2004 SHALL BE DESIGNED TO THE 2004 | | | FLORIDA BUILDING CODE. | | | | | | 11.PROVISIONS FOR FLOOD HAZARD | | | REDUCTION;ALL NEW CONSTRUCTION OR | | | SUBSTANTIAL IMPROVEMENT OF ANY EXISTING | | | RESIDENTIAL STRUCTURE SHALL HAVE THE | | | LOWEST FLOOR, INCLUDING BASEMENT, | | | ELEVATED TO SIX INCHES ABOVE THE BASE | | | FLOOD ELEVATION OF 7 FT. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-04-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-04-21 |
Time |
07:09 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2006-04-21 |
Time |
06:01 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-02-03 |
Time |
10:13 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-02-03 |
Time |
07:13 |
Sent To |
M |
|
| Notes |
| 2006-02-03 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE SMALL APPLIANCE CALCULATION IS | | | INCORRECT, SEE 220.16, 1500 VA PER | | | CIRCUIT. | | | | | | 2} PLEASE LOCATE THE AIR HANDLERS AND | | | CONDENSING UNITS ON PLAN. SHOW | | | DISCONNECTING MEANS PER 110.26 AND | | | 440.14, AND RECEPTACLE LOCATIONS PER | | | 210.63, LIGHTING PER 210.70(A)(3). | | | | | | 3} THE LOAD CALCULATION FOR THE A/C | | | SYSTEMS DOES NOT CORRESPOND WITH THE | | | MECHANICAL SPECIFICATION. PLEASE | | | CORRELATE AND RECALCULATE PER 220.30 OR | | | 220.31. | | | | | | 4} PLEASE SEE 210.8(A)(7) FOR GFI | | | REQUIREMENTS AT THE WET BAR. | | | | | | 5} IF THE TUB UNIT IN THE MASTER BATH IS | | | THE SPA REFERENCED IN THE LOAD CALCS, | | | SHOW COMPLIANCE WITH 680.43. SWITCHES | | | SHALL BE LOCATED AT LEAST 1.5 M (5 FT), | | | MEASURED HORIZONTALLY, FROM THE INSIDE | | | WALLS OF THE SPA OR HOT TUB IS PART OF | | | THAT ARTICLE. | | | | | | 6} A SMOKE DETECTOR IS REQUIRED ON THE | | | THIRD LEVEL PER R313.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-14 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-14 |
Time |
09:48 |
Sent To |
M |
|
| Notes |
| 2006-06-14 00:00:00 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-06-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-08 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-08 |
Time |
10:18 |
Sent To |
Z |
|
| Notes |
| 2006-06-08 00:00:00 | TO "Z" BOX/RESUB--NEW SHEETS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-04-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-13 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-13 |
Time |
17:15 |
Sent To |
E |
|
| Notes |
| 2006-04-13 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-02-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-02 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-02 |
Time |
17:50 |
Sent To |
E |
|
| Notes |
| 2006-02-02 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-03-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-03-03 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-01-27 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2006-01-27 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-06-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-15 |
Time |
08:34 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-06-15 |
Time |
08:34 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-04-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-04-25 |
Time |
10:22 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-04-25 |
Time |
10:22 |
Sent To |
P |
|
| Notes |
| 2006-04-25 00:00:00 | *** DENIED *** | | | 1)NO MECHANICAL PLANS WERE SUBMITTED FOR | | | REVIEW. PLEASE SUBMIT MECHANICAL PLANS | | | FOR REVIEW, OR YOU MAY WISH TO VOID YOUR | | | MECHANICAL PERMIT NUMBER 06011030 SO | | | YOUR BUILDING PLANS MAY BY-PASS A | | | MECHANICAL REVIEW. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-02-14 |
Time |
09:34 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-02-14 |
Time |
09:34 |
Sent To |
B |
|
| Notes |
| 2006-02-14 00:00:00 | *** DENIED *** | | | 1) A/C SYSTEM #3 IS NOT ON ENERGY | | | CALCULATIONS, PLEASE CORRECT. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT. | | | | | | 3) JOB ADDRESS NEEDS TO BE ON ALL MECH. | | | PLAN SHEETS. | | | | | | 4) MECH. PLANS NEED NAME AND SIGNATURE | | | OF DESIGNER. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 5) NEED TO SHOW CLOTHES DRYER VENT | | | LOCATION AND TERMINATION ON MECH. PLANS. | | | | | | 6) DUCTS (FLEX) NOT SIZED IN MASTER | | | BEDROOM. | | | | | | 7) DOOR TO AHU #2 IS NOT ON BUILDING | | | FLOOR PLAN PLEASE CORRECT. | | | | | | 8) CLOSET FOR AHU #3 NOT SHOWING ON | | | BUILDING FLOOR PLAN PLEASE CORRECT. | | | | | | 9) 3RD FLOOR BBQ GRILL UNDER COVERED | | | DECK NEEDS AN APPROVED HOOD, PER 2004 | | | FBC/M 505.3 . | | | | | | 10) PLEASE NOTE THAT DUCT WORK IN A | | | GARAGE NEEDS TO BE METAL WITH NO | | | OPENINGS IN GARAGE, PER 2004 FBC/R | | | 309.1.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-06-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-06-15 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-06-15 |
Time |
15:15 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-04-29 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-04-29 |
Time |
11:04 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-02-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-02-14 |
Time |
07:22 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2006-02-14 |
Time |
07:22 |
Sent To |
M |
|
| Notes |
| 2006-02-14 00:00:00 | DENIED; | | | 1.SIZE ROOF DRAINS, AND RAIN LEADERS. | | | SHOW POINT OF DISCHARGE. (MUST BE 12" | | | FROM BUILDING) | | | 2.RISER DIAGRAM, AUTOMATIC CLOTHES | | | WASHER MUST DISCHARGE DOWN STREAM OF THE | | | BATHROOM GROUP. FBC-2004 PLUMBING SEC. | | | 909.1. SEE CHAPTER 11 FOR SIZING OF ROOF | | | DRAINS AND LEADERS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-06-12 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-06-12 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-06-12 |
Time |
14:15 |
Sent To |
I |
|
| Notes |
| 2006-06-12 00:00:00 | NEW SHEETS - | | | 1. MUST PULL A SEPERATE PERMIT FOR | | | POOL/SPA/DECK | | | | | | NOTE: THE A/C UNIT WILL BE 1FT FROM SIDE | | | PROPERTY LINE. | | | SEC 94-303 MECHANICAL/POOL | | | EQUIPMENT/GENERATOR MAY NOT PROJECT MORE | | | THAN FOUR FEET INTO A SETBACK. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-01-31 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-01-31 |
Time |
17:50 |
Sent To |
I |
|
| Notes |
| 2006-01-31 00:00:00 | NOTE: MUST PULL A SEPERATE PEMIT FOR | | | POOL/SPA/DECK. |
|
|